ABC Cable Duplex Service Drop, Triplex Service Drop

ABC Cable Duplex Service Drop, Triplex Service Drop

ABC Cable Duplex Service Drop, Triplex Service Drop

ABC CABLE

Jinyuan

ISO9001, CE, UL, CCC, RoHS, VDE

Overhead

Round Wire

XLPE

No

Aluminum

Overhead

Stranded

Insulated

0.6/1kv

1km

Heated Wooden Drum

Jinyuan

Drum Coil

drum

China

8544492100

Product Description

ABC CABLE -aerial bundle cable :are mainly used for electric power transmission, rebuiding of urban and forest regions. They can improves safety and reliance of electrified wire netting.
1 Type:Duplex Service Drop, Triplex Service Drop, Quadruplex Service Drop
Duplex Service Drop
  Applications:To supply 120 volt aerial service for temporary service at construction sites,outdoor or street lighting . For service at 600 volts or lower at a conductor temperature of 75 maximum.
Triplex Service Drop
  Applications: To supply power from the ulility`s lines to the consumer`s weatherhead. For service at 600 volts or less(phase to phase ) at a conductor temperature of 75 maximum for PE insulation or 90 maximum for XLPE insulation .
Quadruplex Service Drop
  Applications: Used to supply 3 phase power , usually from a pole-mounted transformer to the use`s servic head where connection to the service entance cable is made . To be used at voltages of 600 volts or less phase to phase and at conductor temperature not to exceed 75 for PE insulated conductors or 90 for XLPE insulated conductors.
2  Construction
   a Phase Conductor construction:The phase conductor is aluminum alloy 1350-H19 hard-drawn, compressed concentric-lay-stranded.
  b  Neutral Conductor Construction
Cable assemblies are available with the following neutral conductors:
Aluminum conductors, coated-steel reinforced (ACSR), concentric-lay-stranded
Aluminum alloy 1350-H19 hard-drawn, concentric-lay-stranded
Aluminum alloy 6201-T81, concentric-lay-stranded
  c Insulation Material
The standard insulation on the phase conductor is black low-density crosslinked polyethylene (XLPE)
Alternatively, black linear low-density polyethylene (LLDPE) insulation with a 75°C temperature rating is available upon request.
3 specification
  see following table
4.Standards
1. B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
2. B-231 Aluminum Conductors, Concentric-Lay-Stranded.
3. B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
4. B-399 Concentric-Lay_Stranded 6201-T81 Aluminum Alloy Conductors.
5. B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
6. Duplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-

Code Name                     Phase Conductor            Bare Neutral Messenger Weight Per 1000ft(lbs) Rating(Amps)
Size AWG Strand Insulation Thickness(mls) Size AWG Strand Breaking Strength(lbs) XLPE Poly XLPE Poly
AAC NEUTRAL-MESSENGER
Clydesdale 4 Solid 45 4 7 881 208 201.8 100 80
Pinto 4 7/w 45 4 7 881 223 207.9 100 80
Mustang 2 7/w 45 2 7 1,350 333 312.6 135 105
Criollo 1/0 19/w 60 1/0 7 1,990 529 504.5 180 140
Percheron 2/0 19/w 60 2/0 7 2,510 649 620.5 205 160
Hanoverian 3/0 19/w 60 3/0 19 3,310 799 765.6 235 185
Oldenburg 4/0 19/w 60 4/0 19 4,020 986 946.7 275 210
Lippizaner 336.4 19/w 80 336.4 19 6,146 1,546 1,519.2 370 280
ACSR NEUTRAL-MESSENGER
Morochuca 6 Solid 45 6 6/1 1,190 152 147.4 75 60
Chola 6 7/w 45 6 6/1 1,190 162 151.7 75 60
Morgan 4 Solid 45 4 6/1 1,860 226 220 100 80
Hackney 4 7/w 45 4 6/1 1,860 241 226.1 100 80
Palomino 2 7/w 45 2 6/1 2,850 362 342.6 135 105
Costena 1/0 19/w 60 1/0 6/1 4,380 575 550.6 180 140
Grullo 2/0 19/w 60 2/0 6/1 5,310 707 678.7 205 160
Suffolk 3/0 19/w 60 3/0 6/1 6,620 872 838.9 235 185
Appaloosa 4/0 19/w 60 4/0 6/1 8,350 1,079 1,039.2 275 210
Bronco 336.4 19/w 80 336.4 18/1 8,580 1,613 1,568.2 370 280
Gelding 336.4 19/w 80 4/0 6/1 8,350 1,548 1,494.3 370 280

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.