Aluminum Alloy Overhead AAAC Conductor

Aluminum Alloy Overhead AAAC Conductor

Aluminum Alloy Overhead AAAC Conductor

Rmjt

ISO9001, CCC, BV

Overhead

Round Wire

Bare

Bare

Aluminium Alloy

Overhead

Stranded

Bare

High Voltage

7, 19, 37, 61, 91

AAAC Conductor

Power Transimision

Yes

RMJT

Wooden Drum

16mm2, 25mm2, 35mm2…1000mm2

China

7614900000

Product Description

Electric Cable Aluminium Alloy Condutor AAAC Conductor Aluminium Wire with ISO Certificate

1.Application
The AAAC is used for overhead power transmission lines , especially the electric power augmentation of old transmission lines. We specialized in the research and application of AAAC for almost ten years. When replacing the aluminium conductor steel reinforced , the AAAC can save 5-8% of the construction cost. This AAAC covers aluminium alloy (hard solution, heat-treated, cold worked, and artifically aged) round wires for electrical purposes to be used as component wires of aluminium alloy conductor and aluminium alloy conductor steel reinforced.

2.Standard:
ASTM B399,BS EN50183 ,BS 3242,DIM 48201,IEC 61089

3.Specification
All Aluminum Alloy Conductors ASTM B 399

Area Stranding Approx. Dia. Weight Nominal Breaking Load D.C. Resistance at 20ºC Standard Length
Nominal Actual
AWG or MCM mm2 mm mm kg/km kN ohm/km m±5%
6 13.30 7/1.554 4.67 37 4.22 2.5199 3500
4 21.15 1/1.961 5.89 58 6.71 1.5824 3000
2 33.63 7/2.474 7.42 93 10.68 0.9942 2500
1/0 53.48 7/3.119 9.36 148 16.97 0.6256 2000
2/0 67.42 7/3.503 10.51 186 20.52 0.4959 3500
3/0 85.03 7/3.932 11.80 234 25.86 0.3936 3000
4/0 107.23 7/4.417 13.26 296 32.63 0.3119 2000
250 126.66 19/2.913 14.57 349 38.93 0.2642 2000
300 152.10 19/63.193 15.97 419 46.77 0.2199 3000
350 177.35 19/3.447 17.24 489 52.25 0.1887 3000
400 202.71 19/3.686 18.43 559 59.74 0.1650 2500
450 228.00 19/3.909 19.55 629 67.19 0.1467 2000
500 253.35 19/4.120 20.60 698 74.64 0.1321 2000
550 278.60 37/3.096 21.67 768 83.80 0.1202 2000
600 303.80 37/3.233 22.63 838 91.38 0.1102 2000
650 329.25 37/3.366 23.56 908 97.94 0.1016 2000
700 354.55 37/3.493 24.45 978 102.20 0.0944 3500
750 380.20 37/3.617 25.32 1049 109.60 0.0880 3000
800 405.15 37/3.734 26.14 1117 116.80 0.0826 3000
900 456.16 37/3.962 27.73 1258 131.50 0.0733 3000
1000 506.71 37/4.176 26.23 1300 146.10 0.0660 2500

 

6201 All Aluminum Alloy Conductor                            ASTM B399                          
Code Name Area Size&Stranding of 
ACSR with equal 
diameter
No. and 
diameter 
Overall 
diameter
Weight Nominal
 breaking load
Nominal Actual
MCM mm2 AWG or MCM mm mm kg/km kN
AKRON 30.58 15.48 6 7/1.68 5.04 42.7 4.92
ALTON 48.69 24.71 4 7/2.12 6.35 68 7.84
AMES 77.47 39.22 2 7/2.67 8.02 108 12.45
AZUSA 123.3 62.38 1/0 7/3.37 10.11 172 18.97
ANAHEIM 155.4 78.65 2/0 7/3.78 11.35 217 23.93
AMHERST 195.7 99.22 3/0 7/4.25 12.75 273 30.18
ALLIANCE 246.9 125.1 4/0 7/4.77 14.31 345 38.05
BUTTE 312.8 158.6 266.8 19/3.26 16.3 437 48.76
CANTON 394.5 199.9 336.4 19/3.66 18.3 551 58.91
CAIRO 465.4 235.8 397.5 19/3.98 19.88 650 69.48
DARIEN 559.5 283.5 477 19/4.36 21.79 781 83.52
ELGIN 652.4 330.6 556.5 19/4.71 23.54 911 97.42
FLINT 740.8 375.3 636 37/3.59 25.16 1035 108.21
GREELEY 927.2 469.8 795 37/4.02 28.14 1295 135.47

 

AAAC (Characteristics of A3 Conductors)                  IEC 61089
Code number Area Number of wires Diameter Linear mass Rated strength D.C resistance
Wire Cond
mm2   mm mm kg/km kN Ohm/km
16 18.6 7 1.84 5.52 50.8 6.04 1.7896
25 29 7 2.3 6.9 79.5 9.44 1.1453
40 46.5 7 2.91 8.72 127.1 15.1 0.7158
63 73.2 7 3.65 10.9 200.2 23.06 0.4545
100 116 19 2.79 14 319.3 37.76 0.2877
125 145 19 3.12 15.6 399.2 47.2 0.2302
160 186 19 3.53 17.6 511 58.56 0.1798
200 232 19 3.95 19.7 638.7 73.2 0.1439
250 290 19 4.41 22.1 798.4 91.5 0.1151
315 366 37 3.55 24.8 1008.4 115.29 0.0916
400 465 37 4 28 1280.5 146.4 0.0721
450 523 37 4.24 29.7 1440.5 164.7 0.0641
500 581 37 4.47 31.3 1600.6 183 0.0577
560 651 61 3.69 33.2 1795.3 204.96 0.0516
630 732 61 3.91 35.2 2019.8 230.58 0.0458
710 825 61 4.15 37.3 2276.2 259.86 0.0407
800 930 61 4.4 39.6 2564.8 292.8 0.0361
900 1046 91 3.83 42.1 2888.3 329.4 0.0321
1000 1162 91 4.03 44.4 3209.3 366 0.0289
1120 1301 91 4.27 46.9 3594.4 409.92 0.0258

 

All Aluminium Alloy Conductors (AAAC)                    BS EN 50183
Designation Area Stranding wire Dia. Overall
 Diameter
Nominal 
Breaking Load
Nominal DC 
Resistance at 20
ºC
Standard Weight
mm2 No Φ mm kN Ohm/km kg/km
ASTER 22 22 7 2 6 7.15 1.4989 60
ASTER 34.4 34.4 7 2.5 7.5 11.17 0.9593 93.8
ASTER 54.6 54.6 7 3.15 9.45 17.73 0.6042 148.9
ASTER 75.5 75.5 19 2.25 11.3 24.55 0.4388 207.4
ASTER 117 117 19 2.8 14 38.02 0.2833 321.2
ASTER 148 148.1 19 3.15 15.8 48.12 0.2239 406.5
ASTER 181.6 181.6 37 2.5 17.5 59.03 0.1831 500.3
ASTER 228 227.8 37 2.8 19.6 74.04 0.146 627.6
ASTER 288 288.3 37 3.15 22.1 93.71 0.1154 794.3
ASTER 366 366.2 37 3.55 24.9 115.36 0.0908 1008.9
ASTER 570 570.2 61 3.45 31.1 185.33 0.0585 1576
ASTER 851 850.7 91 3.45 38 276.47 0.0394 2360.7
ASTER 1144 1143.5 91 4 44 360.22 0.0293 3173.4
ASTER 1600 1595.9 127 4 52 502.72 0.021 4427.5

4.Packing

Packing in wooden drums,steel wooden drums or as customer’s requirement.

5.Customer Visit  

We have a professional sales team with each of them has engaged in this job for 3-10 years, so that we can provide the comprehensive and professional technology for you. With the perfect quality and after sales service, till now we have exported to more than 80 countries, welcome to visit us and establish win-win establish relationship!

6.Production process:

AAAC conductor producing process is drawing stranding and cabling,our factory possess 2 subsidiaries,Zhulin factory is professional bare conductor workshop with 20 production line.

7.Certificate

As first rank of the cable supplier in China, we have obtained CCC, ISO9001, ISO14001, OHSAS certificates, passed the SGS and BV test, and our brand "RMJT" be given China famous brand.

8.About us:

People’s Cable Group Co., Ltd. was founded in 2007, located in Zhengzhou Gongyi economic development zone. Our company has 2 factories (Zhitian factory and Zhulin factory), occupies total area of more than 300,000 square meters, with building area 230,000 square meters. 

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.