Al Cu XLPE PVC Insualtion Armoured Non-Armoured 1 Core 2core 3core 3+1core 4core 5 Core 0.6/1kv Power Cable
Product Description
1.Manufactured according to the shandard of IEC,BS,DIN or ICEA upon requst.
2.Suitable for use in power transmission and distribution lines with rated power frequency voltage 0.6/1kV.
3.The ambient temperature for installation: ≥0°C
4.Maximun conductor temperature in normal operation:≤90°C
5.Max operating temperature of conductor when cable short-circuited(5s maximun duration): 250°C
6.Permissible bending radius:
Single cable: [20(D+d)±5%]mm
Multi cable: [15(D+d)±5%]mm
7. Suitable for under ground,can bear mechanical stress.
8. Products Parameter (structure, weight and current rating)
Type | Dia. of conductor | XLPE insulation thickness | Inner sheath thickness | Steel tape thickness | PVC jacket thickness | Approx. dia. of cable | Approx. weight of cable | Current rating of cable | |
mm2 | mm | mm | mm | mm | mm | mm | kg/km | in the air | under ground |
4*4 | 2.25 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 402 | 28 | 35 |
4*6 | 2.76 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 488 | 37 | 46 |
4*10 | 4.05 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 688 | 47 | 56 |
4*16 | 5.10 | 0.7 | 1.2 | 0.2 | 1.8 | 23 | 927 | 64 | 76 |
4*25 | 6.00 | 0.9 | 1.2 | 0.2 | 1.8 | 27 | 1367 | 84 | 98 |
4*35 | 7.00 | 0.9 | 1.2 | 0.2 | 1.8 | 30 | 1558 | 115 | 126 |
4*50 | 6.81 | 1.0 | 1.2 | 0.5 | 1.9 | 33 | 2163 | 141 | 152 |
4*70 | 8.23 | 1.1 | 1.2 | 0.5 | 2.1 | 36 | 2485 | 172 | 181 |
4*95 | 9.71 | 1.1 | 1.2 | 0.5 | 2.2 | 41 | 2813 | 218 | 222 |
4*120 | 10.95 | 1.2 | 1.3 | 0.5 | 2.4 | 44 | 2945 | 269 | 267 |
4*150 | 12.16 | 1.4 | 1.4 | 0.5 | 2.5 | 49 | 3533 | 313 | 305 |
4*185 | 13.61 | 1.6 | 1.5 | 0.5 | 2.7 | 54 | 4236 | 359 | 344 |
4*240 | 15.65 | 1.7 | 1.6 | 0.5 | 3.0 | 60 | 5625 | 405 | 383 |
4*300 | 17.53 | 1.8 | 1.7 | 0.5 | 3.1 | 66 | 6286 | 451 | 422 |
Certificates:
- Next: Airdac Sne Cable Concentric Cable
- Previous: Flat Submersible Pump Cable 2 & 3 Conductor W/ Ground 600 Volts