ASTM Standard ACSR/Aw Core Wire Aluminium Conductor
ASTM Standard ACSR/Aw Core Wire Aluminium Conductor
ACSR/AW
Bare
Stranded
Overhead, Heating
Aluminum Clad Steel Wire
None
No
Round Wire
Overhead
ISO9001, CE
Jinyuan
ACSR/Aw Cable
Aw Core
ACSR/Aw Conductor
JYTOP
Wooden Drum or Base on Requests
DIN48204
Zhengzhou, China
7614100000
Product Description
ASTM Standard Aluminium conductor ACSR/Aw core Wire
Applications of Bare conductor type ACSR/AW
Aluminum Conductors Steel Reinforced /AW code(ACSR/AW) is recommended for use as a transmission cable between the power station and substations, and as primary and secondary distribution cable. It is composed out of 1350-H19 aluminum wires surrounding an aluminum clad steel core. ACSR/AW has as high breaking load as ACSR but better conductivity. ACSR/AW is considered less sensitive to corrosion due to its steel wires being protected by aluminum layer.
This catalogue shows the most common sizes of conductor but other sizes, to any recognized standards or customer specification can also be supplied. ACSR/AW insulated with XLPE or PVC can also be supplied as per customer’s requirements.
Construction
Aluminum alloy 1350-H-19 wires, concentrically stranded about a steel core. Core wire for ACSR is available with class A, B, or C galvanizing; "aluminized"" aluminum coated (AZ); or aluminum-clad (AW) – please see our ACSR/AW spec for more information. Additional corrosion protection is available through the application of grease to the corer or infusion of the complete cable with grease.
Applications of Bare conductor type ACSR/AW
Aluminum Conductors Steel Reinforced /AW code(ACSR/AW) is recommended for use as a transmission cable between the power station and substations, and as primary and secondary distribution cable. It is composed out of 1350-H19 aluminum wires surrounding an aluminum clad steel core. ACSR/AW has as high breaking load as ACSR but better conductivity. ACSR/AW is considered less sensitive to corrosion due to its steel wires being protected by aluminum layer.
This catalogue shows the most common sizes of conductor but other sizes, to any recognized standards or customer specification can also be supplied. ACSR/AW insulated with XLPE or PVC can also be supplied as per customer’s requirements.
Construction
Aluminum alloy 1350-H-19 wires, concentrically stranded about a steel core. Core wire for ACSR is available with class A, B, or C galvanizing; "aluminized"" aluminum coated (AZ); or aluminum-clad (AW) – please see our ACSR/AW spec for more information. Additional corrosion protection is available through the application of grease to the corer or infusion of the complete cable with grease.
STANDARDS
ACSR/AW bare conductor meets or exceeds the following ASTM standards:
l B-230 Aluminum wire, 1350–H19 for Electrical Purposes.
l B-502 Aluminum-Clad Steel Core Wire for Aluminum Conductors, Aluminum–Clad Steel Reinforced.
l B-549 Aluminum Conductors, Concentric-Lay–Stranded, Aluminum-Clad Steel Reinforced (ACSR/AW)
CONSTRUCTION
Aluminum 1350-H19 wires, concentrically stranded around an Aluminum-Clad Steel core.
Code word |
Size (AWG or kcmil) | Strand– ing (Al/AW) |
Diameter(ins.) | Weight per 1000 ft. (Lbs) |
Rated strength (Lbs) |
Resistance /1000 ft. |
Allowable ampacity+ (Amps) |
||||||
Individual wire | AW core |
Comp. cable | Al |
AW |
Total |
DC at 20ºC |
AC at 75ºC |
||||||
Al | AW | ||||||||||||
Swan/AW | 4 | 6/1 | .0834 | .0834 | .0834 | .25 | 39 | 16 | 55 | 1780 | .3917 | .4770 | 145 |
Swanate/AW | 4 | 7/1 | .0772 | .103 | .103 | .257 | 39 | 24 | 63 | 2280 | .3814 | .4642 | 148 |
Sparrow/AW | 2 | 6/1 | .1052 | .1052 | .1052 | .316 | 62 | 25 | 87 | 2760 | .2462 | .2997 | 194 |
Sparate/AW | 2 | 7/1 | .0974 | .1298 | .1298 | .325 | 62 | 38 | 100 | 3510 | .2396 | .2917 | 198 |
Robin/AW | 1 | 6/1 | .1181 | .1181 | .1181 | .354 | 78 | 31 | 109 | 3450 | .1950 | .2373 | 225 |
Raven/AW | 1/0 | 6/1 | .1327 | .1327 | .1327 | .398 | 99 | 39 | 138 | 4250 | .1547 | .1884 | 260 |
Quail/AW | 2/0 | 6/1 | .1489 | .1489 | .1489 | .447 | 124 | 50 | 174 | 5130 | .1227 | .1494 | 301 |
Pigeon/AW | 3/0 | 6/1 | .1672 | .1672 | .1672 | .502 | 156 | 63 | 219 | 6300 | .09747 | .1188 | 347 |
Penguin/AW | 4/0 | 6/1 | .1878 | .1878 | .1878 | .563 | 197 | 79 | 277 | 7690 | .07726 | .09422 | 402 |
Waxwing/AW | 266.8 | 18/1 | .1217 | .1217 | .1217 | .609 | 250 | 33 | 283 | 6820 | .06364 | .07776 | 451 |
Partridge/AW | 266.8 | 26/7 | .1013 | .0788 | .2363 | .642 | 251 | 98 | 349 | 10800 | .06169 | .07541 | 465 |
Ostrich/AW | 300.0 | 26/7 | .1074 | .0835 | .2506 | .68 | 283 | 110 | 393 | 12100 | .05489 | .06712 | 500 |
Merlin/AW | 336.4 | 18/1 | .1367 | .1367 | .1367 | .684 | 315 | 42 | 357 | 8540 | .05044 | .06175 | 522 |
Linnet/AW | 336.4 | 26/7 | .1137 | .0885 | .2654 | .72 | 317 | 123 | 440 | 13500 | .04897 | .05989 | 537 |
Oriole/AW | 336.4 | 30/7 | .1059 | .1059 | .3177 | .741 | 318 | 177 | 494 | 16700 | .04795 | .05861 | 547 |
Chickadee/AW | 397.5 | 18/1 | .1486 | .1486 | .1486 | .743 | 373 | 50 | 422 | 9780 | .04268 | .05230 | 580 |
Brant/AW | 397.5 | 24/7 | .1287 | .0858 | .2574 | .772 | 374 | 116 | 490 | 14100 | .04185 | .05124 | 592 |
Lbis/AW | 397.5 | 26/7 | .1236 | .0962 | .2885 | .783 | 374 | 146 | 520 | 15800 | .04144 | .05072 | 597 |
Lark/AW | 397.5 | 30/7 | .1151 | .1151 | .3453 | .806 | 375 | 209 | 584 | 19600 | .04059 | .04965 | 608 |
Pelican/AW | 477 | 18/1 | .1628 | .1628 | .1628 | .814 | 447 | 59 | 507 | 11500 | .03556 | .04344 | 651 |
Flicker/AW | 477 | 24/7 | .141 | .094 | .2819 | .846 | 449 | 139 | 589 | 16700 | .03487 | .04273 | 663 |
Hawk/AW | 477.0 | 26/7 | .1354 | .1053 | .316 | .858 | 449 | 175 | 624 | 18900 | .03453 | .04231 | 669 |
Hen/AW | 477.0 | 30/7 | .1261 | .1261 | .3783 | .883 | 450 | 251 | 701 | 23400 | .03382 | .04139 | 682 |
Osprey/AW | 556.5 | 18/1 | .1758 | .1758 | .1758 | .879 | 522 | 69 | 591 | 13200 | .03050 | .03749 | 715 |
Parakeet/AW | 556.5 | 24/7 | .1523 | .1015 | .3045 | .914 | 524 | 163 | 687 | 19300 | .02989 | .03667 | 731 |
Dove/AW | 556.5 | 26/7 | .1463 | .1138 | .3413 | .927 | 524 | 204 | 728 | 21900 | .02958 | .03627 | 737 |
Eagle/AW | 556.5 | 30/7 | .1362 | .1362 | 4086 | .953 | 525 | 293 | 818 | 26800 | .02899 | .03551 | 751 |
Peacock/AW | 605.0 | 24/7 | .1588 | .1058 | .3175 | .953 | 570 | 177 | 746 | 21000 | .02749 | .03377 | 770 |
Squab/AW | 605.0 | 26/7 | .1525 | .1186 | .3559 | .966 | 570 | 222 | 792 | 23600 | .02588 | .03341 | 777 |
Teal/AW | 605.0 | 30/19 | .142 | .0852 | .426 | .994 | 571 | 311 | 883 | 28500 | .02672 | .03274 | 791 |
Kingbird/AW | 636.0 | 18/1 | .188 | .188 | .188 | .94 | 596 | 79 | 675 | 15000 | .02667 | .03286 | 778 |
Rook/AW | 636.0 | 24/7 | .1628 | .1085 | .3256 | .977 | 599 | 186 | 785 | 22000 | .02616 | .03216 | 794 |
Grosbeak/AW | 636.0 | 26/7 | .1564 | .1216 | .3649 | .991 | 599 | 233 | 832 | 24800 | .02588 | .03179 | 801 |
Flamingo/AW | 666.6 | 24/7 | .1667 | .1111 | .3333 | 1.000 | 628 | 195 | 823 | 23100 | .02495 | .03069 | 818 |
Gannet/AW | 666.6 | 26/7 | .1601 | .1245 | .3736 | 1.014 | 628 | 245 | 872 | 26000 | .02470 | .03034 | 825 |
Starling/AW | 715.5 | 26/7 | .1659 | .129 | .3871 | 1.051 | 674 | 263 | 936 | 27500 | .02300 | .02830 | 863 |
Redwing/AW | 715.5 | 30/19 | .1544 | .0927 | .4633 | 1.081 | 676 | 368 | 1044 | 33400 | .02260 | .02777 | 878 |
Cuckoo/AW | 795.0 | 24/7 | .182 | .1213 | .364 | 1.092 | 749 | 232 | 981 | 27500 | .02093 | .02582 | 913 |
Drake/AW | 795 | 26/7 | .1749 | .136 | .408 | 1.107 | 749 | 292 | 1040 | 30500 | .02070 | .02549 | 922 |
Tern/AW | 795 | 45/7 | .1329 | .0886 | .2658 | 1.063 | 749 | 124 | 873 | 21500 | .02135 | .02638 | 896 |
Condor/AW | 795 | 54/7 | .1213 | .1213 | .364 | 1.092 | 749 | 232 | 981 | 27800 | .02091 | .02578 | 913 |
Mallard/AW | 795 | 30/19 | .1628 | .0977 | .4884 | 1.139 | 751 | 409 | 1160 | 37100 | .02033 | .02500 | 938 |
Ruddy/AW | 900 | 45/7 | .1414 | .0943 | .2828 | 1.131 | 848 | 140 | 988 | 24000 | .01886 | .02330 | 970 |
Canary/AW | 900 | 54/7 | .1291 | .1291 | .3873 | 1.162 | 848 | 263 | 1111 | 31000 | .01849 | .02286 | 986 |
Rail/AW | 954 | 45/7 | .1456 | .0971 | .2912 | 1.165 | 899 | 149 | 1047 | 25400 | .01779 | .02210 | 1003 |
Cardina/AW | 954 | 54/7 | .1329 | .1329 | .3987 | 1.196 | 899 | 279 | 1177 | 32900 | .01744 | .02161 | 1022 |
Ortolan/AW | 1033.5 | 45/7 | .1515 | .101 | .3031 | 1.212 | 973 | 161 | 1134 | 27200 | .01641 | .02044 | 1054 |
Crulew/AW | 1033.5 | 54/7 | .1383 | .1383 | .415 | 1.245 | 973 | 302 | 1275 | 35200 | .01609 | .01997 | 1074 |
Bluejay/AW | 1113 | 45/7 | .1573 | .1048 | .3145 | 1.258 | 1048 | 173 | 1222 | 29300 | .01606 | .01905 | 1103 |
Pheasant/AW | 1272 | 54/19 | .1535 | .0921 | .4604 | 1.381 | 1204 | 364 | 1568 | 42400 | .01315 | .01646 | 1216 |
Bobolink/AW | 1431 | 45/7 | .1783 | .1189 | .3566 | 1.427 | 1348 | 223 | 1571 | 37600 | .01186 | .01503 | 1283 |
Lapwing/AW | 1590 | 45/7 | .188 | .1253 | .3759 | 1.504 | 1498 | 248 | 1745 | 41800 | .01069 | .01366 | 1365 |
+Conductor temperature of 75ºC, ambient temperature 25ºC, emissivity 0.5, wind 2 ft./sec., in sun. |
ACSR/AW
Code word |
Size (AWG or kcmil) | Strand– ing (Al/AW) |
Diameter(ins.) | Weight per 1000 ft. (Lbs) |
Rated strength (Lbs) |
Resistance /1000 ft. |
Allowable ampacity+ (Amps) |
||||||
Individual wire | AW core |
Comp. cable |
Al | AW | Total | DC at 20ºC |
AC at 75ºC |
||||||
Al | AW | ||||||||||||
HIGH MECHANICAL STRENGTH | |||||||||||||
Grouse/AW | 80 | 8/1 | .1000 | .1670 | .1670 | .367 | 75.1 | 62.6 | 137.7 | 4890 | .1942 | .2357 | 227 |
Petrel/AW | 101.8 | 12/7 | .0921 | .0921 | .2763 | .460 | 96.0 | 133.9 | 229.9 | 9910 | .1425 | .1736 | 281 |
Minorca/AW | 110.8 | 12/7 | .0961 | .0961 | .2883 | .481 | 104.5 | 145.8 | 250.3 | 10800 | .1326 | .1594 | 297 |
Leghorn/AW | 134.6 | 12/7 | .1059 | .1059 | .3177 | .530 | 127.0 | 177.0 | 304.0 | 13000 | .1078 | .1313 | 335 |
Guinea/AW | 159.0 | 12/7 | .1151 | .1151 | .3453 | .576 | 150.0 | 209.1 | 359.1 | 15300 | .09123 | .1112 | 372 |
Dotterol/AW | 176.9 | 12/7 | .1214 | .1214 | .3642 | .607 | 166.8 | 232.7 | 399.5 | 16900 | .08201 | .09988 | 398 |
Dorking/AW | 190.8 | 12/7 | .1261 | .1261 | .3783 | .631 | 180.0 | 251.0 | 431.0 | 18300 | .07601 | .09261 | 418 |
Brahma/AW | 203.2 | 16/19 | .1127 | .0977 | .4885 | .714 | 191.7 | 411.0 | 602.7 | 27100 | .06570 | .07994 | 464 |
Cochin/AW | 211.3 | 12/7 | .1327 | .1327 | .3981 | .664 | 199.3 | 278.0 | 477.3 | 19800 | .06863 | .08364 | 445 |
+Conductor temperature of 75ºC, ambient temperature 25ºC, emissivity 0.5, wind 2 ft./sec., in sun. |
- Next: Overhead Aerial Bundle (AL/XLPE) Insulated ABC Cable-AS/NZS 3560.1 Standard
- Previous: Nyy/Nayy/Nycy/Nysy/Nycwy Copper Underground Electrical Power Cable