AAC Conductor BS 215
AAC Conductor BS 215
AAC
Construction, Overhead, Underground, Industrial, Power Station
Low and Medium Voltage Cable
AC Cable
Bare
Bare
Flat Wire
Aluminum
ISO, CCC, CE, RoHS, UL, VDE
ACSR
Jinshui
JINSHUI
Wooden Drun
bare conductor
China
8544492100
Product Description
Application:
1. AAC are used in overhead power tranmission and distribution lines with various grade voltages.
2. Under the same weight, AAC is with higher DC resistance and lower costthan cooper conductor.
1. AAC are used in overhead power tranmission and distribution lines with various grade voltages.
2. Under the same weight, AAC is with higher DC resistance and lower costthan cooper conductor.
British Sizes-BS215-1
Code Name |
Nominal Aluminium Area |
Stranding And wire diameter |
Sectional Area |
Approximate Overall diameter |
Linear Mass |
Calculate D.C Resistance At20 |
Calculate Breaking Load |
Final Modulus of Elasticity |
Corefficient Of linear expansion |
Mm² | mm | Mm² | mm | Kg/km | Ohm/km | daN | hbar | / | |
Midge | 22 | 7/2.06 | 23.33 | 6.18 | 64 | 1.227 | 399 | 5900 | 23×106 |
Aphis | 25 | 7/3.35 | 26.40 | 7.2 | 73 | 1.081 | 411 | 5900 | 23×106 |
Gnat | 25 | 7/2.21 | 26.8 | 6.6 | 73 | 1.066 | 459 | 5900 | 23×106 |
German Sizes-DIN48201
Area | Stranding and Wire diameter |
Overall diameter |
Linear mass |
Calculated Breaking load |
Calculated D.C Resistance at 20 |
|
Nominal(mm²) | Actual(mm²) | mm | mm | Kg/km | daN | Ohm/km |
16 | 15.89 | 7/1.71 | 5.1 | 44 | 290 | 1.8018 |
25 | 24.25 | 7/2.10 | 6.3 | 67 | 425 | 1.1808 |
35 | 34.36 | 7/2.50 | 7.5 | 94 | 585 | 0.8332 |
50 | 49.48 | 7/3.00 | 9.0 | 135 | 810 | 0.5786 |
50 | 48.36 | 19/1.80 | 9.0 | 133 | 860 | 0.5950 |
70 | 65.82 | 19/2.10 | 10.5 | 181 | 1150 | 0.4371 |
95 | 93.27 | 19/2.50 | 12.5 | 256 | 1595 | 0.3048 |
120 | 117.00 | 19/2.80 | 14.0 | 322 | 1910 | 0.2459 |
- Next: AAAC, ACSR, AAC Aluminum Stranded Conductor
- Previous: Meet Korea Market Overhead Transmission Line ACSR Conductor Aluminium Cable 12mm ACSR