AAC Bare Aluminum Overhead Conductor

AAC Bare Aluminum Overhead Conductor

AAC Bare Aluminum Overhead Conductor

AAC Conductor

Bare

Stranded

Overhead

Aluminum

Bare

ISO9001

AAC Bare Aluminum Overhead Conductor

YIFNAG

Standard export wooden drums

IEC, BS, DIN, GOST, JIS, CAS, NFC etc

ZHENGZHOU CHINA

761490000

Product Description

All Aluminum Conductor(AAC)& Aluminum Conductor Steel Reinforced(ACSR))for ASTM (AAC, ACCR, AAAC, ACSR) Generally Confirming to IS 398 (Part-I, II, IV), IEC-228
(AAAC) Conductor as per ASTM-B-399-1992
(AAAC) Conductor as per BS-3242-1970
(AAAC) Conductor IS: 398-IV-1994
(ACSR) as per ASTM-B-233-1992
(AAC) as per BS-215-1-1970
(AAC) as per IS-398-1: 1976
(AAC) as per ASTM-B-231-1990
(ACSR) as per IS: 398-II: 1976 & IS: 398-V: 1992
(ACSR) BS-215-II-1970
(AACSR) as per IEC-1089-1191
AAC(All aluminum conductor) are suited for overhead power line.
We can supply this conductor according to different recognized standards, such as IEC61089, BS215, BS EN 50182: 2001, STM B231, CSA C49, DIN480201, JIS C3109, customer special specification also can be satisfied.
ACSR or ACSR cable or ACSR conductor used for Overhead electrical distribution and transmission lines for distributing power
Applications
Used as bare overhead transmission cable and as primary and secondary distribution cable. ACSR offers optimal strength for line design. Variable steel core stranding enables desired strength to be achieved without sacrificing ampacity.

Construction
Aluminum alloy 1350-H-19 wires, concentrically stranded about a steel core. Core wire for ACSR is available with class A, B, or C galvanizing; ""aluminized"" aluminum coated (AZ); Or aluminum-clad (AW). Additional corrosion protection is available through the application of grease to the corer or infusion of the complete cable with grease.

Specifications
ACSR bare conductor meets or exceeds the following ASTM specifications:

B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)
B-341 Aluminum-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR/AZ)
B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR/AZ)
B-500 Zinc Coated and Aluminum Coated Stranded Steel Core for Aluminum Conductors, Steel Reinforced (ACSR)

Notes
Resistance is calculated using ASTM standard increments of stranding and metal conductivity of 61.2% IACS for EC (1350) and 8% IACS for steel. AC (60Hz) resistance includes current dependent hysteresis loss factor for 1 and 3 layer constructions.
Current ratings are based on 75oC conductor temperature, 25oC ambient, 2ft/s wind, 96/watts/sq. Ft sun, 0.5 coefficients of emissivity and absorption.

Technical characteristics / British Sizes-BS 215 – Part1      
                   
Code Name Nominal Aluminum Area  Stranding and Wire Diameter  Sectional Area  Approximate Overall Diameter  Linear Mass  Calculated D.C. Resistance at 20C  Calculated Breaking Load  Final Modulus of elasticity  Coefficient Linear expansion 
mm 2 mm mm 2 mm kg/km Ω/km daN hBar /C
Midge 22 7/2.06 23.33 6.18 64 1.2270 399 5900 23Χ10 -6
Aphis 25 7/3.35 26.40 7.20 73 1.0810 411 5900 23Χ10 -6
Gnat 25 7/2.21 26.80 6.60 73 1.0660 459 5900 23Χ10 -6
Weevil  30 3/3.66 31.60 7.90 86 0.9082 486 5900 23Χ10 -6
Mosquito  35 7/2.59 37.00 7.80 101 0.7762 603 5900 23Χ10 -6 
Ladybird 40 7/2.79 42.80 8.40 117 0.6689 687 5900 23Χ10 -6
Ant 50 7/3.10 52.83 9.30 145 0.5419 828 5900 23Χ10 -6
Fly 60 7/3.40 63.55 10.20 174 0.4505 990 5900 23Χ10 -6 
Bluebottle 70 7/3.66 73.70 11.00 202 0.3881 1134 5900 23Χ10 -6
Earwig  75 7/3.78 78.50 11.40 215 0.3644 1194 5900 23Χ10 -6
Grasshopper  80 7/3.91  84.10 11.70 230 0.3406 1278 5900 23Χ10 -6
Clegg 90 7/4.17 95.60 12.50 262 0.2994 1453 5900 23Χ10-6
Wasp 100 7/4.39  106.00 13.17 290 0.2702 1600 5900 23Χ10 -6
Beetle 100 19/2.67 106.00 13.40 293 0.2704 1742 5600 23Χ10 -6
Bee 125 7/4.90 132.00 14.70 361 0.2169 1994 5900 23Χ10 -6
Cricket 150 7/5.36  157.90 16.10 432 0.1818 2385 5900 23Χ10 -6
Hornet 150 19/3.25  157.60 16.25 434 0.1825 2570 5600 23Χ10 -6
Caterpillar 175 19/3.53 186.00 17.70 512 0.1547 2863 5600 23Χ10 -6
Chafer 200 19/3.78  213.20 18.90 587 0.1349 3240 5600 23Χ10 -6
Spider 225 19/3.99  236.90 20.00 652 0.1211 3601 5600 23Χ10 -6
Cockroach 250 19/4.22 265.70 21.10 731 0.1083 4040 5600 23Χ10 -6
Butterfly 300 19/4.65  322.70 23.25 888 0.0892 4875 5600 23Χ10 -6
Moth 350 19/5.00  373.20 25.00 1027 0.0771 5637 5600 23Χ10 -6
Drone 350 37/3.58 373.30 25.10 1029 0.0774 5745 5600 23Χ10 -6
Locust 400 19/5.36  428.50 26.80 1179 0.0671 6473 5600 23Χ10 -6
Centipede 400 37/3.78  415.20 26.46 1145 0.0694 6310 5600 23Χ10 -6
Maybug 450 37/4.09 486.90 28.60 1342 0.0593 7401 5600 23Χ10 -6
Scorpion 500 37/4.27  529.50 29.90 1460 0.0544 7998 5600 23Χ10 -6
Cicada 600 37/4.65  628.60 32.60 1733 0.0459 9495 5600 23Χ10 -6
Tarantula 750 37/5.23 794.60 36.60 2191 0.0363 12010 5600 23Χ10 -6