4 Core XLPE Power Cable Supply Kplc
Product Description
1. Voltage:
According to the IEC 60502, the voltage is 0.6/1(1.2)kv, 1.8/3(3.6) kv, 3.6/6(7.2)kv, 6/10(12)kv, 8.7/15(17.5)kv, 12/20(24)kv, 18/30(36)kv, 21/35kv;
2. Conductor:
Conductor is accoriding to IEC60228, the class 1 or the class 2, bare annealed copper wire or metallic annealed copper wire, aluminium or aluminium alloy;
3.Insualtion:
PVC can be used for 0.6/1kv, 1.8/3kv, as well as 3.6/6kv;
XLPE can be used for every voltage according to the IEC 60502;
The thickness of PVC insulation 3.6/6kv is 3.4mm;
The thickness of XLPE insulation for 3.6/6kv is 2.5mm for <=185mm2;
For 6/10kv is 3.4mm, for 8.7/15kv is 4.5mm, for 12/20kv is 5.5mm, for 18/30kv is 8.0mm
4.Shied:
The metallic shield layer is essential for every insulated cores.
The conductor shield and insulation shield are both needed, except the 2 conditions as below:
For the 3.6/6kv, EPR/HEPR insulated, the shield layer can be omitted;
For the 3.6/6kv PVC insulated styles, the shield layer can also be omitted.
Table of the voltage, cores and cross-section
Item | Category A ,B | 3.6/6kV | 6/10kV | 8.7/15kV | 12/20kV | 18/30kV | 21/35kV |
Category A ,B | 6/6kV | 8.7/10kV | 12/15kV | 18/20kV | – | 26/35kV | |
Single core | mm2 | 25-1200 | 25-1200 | 35-1200 | 50-1200 | 50-1200 | 50-1200 |
Three core | mm2 | 25-400 | 25-400 | 35-400 | 50-400 | 50-400 | 50-400 |
Cable name and application
Type | Designation | Applications |
YJV | Copper conductor,XLPE insulated,PVC sheathed power cable |
For laying indoors,in tunnel or cable trench,unable to bear external mechanical forces.Single core cable is not allowed to laid in magnetic duct. |
YJLV | Aluminum conductor,XLPE insulated,PVC sheathed power cable |
|
YJY | Copper conductor, XLPE insulated,PE sheathed power cable |
|
YJLY | Aluminum conductor, XLPE insulated,PE sheathed power cable |
|
YJV22 | Copper conductor,XLPE insulated,steel tape armoured,PVC sheathed power cable |
For laying indoors,in tunnel in cable trench,or direct in ground,able to bear external mechanical forces.Single core cable is not allowed to laid in magnetic duct. |
YJLV22 | Aluminum conductor,XLPE insulated,steel tape armoured,PVC sheathed power cable |
|
YJV23 | Copper conductor,XLPE insulated,steel tape armoured,PE sheathed power cable |
|
YJLV23 | Aluminum conductor,XLPE insulated,steel tape armoured,PE sheathed power cable |
|
YJV32 | Copper conductor,XLPE insulated,steel wire armoured,PVC sheathed power cable |
For laying indoors,in tunnel cable trench,well or direct in ground,able to bear external mechanical forces and certain pulling force. |
YJLV32 | Aluminum conductor,XLPE insulated,steel wire armoured,PVC sheathed power cable |
|
YJV33 | Copper conductor,XLPE insulated,steel wire armoured,PE sheathed power cable |
|
YJLV33 | Aluminum conductor,XLPE insulated,steel wire armoured,PE sheathed power cab |