Bare Conductor/ Aluminum Conductor Aluminum Alloy Reinforced/Acar
Bare Conductor/ Aluminum Conductor Aluminum Alloy Reinforced/Acar
ACSR IEC 61089 standard
Jp
ACSR IEC 61089 Standard
ISO, CE, SABS
Aluminum Conductor Aluminum Alloy Reinforced
Round Wire
Non
Bare
DC Cable
Low and Medium Voltage Cable
Overhead
by Buyer's Request
JP
Wooden Drum
any standard
China
7614900000
Product Description
Bare Conductor/ Aluminum Conductor Aluminum Alloy Reinforced/Acar
Application
Used as bare overhead conductor for primary and secondary distribution. Designed utilizing a high-strength aluminum alloy to achieve a high strength-to-weight ratio; affords better sag characteristics. Aluminum alloy gives AAAC higher resistance to corrosion than ACSR.
Application
Used as bare overhead conductor for primary and secondary distribution. Designed utilizing a high-strength aluminum alloy to achieve a high strength-to-weight ratio; affords better sag characteristics. Aluminum alloy gives AAAC higher resistance to corrosion than ACSR.
Specification
Code Number | A2 Conductor | A3 Conductor | Max.D.C. Resistance of Conductor at 20ºC | ||||||||
Number of Wires | Diameter of Wires | Diameter of Conductor | Approx. Weight | Rated Strength | Number of Wires | Diameter of Wires | Diameter of Conductor | Approx. Weight | Rated Strength | ||
mm² | – | mm | mm | kg/km | daN | – | mm | mm | kg/km | daN | Ω/km |
16 | 7 | 1.83 | 5.49 | 50.4 | 5.43 | 50.8 | 6.04 | 50.8 | 6.04 | 1.7896 | |
25 | 7 | 2.29 | 6.87 | 78.7 | 8.49 | 1.1453 | 79.5 | 9.44 | 79.5 | 9.44 | 1.1453 |
40 | 7 | 2.89 | 8.67 | 125.9 | 13.58 | 0.7158 | 127.1 | 15.1 | 127.1 | 15.1 | 0.7158 |
63 | 7 | 3.63 | 10.8 | 198.3 | 21.39 | 0.4545 | 200.2 | 23.06 | 200.2 | 23.06 | 0.4545 |
100 | 19 | 2.78 | 13.9 | 316.3 | 33.95 | 0.2877 | 319.3 | 37.76 | 319.3 | 37.76 | 0.2877 |
125 | 19 | 3.10 | 15.5 | 395.4 | 42.44 | 0.2302 | 399.2 | 47.20 | 399.2 | 47.20 | 0.2302 |
160 | 19 | 3.51 | 17.55 | 506.1 | 54.32 | 0.1798 | 511.0 | 58.56 | 511.0 | 58.56 | 0.1798 |
200 | 19 | 3.93 | 19.65 | 623.7 | 67.91 | 0.1439 | 638.7 | 73.20 | 638.7 | 73.20 | 0.1439 |
250 | 19 | 4.39 | 21.95 | 790.8 | 84.68 | 0.1151 | 798.4 | 91.50 | 798.4 | 91.50 | 0.1151 |
315 | 37 | 3.53 | 24.71 | 998.9 | 106.95 | 0.0916 | 1008.4 | 115.29 | 1008.4 | 115.29 | 0.0916 |
400 | 37 | 3.98 | 27.86 | 1268.4 | 135.81 | 0.0721 | 1280.5 | 146.4o | 1280.5 | 146.4o | 0.0721 |
450 | 37 | 4.22 | 29.54 | 1426.9 | 152.79 | 0.0641 | 1440.5 | 164.70 | 1440.5 | 164.70 | 0.0641 |
500 | 37 | 4.45 | 31.15 | 1585.5 | 169.76 | 0.0577 | 1600.6 | 183.oo | 1600.6 | 183.oo | 0.0577 |
560 | 61 | 3.67 | 33.03 | 1778.4 | 190.14 | 0.0516 | 1795.3 | 204.95 | 1795.3 | 204.95 | 0.0516 |
630 | 61 | 3.89 | 35.01 | 2000.7 | 213.90 | 0.0458 | 2019.8 | 230.58 | 2019.8 | 230.58 | 0.0458 |
710 | 61 | 4.13 | 37.17 | 2254.8 | 241.07 | 0.0407 | 2276.2 | 259.86 | 2276.2 | 259.86 | 0.0407 |
800 | 61 | 4.38 | 39.42 | 2540.6 | 271.62 | 0.0361 | 2564.8 | 282.80 | 2564.8 | 282.80 | 0.0361 |
900 | 91 | 3.81 | 41.91 | 2861.1 | 305.58 | 0.0632 | 2888.3 | 329.40 | 2888.3 | 329.40 | 0.0321 |
1000 | 91 | 4.01 | 44.11 | 3179.0 | 339.53 | 0.0289 | 3209.3 | 366.00 | 3209.3 | 366.00 | 0.0289 |
1120 | 91 | 4.25 | 46.75 | 3560.5 | 380.27 | 0.0258 | 3594.4 | 409.92 | 3594.4 | 409.92 | 0 0258 |
1250 | 91 | 4.49 | 49.39 | 3973.7 | 424.41 | 0 0231 | – | – | – | – | – |
Workshop:
What kinds of products does Jiapu Cable manufacture?
1)Bare Conductor ,such as AAC,AAAC,ACSR,ACAR,AACSR,ACSR/AW and so on;
2)Aerial Bundled Cable (1kV-35kV ),such as Duplex,Triplex,Quadruplex Drop Wires and so on;
3)PVC Insulated (Flexible ) Wire ;
4) PVC Insulated and Sheathed (Armoured) Power Cable;
5)Low, Medium, High Voltage (1kV-220kV) XLPE Insulated (Armoured) Power Cable;
6)Welding Cable, Control Cable, Concentric Cable, Rubber Sheathed Cable and so on;
- Next: 8000 Series Aluminum Alloy XLPE Insulation Concentric Cable, Electric Wire, Electric Cable
- Previous: Hot Sale AAC Overhead Power Cable