Airdac Cable Sne Cne 10mm2 16mm2
Product Description
Cable Description
Circular stranded hard drawn copper phase conductor, XLPE insulated with concentrically arranged identified neutral and bare
earth conductors. Polyethylene sheathed 600/1000 V service connection cable. Nylon ripcord laid under sheath. Manufactured to
SANS 1507 -6.
Specification
Conductor | Copper |
Insulation | XLPE |
Jacket | PE |
Color | black |
Pilot cores | 2*1.13mm |
Voltage | 600/1000V |
Cable size | 10mm2 ,16mm2 |
Application | overheas,underground |
Conductor tempeturer in air | ≤90°C |
Technical Data
Electrical Properties
Cable Size (mm? 10 16
Phase Conductor Resistance (Ohm/km) DC @ 20 1,90 1,20
Earth Size (mm? 7,5 10
Neutral Size (mm? 10 16
Phase Core Impedance (Z) (Ohm/km) 2,34 1,47
Current Rating* (A) 50 70
Pilot Cores (No. x OD) Solid (mm) 2 x 1,13 2 x 1,13
* Note: – In air, with 30 ambient with maximum conductor temperature 90
Mechanical Properties
Cable Size (mm? 10 16
Phase Conductor (No. x OD)(mm) 7 x 1,35 7 x 1,67
Nominal InsulationThickness (mm) 1,0 1,0
Neutral Conductor (No. x OD)(mm) 7 x 1,33 7 x 1,76
Earth Conductor (No. x OD)(mm) 3 x 1,78 3 x 2,20
Nominal SheathThickness (mm) 1,6 1,6
Approximate Cable OD (mm) 12,8 14,5
Approximate Cable Mass (kg/km) 320 485
Installation Data
Span (m) 10
SAG* (mm) 10 mm? 45
SAG* (mm) 16 mm? 40
20 30 40 50
180 400 710 1110
170 380 670 1050
Based on
UTS** MWT***
3600 900
5760 1440
Note: * Assuming worst conditions, i.e. – 5,5 with simultaneous wind speed of 31 m/s and measured at midspan.
** UTS = Minimum ultimate tensile strength.
*** MWT = Minimum working tension.