ACSR Rabbit 50mm2 BS 215 Part 2
ACSR Rabbit 50mm2 BS 215 Part 2
ACSR Rabbit
Bare
Stranded
Overhead
Aluminum
None
None
Round Wire
Overhead Distributing Line
ISO9001, CE, UL, CCC
Yifang Cable
50mm2
ACSR Rabbit
Aluminum Condcutor
6+1 Strands
BS 215 Part 2
Kenya,etc
Yifang Cable
Wooden Drum
1.1m size Drum
China
7614100000
Product Description
ACSR Rabbit 50mm2 BS 215 Part 2
Product name
Aluminium Conductor Steel Reinforced ACSR wire ACSR conductor or ACSR bare conductor
Applications
ACSR is a composite conductor consisting of seven or more aluminium and galvanized steel wires built up in concentric-lay-stranded layers.
Used as bare overhead transmission cable and as primary and secondary distribution cable. ACSR provides optimal strength for line design. Variable steel core stranding enables desired strength to be achieved without sacrificing ampacity.
Product name
Aluminium Conductor Steel Reinforced ACSR wire ACSR conductor or ACSR bare conductor
Applications
ACSR is a composite conductor consisting of seven or more aluminium and galvanized steel wires built up in concentric-lay-stranded layers.
Used as bare overhead transmission cable and as primary and secondary distribution cable. ACSR provides optimal strength for line design. Variable steel core stranding enables desired strength to be achieved without sacrificing ampacity.
Suitable For
- Transmission lines
- River crossings
- Other installations
Service Performance
- (1).The permissible long-time operating temperature for aerial conductor is 70oC.
- (2).Under the circumstance that rare climate is occuring and ice coverage rate low in heavy ice area,the biggest stress of cable at the lowest point of the sag should not exceed 60% of the short-time destructive power.
- (3).When connecting conductors,the conductor beside the connecting tube cant be prominent.Otherwise,the force on the operating conductors will be unbalanced.After connectors are install,the connecting tube should be painted by moisture-proof varnish in order to protect it from corrosion.
- (4).Under installaion,the arc downing stress of all the conductors should be the same.With in the permissible distance of crossing buildings or dropping to the ground,the stress can be 10-15% higher than regular stress.
TECHNICAL DATA SHEET | |||
ACSR 100mm2-Dog | |||
Item | Description | Unit | ACSR Conductor |
1 | Manufacturer | ZHENGZHOU YIFANG CABLE CO ., LTD. | |
2 | Governing Standards | BS 215 | |
3 | Copies of Standards Attached: | Yes/No | Yes |
4 | Copies of type test attached? | Yes/No | Yes |
5 | If standards is not BS:215(Part II) are conductor specifications same as the BS:215 requirements in respect of the following?: | ||
Diameter | Yes/No | Yes | |
Strand size | Yes/No | Yes | |
Direction of lay | Yes/No | Yes | |
Lay ratio | Yes/No | Yes | |
Materials | Yes/No | Yes | |
6 | Technical data: | ||
Dog | Dog | ||
Nominal diameter (mm) | 14.15 | ||
Stranding (Al/Steel) | 6/7 | ||
Breaking strength (kN) | 32.7 | ||
Mass (kg/km) | 394 | ||
Resistance at 20ºC | 0.2733 |
- Next: Welding Cable
- Previous: 35kv 185mm2 Sac Spaced Aerial Cable
Contact us
Similar Or Related