Bcc, Bare Copper Stranded Conductor (BS EN 13602)

Bcc, Bare Copper Stranded Conductor (BS EN 13602)

Bcc, Bare Copper Stranded Conductor (BS EN 13602)

BCC

Bare

Stranded

Overhead

Copper

Bare

Bare

Round Wire

Transmission

ISO9001, CCC

Boan

BS En 13602

7-70

1.5-500 mm2

2

DingAn or OEM

Heated Steel-Wooden Drum/Wooden Drum

SGS

Jiangsu Yixing, China

7413000000

Product Description

BCC, Bare Copper Class 2 Conductor (BS EN 13602)
Applications
For use in electrical grounding systems and on insulators for overhead transmission and distribution applications. Stranded conductors offer greater flexibility than solid.

Cable Standards
BS EN 13602, BS EN 60228

Construction
Conductor
Class 2 annealed stranded copper conductor according to BS EN 60228 (previously BS 6360)

NOMINAL CROSS SECTIONAL AREA NO. OF WIRES DIAMETER OF WIRES DIAMETER OF CONDUCTORS Minimum Elongation Minimum Tensile Strength NOMINAL WEIGHT MAXIMUM DC RESISTANCE AT 20°C
mm2 mm mm % N/mm2 kg/km ohms/km
1.5 7 0.53 1.59 24 200 13 12.1
2.5 7 0.67 2.01 24 200 21 7.41
4 7 0.85 2.55 24 200 35 4.61
6 7 1.05 3.15 26 200 52 3.08
10 7 1.35 3.85 26 200 87 1.83
16 7 1.74 4.8 28 200 137 1.15
25 7 2.19 5.8 28 200 215 0.727
35 7 2.62 6.9 28 200 300 0.524
50 10 2.62 8.2 28 200 410 0.387
70 14 2.62 9.7 28 200 595 0.268
95 19 2.62 11.4 28 200 820 0.193
120 24 2.62 13.1 28 200 1040 0.153
150 30 2.62 14.2 28 200 1280 0.124
185 37 2.62 15.8 28 200 1600 0.0991
240 48 2.62 18.6 28 200 2100 0.0754
300 58 2.62 20.4 28 200 2700 0.0601
400 55 3 26 33 200 3400 0.047
500 70 3 30 33 200 4400 0.0366

Tags: , ,