China High Quality Aluminum Conductor, XLPE Insulation ABC Cable, Aerial Cable, Service Cable
Product Description
ABC cable is suitable for transmitting line and distributing line of rated voltage 0.6/1KV and others.It is widely used at tall buildings,traveling development area and rural area or other place the cost of underground network is expensive.
Basic Information
Code Name
ABC
Rated Voltage (Uo/U)
0.6/1KV
Temperature Range
-15ºC-90ºC
—————————————————————————————————————————–
CONSTRUCTION
Conductor: Copper or Aluminium
Insulation: XLPE
Normally,ABC Cable(ABC Bundled Cable-Aerial Cable) do not use copper,because Aluminium Cost is high,most of our customers use aluminium.
—————————————————————————————————————————–
CABLE STANDARDS
Chinese National Standards, IEC,SANS 1418-1, SANS1418-2, ASTMB230, ASTMB231,ASTM B398,ASTM B399, NF C33-209 and etc. upon request.
—————————————————————————————————————————–
Aerial Bundle Conductor-ABC(South Africa Standard Sizes)-SANS 1418-1
Table 01 Aerial Bundled Cable-ABC-AS NZS 3506.1
1+1 Structure | ||||||||||
Phase Conductor | Neutral Conductor | Completed Cable | ||||||||
Section | Insulation Thickness | Minimum number of wires | Max. dc resistance at 20°C | Section | Insulation Thickness | Minimum number of wires | Max. dc resistance at 20°C | Minimum breaking load | Approx. Overall Diameter | Approx. Weight Of Cable |
mm2 | mm | No. | ohm/km | mm2 | mm | No. | ohm/km | KN | mm | Kg/km |
1×16 | 1.3 | 6 | 1.91 | 1×16 | 1.3 | 6 | 1.91 | 4.4 | 15.0 | 140 |
1×25 | 1.3 | 6 | 1.20 | 1×25 | 1.3 | 6 | 1.20 | 7.0 | 17.6 | 210 |
1×35 | 1.5 | 6 | 0.868 | 1×35 | 1.5 | 6 | 0.868 | 9.8 | 19.6 | 270 |
1×50 | 1.5 | 6 | 0.641 | 1×50 | 1.5 | 6 | 0.641 | 14.0 | 22.8 | 370 |
1×95 | 1.7 | 15 | 0.320 | 1×95 | 1.7 | 15 | 0.320 | 26.6 | 30.6 | 680 |
2+1 Structure | ||||||||||
Phase Conductor | Neutral Conductor | Completed Cable | ||||||||
Section | Insulation Thickness | Minimum number of wires | Max. dc resistance at 20°C | Section | Insulation Thickness | Minimum number of wires | Max. dc resistance at 20°C | Minimum breaking load | Approx. Overall Diameter | Approx. Weight Of Cable |
mm2 | mm | No. | ohm/km | mm2 | mm | No. | ohm/km | KN | mm | Kg/km |
2×25 | 1.3 | 6 | 1.20 | 1×25 | 1.3 | 6 | 1.20 | 10.5 | 19.0 | 310 |
2×35 | 1.3 | 6 | 0.868 | 1×35 | 1.3 | 6 | 0.868 | 14.7 | 21.1 | 410 |
2×50 | 1.5 | 6 | 0.641 | 1×50 | 1.5 | 6 | 0.641 | 21.0 | 24.6 | 550 |
3+1 Structure | ||||||||||
Phase Conductor | Neutral Conductor | Completed Cable | ||||||||
Section | Insulation Thickness | Minimum number of wires | Max. dc resistance at 20°C | Section | Insulation Thickness | Minimum number of wires | Max. dc resistance at 20°C | Minimum breaking load | Approx. Overall Diameter | Approx. Weight Of Cable |
3×16 | 1.3 | 6 | 1.91 | 1×16 | 1.3 | 6 | 1.91 | 8.8 | 18.1 | 290 |
3×25 | 1.3 | 6 | 1.20 | 1×25 | 1.3 | 6 | 1.20 | 14.0 | 21.2 | 410 |
3×35 | 1.3 | 6 | 0.868 | 1×35 | 1.3 | 6 | 0.868 | 19.6 | 23.7 | 550 |
3×50 | 1.5 | 6 | 0.641 | 1×50 | 1.5 | 6 | 0.641 | 28.0 | 27.5 | 740 |
3×70 | 1.5 | 12 | 0.443 | 1×70 | 1.5 | 12 | 0.443 | 39.2 | 31.9 | 1000 |
3×95 | 1.7 | 15 | 0.320 | 1×95 | 1.7 | 15 | 0.320 | 53.2 | 36.9 | 1370 |
3×120 | 1.7 | 15 | 0.253 | 1×120 | 1.7 | 15 | 0.253 | 67.2 | 40.6 | 1690 |
3×150 | 1.7 | 15 | 0.206 | 1×150 | 1.7 | 15 | 0.206 | 84.0 | 43.9 | 2020 |
BS7884-1997 | |||||
Nominal Area | Stranding | Diameter of conductor | Linear mass | Rated strength | D.C. resistance at 20°C |
mm2 | No./mm | mm | Kg/km | KN | Ω/km |
10 | 7/1.35 | 4.05 | 89.82 | 3.752 | 1.829 |
14 | 7/1.6 | 4.8 | 126.2 | 5.627 | 1.30300 |
16 | 3/2.65 | 5.72 | 148.30 | 6.194 | 1.10600 |
16 | 7/1.7 | 5.10 | 142.40 | 5.946 | 1.15400 |
25 | 7/2.1 | 6.30 | 217.30 | 9.073 | 0.75630 |
32 | 3/3.75 | 8.10 | 296.90 | 12.4 | 0.55200 |
32 | 7/2.46 | 7.38 | 298.20 | 12.442 | 0.54970 |
35 | 7/2.5 | 7.50 | 308.00 | 12.86 | 0.53370 |
50 | 7/3.00 | 9.00 | 443.50 | 18.52 | 0.37060 |
50 | 19/1.8 | 9.00 | 435.80 | 17.7 | 0.38190 |
70 | 7/3.55 | 10.65 | 621.10 | 25.93 | 0.26460 |
70 | 19/2.1 | 10.50 | 593.20 | 24.09 | 0.28060 |
95 | 19/2.5 | 12.50 | 840.70 | 34.14 | 0.19800 |
100.0 | 7/4.3 | 12.90 | 911.20 | 36.54 | 0.18100 |
120.0 | 19/2.8 | 14.00 | 1055.00 | 42.83 | 0.15780 |
125.0 | 19/2.9 | 14.50 | 1131.00 | 45.94 | 0.14710 |
150.0 | 19/3.2 | 16.00 | 1377.00 | 55.94 | 0.12080 |
150.0 | 37/2.25 | 15375.00 | 1334.00 | 53.88 | 0.12640 |
185.0 | 19/3.55 | 17.75 | 1695.00 | 68.86 | 0.09815 |
185.0 | 37/2.5 | 17.75 | 1647.00 | 66.49 | 0.10240 |
Phase | Phase | Phase | Approx.Overall Diameter | Max. D.C. Resistance of Conductor at 20 Centigrade | |||
AAC+UV-XLPE | Compact Conductor | UV-XLPE Insulation | |||||
No.X Normal Cross Section of Cores | No.of Al Wires | Overall Diameter | Normal Thickness | Min. | Diameter | ||
No. X mm 2 | – | mm | mm | mm | mm | mm | ohm/km |
1 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 6.05 | 3.08 |
1 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 7.20 | 1.91 |
1 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 8.40 | 1.20 |
1 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 9.80 | 0.868 |
1 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 11.10 | 0.641 |
1 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 12.60 | 0.443 |
1 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 14.80 | 0.320 |
1 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 16.20 | 0.253 |
1 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 18.20 | 0.206 |
1 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 20.20 | 0.164 |
1 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 22.80 | 0.125 |
2 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 12.10 | 3.08 |
2 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 14.40 | 1.91 |
2 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 16.80 | 1.20 |
2 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 19.60 | 0.868 |
2 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 22.20 | 0.641 |
2 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 25.20 | 0.443 |
2 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 29.60 | 0.320 |
2 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 32.40 | 0.253 |
2 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 36.40 | 0.206 |
2 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 40.40 | 0.164 |
2 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 45.60 | 0.125 |
3 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 13.07 | 3.08 |
3 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 15.55 | 1.91 |
3 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 18.14 | 1.20 |
3 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 21.17 | 0.868 |
3 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 23.98 | 0.641 |
3 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 27.22 | 0.443 |
3 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 31.97 | 0.320 |
3 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 34.99 | 0.253 |
3 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 39.31 | 0.206 |
3 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 43.63 | 0.164 |
3 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 49.25 | 0.125 |
4 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 14.64 | 3.08 |
4 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 17.42 | 1.91 |
4 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 20.33 | 1.20 |
4 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 23.72 | 0.868 |
4 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 26.86 | 0.641 |
4 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 30.49 | 0.443 |
4 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 35.82 | 0.320 |
4 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 39.20 | 0.253 |
4 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 44.04 | 0.206 |
4 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 48.88 | 0.164 |
4 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 55.18 | 0.125 |
- Next: Copper/Aluminum XLPE Insulated PVC Sheathed Power Cable Rated Voltage up to 35kv
- Previous: PVC Insualted Wires, Copper Conductor Electrical Wire BV Building Wire
Contact us
Similar Or Related
-
0.6/1kv Single Core Aluminum Conductor XLPE Insulation Electrical Overhead Cable
-