Aluminum Cord-Plex Isolated Multiplex 1kv Ca, Caa Ou Cal Cable

Aluminum Cord-Plex Isolated Multiplex 1kv Ca, Caa Ou Cal Cable

Aluminum Cord-Plex Isolated Multiplex 1kv Ca, Caa Ou Cal Cable

Cabo Multiplex 1kv

Hongda

0.6/1 Kv Aluminum Multiplexed Cable

ISO, CCC, CE

Aluminum

Round Wire

N/a

XLPE

DC & AC

Low and Medium Voltage Cable

Construction, Overhead, Industrial, Overhead Power Lines

NBR 8182, IEC60502

XLPE or Polyethylene

1kv

Max 65c

Hongda Cable

Wooden Drum or as Customer Requirement

6mm2 to 120mm2

China

8544492100

Product Description

ALUMINUM CORD-PLEX WITH Isolated CA, CAA OU CAL Cable
Cabo Multiplex 1kv

1.1 APPLICATION

The self-sustaining multiplexed power cable is designed for power distribution cables for voltages up to 0.6/1 kV, in permanent aerial installations to posts or building facings.
Power Multiplexed Self-supporting cables with PE Extruded Insulation (thermoplastic) or XLPE (Thermoset) for voltages up to 0.6 / 1 kV.
Suitable for all urban network of secondary distribution and also for rural secondary

1.2 CONSTRUCTION

Phase conductor: Aluminum wires 1350, stringing class 2, compact, acc. to NM 280.

Insulation: Polyethylene compound (PE) 70° or cross-linked polyethylene (XLPE) 90°C, weather resistant.
Identificación:
1 phase: black
2 phases: black and gray
3 phases: black, grey and red

Neutral conductor:
Bare aluminum (Al), aluminum alloy (CAL), or steel core (ACSR) String class 2 regular circled
Neutral conductor insulation: if requested, in XLPE in light blue.

1.3 ELECTRICAL CHARACTERISTICS

Maximum Operating Temperatures
In continuous regime: 90°C
In overload: 130°C
In short circuit: 250°C

1.4 Reference Standards

ABNT NBR 8182 – Self-sustained multiplex power cables with extruded insulation of PE or XLPE, for voltages up to 0,6/1 kV – Performance requirements.
ABNT NBR NM 280 – Conductors of insulated cables (IEC 60228, MOD).
ABNT NBR 10298 – Bare cables with alloy aluminum-magnesium-silicon, for overhead lines – Specification.

1.5 Conditioning

In rolls of 100 m or reels, for section up to 25 mm². For other constructions, in reels.

1.6 CONDUCTOR INDENTIFICATION:
DUPLEX: Black
TRIPLEX: Black – Gray
QUADRUPLEX: Black – Gray – Red
NEUTRAL WHEN INSULATED: Light Blue

Format 1: *Format 2: *Format 3:    

Duplex

Phase 1: Black.
Neutral: Nu.

 

Duplex 

Phase 1: Black.
Neutral: Blue.

Triplex

Phase 1: Black.
Phase 2: Gray.
Neutral: Bare

Triplex

Phase 1: Black.
Phase 2: Black.
Neutral: Bare.

Triplex

Phase 1: Black.
Phase 2: Gray.
Neutral: Blue.

Quadruplex

Phase1: Black.
Phase 2: Gray.
Phase 3: Red.
Neutral: Nu

Quadruplex

Phase 1: Black.
Phase 2: Black.
Phase 3: Black.
Neutral: Bare.

Quadruplex

Phase 1: Black.
Phase 2: Gray.
Phase 3: Red.
Neutral: Blue.

* Formats 2 and 3 only by special request.

Conduspar – Multiplex Cable 1 kV
Nominal Dimensions

Cables with Neutral Aluminum – CA
Nominal Section Area
(mm2)
Condutor Phase Diameter (mm) Insulation  Neutral Conductor – CA Bursting Load (daN) Wiring Diameter (mm) Nominal Weight (kg/km)
Thickness (mm) Diameter (mm)  Wires x Diameter(mm) Diameter (mm)
1x1x10+10 3,7 1,2 6,1 7 x 1,36 4,2 195 10,6 71
1x1x16+16 4,7 1,2 7,1 7 x 1,70 5,2 300 12,7 106
1x1x25+25 5,9 1,4 8,7 7 x 2,06 6,3 446 15,5 160
1x1x35+35 7,0 1,6 10,2 7 x 2,50 7,7 614 17,9 270
1x1x50+50 8,6 1,6 11,3 7 x 3,00 9,2 836 20,5 348
1x1x70+70 9,5 1,8 13,1 7 x 3,45 10,6 1081 23,7 449
2x1x10+10 3,7 1,2 6,1 7 x 1,36 4,2 195 12,2 168
2x1x16+16 4,7 1,2 7,1 7 x 1,70 5,2 300 14,4 255
2x1x25+25 5,9 1,4 8,7 7 x 2,06 6,3 446 17,6 356
2x1x35+35 7,0 1,6 10,2 7 x 2,50 7,7 614 20,2 406
2x1x50+50 8,6 1,6 11,3 7 x 3,00 9,2 836 22,8 554
2x1x70+70 9,5 1,8 13,1 7 x 3,45 10,6 1081 26,4 713
3x1x10+10 3,7 1,2 6,1 7 x 1,36 4,2 195 14,0 157
3x1x16+16 4,7 1,2 7,1 7 x 1,70 5,2 300 16,4 230
3x1x25+25 5,9 1,4 8,7 7 x 2,06 6,3 446 20,1 350
3x1x35+35 7,0 1,6 10,2 7 x 2,50 7,7 614 23,7 487
3x1x50+50 8,1 1,6 11,3 7 x 3,00 9,2 836 26,7 640
3x1x70+70 9,5 1,8 13,1 7 x 3,45 10,6 1081 31,0 892
3x1x95+95 11,2 2,0 15,2 19 x 2,50 12,8 1613 36,2 1.225
3x1x120+120 12,6 2,0 16,6 19 x 2,90 14,8 2054 40,1 1.531

 

Cables with Neutral Aluminum Alloy – CAL
Nominal Section Area
(mm2)
Condutor Phase Diameter (mm) Insulation  Neutral Conductor – CAL Bursting Load (daN) Wiring Diameter (mm) Nominal Weight (kg/km)
Thickness (mm) Diameter (mm)  Wires x Diameter(mm) Diameter (mm)
3x1x35+35 7,0 1,6 10,2 7 x 2,50 7,65 1092 23,7 490
3x1x35+50 7,0 1,6 10,2 7 x 3,00 9,18 1572 24,6 530
3x1x50+35 8,1 1,6 11,3 7 x 2,50 7,65 1092 25,8 625
3x1x50+50 8,1 1,6 11,3 7 x 3,00 9,18 1572 26,7 665
3x1x70+50 9,5 1,8 13,1 7 x 3,00 9,18 1572 30,1 895
3x1x70+70 9,5 1,8 13,1 7 x 3,45 10,56 1991 31,0 920
3x1x95+70 11,2 2,0 15,2 7 x 3,45 10,56 1991 34,9 1.12
3x1x120+70 12,6 2,0 16,6 7 x 3,45 10,56 1991 37,5 1.375

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information.