Product Description
450/750V Stranded copper Conductors PVC Insulated Thw Wire AWG8/10/12/14
.Brief construction
1) Conductor: Copper, solid or stranded.
2) Insulation: PVC.
3) No.cores: Single.
4) Common Size: 14AWG,12AWG,10AWG,8AWG
5) Color:Optional.
6)Packing:100m per roll
We can design and manufacture wires according to special requirements of customers.
Copper conductor PVC insulated electrical cable wire
Characteristics:
1). Rated voltage U0/U 300/500V and 450/750V
2). The long-time permissible temperature of cable: BV-105 below 105°C,and the other below 70°C.
3). Conductor maximum short circuit(not more than 5 seconds)temperature shall not be higher than 160°c. 4). The power cable is not limited by drop in level when being laid, and the ambient temperature shall not be lower than 0°c.
5). The bend radius: the external diameter of cable <25mm, and the bend radius is above 4 times of the external diameter of
cable. And the other is above 6 times of the external diameter of cable.
6). Perfect chemical stability, resistant against acids, alkalis, grease and organic solvents, and flame.
7). Light weight, perfect bending properties, installed and maintained easily and conveniently.
8). Insulation sheath material and color: PVC in red, black, blue, and any color as required.
9). Type: Single or twin cables with different colors Provides OEM according to requests of customer.
Product technical
Electric Wire PVC Insulated Wire Building Wire Thw
.Brief construction
1) Conductor: Copper, solid or stranded.
2) Insulation: PVC.
3) No.cores: Single.
4) Common Size: 14AWG,12AWG,10AWG,8AWG
5) Color:Optional.
6)Packing:100m per roll
We can design and manufacture wires according to special requirements of customers.
Copper conductor PVC insulated electrical cable wire
Characteristics:
1). Rated voltage U0/U 300/500V and 450/750V
2). The long-time permissible temperature of cable: BV-105 below 105°C,and the other below 70°C.
3). Conductor maximum short circuit(not more than 5 seconds)temperature shall not be higher than 160°c. 4). The power cable is not limited by drop in level when being laid, and the ambient temperature shall not be lower than 0°c.
5). The bend radius: the external diameter of cable <25mm, and the bend radius is above 4 times of the external diameter of
cable. And the other is above 6 times of the external diameter of cable.
6). Perfect chemical stability, resistant against acids, alkalis, grease and organic solvents, and flame.
7). Light weight, perfect bending properties, installed and maintained easily and conveniently.
8). Insulation sheath material and color: PVC in red, black, blue, and any color as required.
9). Type: Single or twin cables with different colors Provides OEM according to requests of customer.
Product technical
Electric Wire PVC Insulated Wire Building Wire Thw
Size of conductor | Nominal thickness of insulation mm |
Mean overall diameter Upper limit mm |
Approx. net weight per km (kg) |
|
Nominal cross-sectional area mm2 (one core cable) |
Number and diameter of wires no./mm |
|||
1.0 | 1/1.13 | 0.6 | 2.8 | 14 |
1.5 | 1/1.38 | 0.7 | 3.3 | 20 |
1.5 | 7/0.50 | 0.7 | 3.4 | 20 |
2.5 | 1/1.78 | 0.8 | 3.9 | 33 |
2.5 | 7/0.67 | 0.8 | 4.2 | 34 |
4 | 1/2.25 | 0.8 | 4.4 | 51 |
4 | 7/0.85 | 0.8 | 4.8 | 51 |
6 | 1/2.76 | 0.8 | 4.9 | 67 |
6 | 7/1.04 | 0.8 | 5.4 | 71 |
10 | 1/3.57 | 1.0 | 6.4 | 110 |
10 | 7/1.35 | 1.0 | 6.8 | 120 |
16 | 1/4.50 | 1.0 | 7.3 | 170 |
16 | 7/1.70 | 1.0 | 8.0 | 180 |
25 | 7/2.14 | 1.2 | 9.8 | 285 |
35 | 19/1.53 | 1.2 | 11.0 | 380 |
50 | 19/1.78 | 1.4 | 13.0 | 510 |
70 | 19/2.14 | 1.4 | 15.0 | 715 |
95 | 19/2.52 | 1.6 | 17.0 | 990 |
120 | 37/2.03 | 1.6 | 19.0 | 1230 |
150 | 37/2.25 | 1.8 | 21.0 | 1510 |
185 | 37/2.52 | 2.0 | 23.5 | 1900 |
240 | 61/2.25 | 2.2 | 26.5 | 2490 |
300 | 61/2.52 | 2.4 | 29.5 | 3050 |
400 | 61/2.85 | 2.6 | 33.5 | 3900 |
500 | 61/3.20 | 2.8 | 37.0 | 4880 |
Model :
Type | Name | Laying Site and Requirements | Long-time Permissible Working Temperature of Conductor(° C) |
227IEC01/05 BV BLV | Copper Conductor, PVC Insulated Wire | Fixed laid in the circumstance of indoor, conduit etc. | 70 |
Aluminium Conductor, PVC Insulated Wire | |||
227IEC 07 BV-90 | Heat Resistant Copper Conductor, PVC Insulated Wire at 90 |
Fixed laid in the circumstance of high temperature environment and can be laid indoor, conduit etc. |
90 |
BVR | Copper Conductor, PVC Insulated Flexible Wire | Fixed laid where flexibility is required. | 70 |
227-IEC10 BVV | Copper Conductor PVC Insulated and PVC Sheathed Round Wire | Fixed laid where high mechanical protection and moisture are required. They can be laid in the air or underground. | 70 |
BLVV | Aluminium Conductor PVC Insulated and PVC Sheathed Round Wire | ||
BVVB | Copper Conductor PVC Insulated and PVC Sheathed Flat Wire | ||
BLVVB | Aluminium Conductor PVC Insulated and PVC Sheathed Flat Wire | ||
227IEC 02 RV227 IEC 06 RV | Copper Conductor, PVC Insulated Flexible Connector | Mainly used at middle-light type movable euipments, instrument and meters, household appliances, power and lighting and the places where flexibility is required. | 70 |
227IEC 42 RVB | Copper Conductor, PVC Insulated Flat Flexible Connector | ||
RVS | Copper Conductor, PVC Insulated Flexible Twisting Connector | ||
227IEC52 RVV 227IEC53 RVV | Copper Conductor PVC Insulated and PVC Sheathed Round Flexible Connector(Light and Common Type) |