AAAC All Aluminum Alloy Conductor, Britain Sizes

AAAC All Aluminum Alloy Conductor, Britain Sizes

AAAC All Aluminum Alloy Conductor, Britain Sizes

JS-AAA10

Bare

Stranded

Overhead, Heating

Aluminum

Bare

ISO9001, CE, UL, CCC, RoHS, VDE

15.5, 24.7, 39.2, 62.4

Bare

Overhead AAAC Line Conductor IEC 61089 (All Alumin

Astmb399 Bs En50182

10 Years

Silver

JINSHUI CABLE

Drum

SGS, CCC

Henan

Product Description


All Aluminum Alloy Conductor(AAAC Conductor)

DESCRIPTION

The conductor consists of Aluminum Magnesium-Silicon alloy wires stranded in successive layers in opposite direction and the outer layer is right hand direction Z. Natural grease may be applied between the layers of AAAC except the outer layer.

STANDARD

Construction as per ASTMB399,DIN48201,BS EN50182,IEC61089,CSA49

APPLICATION :

AAAC bare conductors are used for primay and secondary overhead power transmission lines haveing long spans and high resistance to corrosion .

Product photo :

CERTIFICATE:

 Code
Name
Cross
section
(mm2) 
 Stranding and
wire Dia
(in)
 Overall Dia
(mm)
 Weight
(1b/1000ft)
 Rated
Strength
(kN)
 Max.D.C
Resistance
(Ω/km,20ºC)
 Akron  15.5  7/0.0661  5.04  28.52  4.92  2.159
 Alton  24.7   7/0.0834  6.36  45.40  7.83  1.356
 Ames  39.2   7/0.1052  8.01  72.24  12.4  0.8547
 Azusa  62.4   7/0.1327  10.11  114.9  18.9  0.5365
 Anaheim  78.6   7/0.1490  11.34  144.9  23.8  0.4264
 Amherst  99.3   7/0.1672  12.75  182.5  30.0  0.3373
 Alliance 125    7/0.1878  14.31  230.2  37.8  0.2678
 Butte  159  19/0.1283  16.3  291.6  46.5  0.2112
 Canton  200  19/0.1441  18.3  367.9  58.6  0.1676
 Cario  236  19/0.1565  19.9  433.9  69.2  0.1417
 Darien  284  19/0.1716  21.8  521.7  83.1  0.1181
 Elgin  331  19/0.1853  23.55  608.3  97.0  0.1012
 Flint  375  37/0.1415  25.13  690.8  107  0.08944
 Greeley  470  37/0.1583  28.14  864.6  135  0.071133
 —  547  61/0.1329  30.42  1005  156  0.06120
 ———-  590  61/0.1382  31.59  1086  167  0.05675
 ———–  638  61/0.1437  32.85  1175  181  0.05248
 ———–  685  61/0.1487  34.02  1258  194  0.04893
 ——  729  61/0.1536  35.1  1342  207  0.04597

CEDAR

 Nominal
Aea
(mm²)
 Cross
Section
(mm²)
 Stranding
and wires
Dia
(mm)
Overall
Dia
(mm)
 Weight
(kg/km)
 Rated
Strength
(kN)
 Max.D.C
Resistance
(Ω/km,20ºC)
 BOX  18.8  7/1.85  5.55  51.4  5.55 1.7480 
 ACACIA  23.8  7/2.08  6.24  64.9  7.02 1.3828 
 ALMOND  30.1  7/2.34  7.02  82.2  8.88  1.0926
 CEDAR  35.5  7/2.54  7.62  96.8  10.46  0.9273
 DEODAR  42.2  7/2.77  8.31  115.2  12.44  0.7797
 FIR  47.8  7/2.95  8.85  130.6 14.11   0.6875
 HAZEL  59.9  7/3.30  9.90  163.4 17.66   0.5494
 PINE  71.6  7/3.61  10.8  195.6 21.14  0.4591 
 HOLLY  84.1  7/3.91  11.7  229.5  24.79  0.3913
 WILLOW  89.7  7/4.04  12.1  245.0  26.47  0.3665
 OAK  118.9 7/4.65  14.0  324.5  35.07  0.2767
 MULBERRY  150.9  19/3.18  15.9  414.3  44.52  0.2192
 ASH  180.7  19/3.48  17.4  496.1 63.31   0.1830
 ELM  211.0  19/3.76  18.8  579.2  62.24  0.1568
 POPLA  239.4  37/2.87  20.1  659.4  70.61  0.1387
 SYCAMORE  303.2  37/3.23  22.6  835.2  89.40  0.1095
 UPAS  362.1  37/3.53  24.7  997.5  106.82  0.0917
 YEW  479.0  37/4.06  28.4  1319.6  141.31  0.0693
 TOTARA  498.1  37/4.14  29.0  1372.1  146.93  0.0666
 RUBUS  586.9  61/3.50  31.5  1622.0  173.13  0.0567
 SORBUS  659.4  61/3.71  33.4  1822.5  194.53 0.0505 
 ARAUCARIA  821.1  61/4.14  37.3  2269.4 242.24   0.0406
 RED WOOD  996.2  61/4.56  41.0  2753.2  293.88  0.0334

Tags: , , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.