Aluminum Conductor XLPE Power Cable 0.6/1kv Low Voltage
Product Description
1. The PVC insulated power electric cable
The conductor can be copper or aluminium; Be strands or solid
The electrical cable can be very solid or flexible
The insualtion is PVC
The Jacket/Sheath is PVC
Armored or without armored
Class 2 stranded conductors for single-core and multi-core cables | |||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 |
Nominal crosssectional area | Minimum number of wires in the conductor | Maximum resistance of conductor at 20ºC | |||||||
Circular | Circular compacted | Shaped | Annealed copper conductor | Aluminium or aluminium alloy conductor | |||||
Cu | Al | Cu | Al | Cu | Al | Plain wires | Metal-coated wires | ||
mm2 | Ω/KM | Ω/KM | Ω/KM | ||||||
0.5 | 7 | 36 | 36.7 | ||||||
0.75 | 7 | 24.5 | 24.8 | ||||||
1 | 7 | 18.1 | 18.2 | ||||||
1.5 | 7 | 6 | 12.1 | 12.2 | |||||
2.5 | 7 | 6 | 7.41 | 7.58 | |||||
4 | 7 | 6 | 4.61 | 4.7 | |||||
6 | 7 | 6 | 3.08 | 3.11 | |||||
10 | 7 | 7 | 6 | 6 | 1.83 | 1.84 | 3.08 | ||
16 | 7 | 7 | 6 | 6 | 1.15 | 1.16 | 1.91 | ||
25 | 7 | 7 | 6 | 6 | 6 | 6 | 0.727 | 0.734 | 1.2 |
35 | 7 | 7 | 6 | 6 | 6 | 6 | 0.524 | 0.529 | 0.868 |
50 | 19 | 19 | 6 | 6 | 6 | 6 | 0.387 | 0.391 | 0.641 |
70 | 19 | 19 | 12 | 12 | 12 | 12 | 0.268 | 0.27 | 0.443 |
95 | 19 | 19 | 15 | 15 | 15 | 15 | 0.193 | 0.195 | 0.32 |
120 | 37 | 37 | 18 | 15 | 18 | 15 | 0.153 | 0.154 | 0.253 |
150 | 37 | 37 | 18 | 15 | 18 | 15 | 0.124 | 0.126 | 0.206 |
185 | 37 | 37 | 30 | 30 | 30 | 30 | 0.0991 | 0.1 | 0.164 |
240 | 37 | 37 | 34 | 30 | 34 | 30 | 0.0754 | 0.0762 | 0.125 |
300 | 61 | 61 | 34 | 30 | 34 | 30 | 0.0601 | 0.0607 | 0.1 |
400 | 61 | 61 | 53 | 53 | 53 | 53 | 0.047 | 0.0475 | 0.0778 |
500 | 61 | 61 | 53 | 53 | 53 | 53 | 0.0368 | 0.0369 | 0.0605 |
630 | 91 | 91 | 53 | 53 | 53 | 53 | 0.0283 | 0.0286 | 0.0469 |
800 | 91 | 91 | 53 | 53 | 0.0221 | 0.0224 | 0.0367 | ||
1000 | 91 | 91 | 53 | 53 | 0.0176 | 0.0177 | 0.0291 |
Armoured material: Can be steel tape or steel wire or others as your request!
The recommended nominal cross section is from 1.5 sq mm to 400 sqmm
The core number can be single or multi
The Voltage is 0.6/1kV
The long-time working temperature of cable should not be higher than 70 celsius
When core is in short-circuit(max 5s) the temperature should not be exceed 160 celsius
While installation the ambient temperature should not be lower than 0 celsius
2. The XLPE insulated power electric cable
The conductor can be copper or aluminium; Be strands or solid
The electrical cable can be very solid or flexible
The insualtion is PVC
The Jacket/Sheath is PVC
Armored or without armored
Armoured material: Can be steel tape or steel wire or others as your request!
The recommended nominal cross section is from 1.5 sq mm to 400 sqmm
The core number can be single or multi
The Voltage is 0.6/1, 3.6/6, 6/6, 6/10, 8.7/10, 8.7/15, 21/35, 26/35 kv
The long-time working temperature of cable should not be higher than 90 celsius
When core is in short-circuit(max 5s) the temperature should not be exceed 250 celsius
While installation the ambient temperature should not be lower than 0 celsius
The OEM and customized productes will also be welcomed! !
Contact us
Similar Or Related
-
15kV 3 Core 4/0AWG Aluminum Conductor XLPE Insulated SWA Armored MV Power Cable
-
XLPE Insulated Aerial Service Drop Cable Conductor #3AWG Duplex ICEA S-66-524 NEMA WC7
-
3Cx185mm2 XLPE Insulated Copper Tape Screened Galvanized Steel Wire Armored Power Cable 33kV
-
0.6/1kV 4Cx500mm2 Copper Conductor PVC Insulated SWA Armored LV Power Cable IEC 60502-1
-
Low Voltage Single Core Power Cable 1X300 mm2 N2XCH CU/XLPE/CWS/LSF 0.6/1kV