ABC Cable, Aerial Bundled Cable, Overhead Cable, BS, NF, IEC Standard

ABC Cable, Aerial Bundled Cable, Overhead Cable, BS, NF, IEC Standard

Quick Details

ABC Cable, Aerial Bundled Cable, Overhead Cable, BS, NF, IEC Standard

3*50+1*54.4

Zhonghua

ISO9001, CCC

LSOH

Round Wire

XLPE

PVC

Aluminum

Overhead

Stranded

Insulated

ZHONGHUA

Reels

3*35+1*54.4

Wuhan

Product Details

1 Standard
IEC60502, IEC61089; NF C33-209; GB 12527-9; ASTM B231, ASTM B232, BS215; DIN48201, DIN48204. 
We can also manufacture ABC cable according to customer’s special requirements.
2 Application
The cable as a new-type aerial cable is used for transmitting electric power overhead, extensively used in rebuilding of urban and forest region electrified wire netting. It improves the safety and reliance of electrified wire netting. To be used at cotages of 600V phase-to-phase or less and at conductor temperatures not to exceed 75ºC for polyethylene insulated conductors or 90ºC for cross-liked polyethylene(XLPE) insulated conductors.
3 Specification
Concentric strand aluminum wires as phase conductor; AAAC(all aluminum alloy conductors) or ACSR(aluminum conductor steel reinforced) as messenger (Neutral) core;Phase conductor is insulated by XLPE or HDPE or PVC.
It meets or exceeds the following specifications: 
1). Aluminum Wire, 1350-H19 for Electrical Purposes. 
2). Aluminum Conductors, Concentric-Lay-Stranded. 
3). Aluminum Conductor, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR). 
4). Concentric-Lay-Stranded 6201-T81 Conductors. 
5). Compressed Round Stranded Aluminum Conductors Using Single Input Wire. 
It meets or exceeds all applicable requirements of ANSI/ICEA S-76-474
4 Type of XLPE(PE) insulated ABC cable (service drop)
XLPE(PE) insulate cable (service drop)covers mainly three types:
Duplex Service Drop
Triplex Service Drop
Quadplex Service Drop
5 Construction
The basic construction is as follows: 
3 power cores consisting of standard aluminum conductors, insulated with XLPE insulation 
+ One sheath lighting aluminum conductor with XLPE insulation(optional) 
+ One messenger Al-alloy conductor (bare or covered) 
The messenger conductor can be of galvanized steel wire also. 
The purpose of messenger wire is: 
A) It acts as load bearing wire. 
B) It acts as earth or neutral conductor.

Standards:
(1). BS 7870-5: Part 5: Polymeric insulated aerial bundled conductors (ABC) of rated voltage 0.6/1 kV for overhead distribution

ABC Cables without Street Lighting
1+1 Structure
Phase Conductor Neutral Conductor Completed Cable
Section Insulation Thickness Electrical Resistance Section Insulation Thickness Electrical Resistance Overall Diameter Cable Weight
DC.20°C DC.20°C    
No.xmm2 mm Ω/km mm2 mm Ω/km mm kg/km
1×25 1.3 1.20 25 1.3 1.20 17.6 210
1×35 1.3 0.868 35 1.3 0.868 19.6 270
1×50 1.5 0.641 50 1.5 0.641 23 360
1×70 1.5 0.443 70 1.5 0.443 26.4 500
1×95 1.7 0.320 95 1.7 0.320 30.6 680
               
3+1 Structure
Phase Conductor Neutral Conductor Completed Cable
Section Insulation Thickness Electrical Resistance Section Insulation Thickness Electrical Resistance Overall Diameter Cable Weight
DC.20°C DC.20°C    
No.xmm2 mm Ω/km mm2 mm Ω/km mm kg/km
3×25 1.3 1.20 25 1.3 1.20 21.2 410
3×35 1.3 0.868 35 1.3 0.868 23.7 550
3×50 1.5 0.641 50 1.5 0.641 27.8 730
3×70 1.5 0.443 70 1.5 0.443 31.9 1000
3×95 1.7 0.320 95 1.7 0.320 36.9 1370
3×120 1.7 0.253 120 1.7 0.253 40.6 1690
ABC Cables with Street Lighting
3+1+1 Structure
Phase Conductor Neutral Conductor Street Lighting Conductor Completed Cable
Section Insulation Thickness Section Insulation Thickness Section Insulation Thickness Overall Diameter Cable Weight
No.xmm2 mm mm2 mm mm2 mm mm kg/km
3×50 1.5 50 1.5 25 1.3 29.8 830
3×70 1.5 70 1.5 25 1.3 33.6 1100
3×95 1.7 95 1.7 25 1.3 38.2 1470

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.