450/750V, 300/500V, 300/300V, Building Wire, Instrument Cable, Control Cable, Copper/PVC Cable
450/750V, 300/500V, 300/300V, Building Wire, Instrument Cable, Control Cable, Copper/PVC Cable
BV
Insulated
Stranded
Instrument
Copper
PVC
PVC
Round Wire
Construction, Instrument, Equipment
ISO9001, CCC, RoHS
IEC Type Test Report
Gdyg
GDYG
Wooden Reel, Coil, Plastic Barrel
0.5mm2 – 300mm2
Guandong Province, China
8544492100
Product Description
Product Instroduction:
1. Standard: IEC60227, HD22.4, NFC-32-12-4.
2. Voltage: 450/750V, 300/500V,300/300V
3. Conductor: Copper, Aluminum.
4. Construction: Solid, Stranded wires, flexible
5. Numer of Cores: single core, two cores, 3 cores, multi-pairs,
6. Material of insulation: PVC, EPR
7. Insulation: PVC
8. Cross Section area of conductor: 0.5mm2, 1mm2, 2mm2, 1.5mm2, 6mm2, 10mm2……….300mm2
These cables are applied to construction, telecom, instrument, equipent, computer, electric appliances, robot, AI industries.
These cables are also customized to manufacture flame retardant PVC cables, the main features of the flame retardant PVC cable or wire is hard to get fire or that the continuous burning of cables is very limited when it is on fire.It applies to the places with special demands for flame retardant property. Flame retardant cable is classified as class A,B or C. Amongst the 3 class , class A is the best in aspect of flame retardant.
Fire-resistance cable can operate normally for some time when it is burning except that it can transmit electrical power under normal condition. It is used in the places with special demands for fire resistance property.
1. Standard: IEC60227, HD22.4, NFC-32-12-4.
2. Voltage: 450/750V, 300/500V,300/300V
3. Conductor: Copper, Aluminum.
4. Construction: Solid, Stranded wires, flexible
5. Numer of Cores: single core, two cores, 3 cores, multi-pairs,
6. Material of insulation: PVC, EPR
7. Insulation: PVC
8. Cross Section area of conductor: 0.5mm2, 1mm2, 2mm2, 1.5mm2, 6mm2, 10mm2……….300mm2
These cables are applied to construction, telecom, instrument, equipent, computer, electric appliances, robot, AI industries.
These cables are also customized to manufacture flame retardant PVC cables, the main features of the flame retardant PVC cable or wire is hard to get fire or that the continuous burning of cables is very limited when it is on fire.It applies to the places with special demands for flame retardant property. Flame retardant cable is classified as class A,B or C. Amongst the 3 class , class A is the best in aspect of flame retardant.
Fire-resistance cable can operate normally for some time when it is burning except that it can transmit electrical power under normal condition. It is used in the places with special demands for fire resistance property.
60227 IEC 01(BV) GB/T5023-2008
Nominal cross- section
mm2 |
Conductor Type | Upper limit Of O.D.
mm |
20ºC Max.D.C. resistance at 20ºC
Ω/km |
70ºC Min.insulation resistance at 70ºC
MΩ ·km |
Approx. ampacity A | Reference weight of cable kg/km |
1.50 | 1 | 3.2 | 12.1 | 0.011 | 25 | 20.0 |
1.50 | 2 | 3.3 | 12.1 | 0.010 | 25 | 21.5 |
2.50 | 1 | 3.9 | 7.41 | 0.010 | 34 | 31.8 |
2.50 | 2 | 4.0 | 7.41 | 0.009 | 34 | 34.8 |
4.00 | 1 | 4.4 | 4.61 | 0.0085 | 44 | 46.8 |
4.00 | 2 | 4.6 | 4.61 | 0.0077 | 44 | 50.3 |
6.00 | 1 | 5.0 | 3.08 | 0.0070 | 58 | 66.50 |
6.00 | 2 | 5.2 | 3.08 | 0.0065 | 58 | 71.00 |
10 | 2 | 6.7 | 1.83 | 0.0065 | 79 | 116.0 |
16 | 2 | 7.8 | 1.15 | 0.0050 | 111 | 180 |
25 | 2 | 9.7 | 0.727 | 0.0050 | 146 | 277 |
35 | 2 | 10.9 | 0.524 | 0.0040 | 180 | 375 |
50 | 2 | 12.8 | 0.387 | 0.0045 | 282 | 536 |
70 | 2 | 14.6 | 0.268 | 0.0035 | 281 | 706 |
95 | 2 | 17.1 | 0.193 | 0.0035 | 344 | 977 |
120 | 2 | 18.8 | 0.153 | 0.0032 | 397 | 1231 |
150 | 2 | 20.9 | 0.124 | 0.0032 | 456 | 1503 |
185 | 2 | 23.3 | 0.0991 | 0.0032 | 519 | 1870 |
240 | 2 | 26.6 | 0.0754 | 0.0032 | 592 | 2457 |
300 | 2 | 29.6 | 0.0601 | 0.0030 | 685 | 3053 |
400 | 2 | 33.2 | 0.0470 | 0.0028 | 799 | 3948 |