AAC, AAAC, Aacsr Bare Conductors for High Voltage Distrution Line
Product Description
AAAC (All Aluminum Alloy Conductor) referred to have higher strength but lower conductivity than pure aluminum. Being lighter, alloy conductors can sometimes be used to advantage in place of the more conventional ACSR; Having lower breaking loads than the latter, their use becomes particularly favourable when ice and win loadings are low.
We can supply this conductor according to different recognized standards, such as BS EN50182, IEC61089, ASTM B399DIN 48, customer special specification also can be satisfied.
The data sheets below show the most common standards, British standard and IEC standard.
IEC Sizes IEC 61089
Code Number | Stranding&wire diameter | Approx Overall diameter | Nominal | Approx. | Breaking Load | DC Resistance at 20 |
area | Weight | |||||
mm | mm | mm 2 | Kg/km | KN | Ohm/km | |
16 | 7/1.83 | 5.49 | 18.4 | 50.4 | 5.43 | 1.7896 |
25 | 7/2.29 | 6.86 | 28.8 | 78.7 | 8.49 | 1.1453 |
40 | 7/2.89 | 8.68 | 46 | 125.9 | 13.58 | 0.7158 |
63 | 7/3.63 | 10.9 | 72.5 | 198.3 | 21.39 | 0.4545 |
100 | 19/2.78 | 13.9 | 115 | 316.3 | 33.95 | 0.2877 |
125 | 19/3.10 | 15.5 | 144 | 395.4 | 42.44 | 0.2302 |
160 | 19/3.51 | 17.6 | 184 | 506.1 | 54.32 | 0.1798 |
200 | 19/3.93 | 19.6 | 230 | 632.7 | 67.91 | 0.1439 |
250 | 19/4.39 | 22 | 288 | 790.8 | 84.88 | 0.1151 |
315 | 37/3.53 | 24.7 | 363 | 998.9 | 106.95 | 0.0916 |
400 | 37/3.98 | 27.9 | 460 | 1268.4 | 135.81 | 0.0721 |
450 | 37/4.22 | 29.6 | 518 | 1426.9 | 152.79 | 0.0641 |
500 | 37/4.45 | 31.2 | 575 | 1585.5 | 169.76 | 0.0577 |
560 | 61/3.67 | 33 | 645 | 1778.4 | 190.14 | 0.0516 |
630 | 61/3.89 | 35 | 725 | 2000.7 | 213.9 | 0.0458 |
710 | 61/4.13 | 37.2 | 817 | 2254.8 | 241.07 | 0.0407 |
800 | 61/4.38 | 39.5 | 921 | 2540.6 | 271.62 | 0.0361 |
900 | 91/3.81 | 41.8 | 1036 | 2861.1 | 305.58 | 0.0321 |
1000 | 91/4.01 | 44.1 | 1151 | 3179 | 339.53 | 0.0289 |
1120 | 91/4.25 | 46.7 | 1289 | 3560.5 | 380.27 | 0.0258 |
1250 | 91/4.49 | 49.4 | 1439 | 3973.7 | 424.41 | 0.0231 |
BS EN 50182:2001
Code Name | Stranding&wire diameter | Approx Overall diameter | Total area | Weight | Breaking Load | DC Resistance at 20 | Current Rating |
mm | mm | mm 2 | Kg/km | KN | Ohm/km | A | |
Box | 7/1.85 | 5.55 | 18.8 | 51.4 | 5.55 | 1.748 | 93 |
Acacia | 7/2.08 | 6.24 | 23.9 | 64.9 | 7.02 | 1.3828 | 110 |
Almond | 7/2.34 | 7.02 | 30.1 | 82.2 | 8.88 | 1.0926 | 128 |
Cedar | 7/2.54 | 7.62 | 35.5 | 96.8 | 10.46 | 0.9273 | 132 |
Deodar | 7/2.77 | 8.31 | 42.2 | 115.2 | 12.44 | 0.7797 | 148 |
Fir | 7/2.95 | 8.85 | 47.8 | 130.6 | 14.11 | 0.6875 | 161 |
Hazel | 7/3.30 | 9.9 | 59.9 | 163.4 | 17.66 | 0.5494 | 184 |
Pine | 7/3.61 | 10.8 | 71.6 | 195.6 | 21.14 | 0.4591 | 204 |
Holly | 7/3.91 | 11.7 | 84.1 | 229.5 | 24.79 | 0.3913 | 222 |
Willow | 7/4.04 | 12.1 | 89.7 | 245 | 26.47 | 0.3665 | 233 |
Oak | 7/4.65 | 13.95 | 118.9 | 324.5 | 35.07 | 0.2767 | 272 |
Mulbery | 19/3.18 | 15.9 | 150.9 | 414.3 | 44.52 | 0.2192 | 319 |
Ash | 19/3.48 | 17.4 | 180.7 | 496.1 | 53.31 | 0.183 | 354 |
Elm | 19/3.76 | 18.8 | 211 | 579.2 | 62.24 | 0.1568 | 385 |
Poplar | 37/2.87 | 20.1 | 239.4 | 659.4 | 70.61 | 0.1387 | 414 |
Sycamore | 37/3.23 | 22.6 | 303.2 | 835.2 | 89.4 | 0.1095 | 487 |
Upas | 37/3.53 | 24.7 | 362.1 | 997.5 | 106.82 | 0.0917 | 527 |
Yew | 37/4.06 | 28.4 | 479 | 1319.6 | 141.31 | 0.0693 | 629 |
Totara | 37/4.14 | 29.42 | 498.1 | 1372.1 | 146.93 | 0.0666 | 640 |
Rubus | 61/3.50 | 31.5 | 586.9 | 1622 | 173.13 | 0.0567 | 716 |
Sorbus | 61/3.71 | 33.4 | 659.4 | 1822.5 | 194.53 | 0.0505 | 760 |
Araucaria | 61/4.14 | 37.3 | 821.1 | 2269.5 | 242.24 | 0.0406 | 842 |
Redwood | 61/4.56 | 41 | 996.2 | 2753.2 | 293.88 | 0.0334 | 920 |
Company Information
- Next: Building Wire with Safe Standard and Certificate
- Previous: Aerial Bundle Cable with Direct Supply
Contact us
Similar Or Related
-
Aster Cable 366mm2 37 Strands AAAC Bare Conductor for 90kV HV Substation
-
AAAC Bare Conductor 100mm2 7/4.26mm for Uganda 33kV Distribution Line
-
AAAC Bare Conductor 50mm2 7/3.02mm for Uganda 11kV Distribution Line
-
Aerial Bundled Conductor 70mm2 Hard drawn Aluminum ABC Cable for 400V Distribution Line
-
50mm2;AAAC PVC Covered Hazel Conductor BS 3242 for 11kV Distribution Line
-
AAC, AAAC, Aacsr Bare Conductors for High Voltage Distrution Line