Al/XLPE/Cts/PVC/Awa/PVC, Power Cable, 6/10 (12) Kv, 1/C (IEC 60502-2)

Al/XLPE/Cts/PVC/Awa/PVC, Power Cable, 6/10 (12) Kv, 1/C (IEC 60502-2)

Al/XLPE/Cts/PVC/Awa/PVC, Power Cable, 6/10 (12) Kv, 1/C (IEC 60502-2)

AL/XLPE/CTS/PVC/AWA/PVC

Underground, Industrial, Power Station

Low and Medium Voltage Cable

DC Cable

XLPE

PVC

Round Wire

Aluminum

ISO, CCC, CE

Al/XLPE/Cts/PVC/Awa/PVC

Boan

6/10 (12) Kv

2

1

25-1000 mm2

Aluminum Wire Armour

DingAn

Heated Steel-Wooden Drum/Steel Drum

SGS

Jiangsu Yixing, China

8544601200

Product Description

AL/XLPE/CTS/PVC/AWA/PVC, Power Cable, 6/10(12) KV, 1/C (IEC 60502-2)
The cable design conforms to IEC 60502 part 2. However if requested, we can separately offer guaranteed technical particulars for cables as per different international specifications or specific customer needs.

CONSTRUCTIONAL FEATURES

Conductor
Aluminum Conductors upto 1000 sq mm will be circular compacted & stranded and shall comply with IEC-60228 Class 2.

Conductor screen
This will be an extruded layer of semiconducting XLPE applied under simultaneous triple extrusion process over the conductor along with the insulation and the insulation screen.

Insulation
This will be an extruded layer of insulating grade XLPE applied over conductor screen under triple extrusion process along with conductor screen and insulation screen.

Insulation screen
This will be a layer of semiconducting XLPE which will be applied by tripe extrusion process over the insulation.

Metallic screen
It will consist of a layer of copper wires applied helically with overlap over insulation screen. Other combinations of metallic screens as per customer’s requirement can also be provided on request.

Inner Sheath (Bedding)
Extruded layer of PVC or PE is applied over the laid-up cores. PVC is normally of grade ST2 or PE of grade ST7 as per IEC 60502 Part 2.

Armour

The armour is applied over inner sheath. For Single core cables this is of aluminium wires and for multicore cables the armour can be of one among the following options: –
A) Galvanized steel wire.
B) Galvanized steel tape.
C) Galvanised steel strip.
The armour is applied helically over the bedding.

Outer sheath
An extruded layer is applied over the armour in case of armoured cables and over the laid up cores in case of unarmoured cables. Outer sheath material can be either PVC of grade ST2 or PE of grade ST7 as per IEC-60502 Part 2.

Section Conductor diameter Conductor weight Insulation thickness Bedding thickness Armour wire diameter Outer sheath thickness Cable overall diameter Cable weight Minimum bending radius of cable DC resistance of conductor at 20 °C Armour DC resistance at 20 °C Short circuit current rating of armour for 1 second
mm2 mm kg/km mm mm mm mm mm kg/km mm ohm/km ohm/km kA
25 5.9 67 3.4 1.2 1.6 1.8 23.5 675 353 1.20 0.542 4.78
35 6.9 92 3.4 1.2 1.6 1.8 24.5 740 368 0.868 0.506 5.12
50 8.1 125 3.4 1.2 1.6 1.8 26.0 820 390 0.641 0.474 5.46
70 9.7 182 3.4 1.2 1.6 1.9 27.5 950 413 0.443 0.434 5.97
95 11.4 251 3.4 1.2 1.6 1.9 29.5 1085 443 0.320 0.400 6.49
120 12.9 317 3.4 1.2 1.6 2.0 31.0 1220 465 0.253 0.380 6.83
150 14.3 390 3.4 1.2 2.0 2.1 33.5 1455 503 0.206 0.286 9.07
185 16.0 493 3.4 1.2 2.0 2.1 35.0 1625 525 0.164 0.270 9.60
240 18.4 646 3.4 1.2 2.0 2.2 38.0 1905 570 0.125 0.243 10.67
300 20.6 803 3.4 1.2 2.0 2.2 40.0 2155 600 0.100 0.226 11.47
400 23.3 1027 3.4 1.2 2.0 2.4 43.5 2570 653 0.0778 0.207 12.54
500 26.3 1307 3.4 1.3 2.5 2.5 48.0 3190 720 0.0605 0.152 17.09
630 30.0 1721 3.4 1.4 2.5 2.6 52.0 3830 780 0.0469 0.138 18.75
800 34.2 2188 3.4 1.4 2.5 2.7 57.0 4600 855 0.0367 0.122 21.25
1000 38.2 2759 3.4 1.5 2.5 2.9 61.5 5440 923 0.0291 0.111 23.34

Tags: , ,