4 Core 50mm 70mm2 95mm2 ABC Service Drop Aerial Bundled Cable

4 Core 50mm 70mm2 95mm2 ABC Service Drop Aerial Bundled Cable

4 Core 50mm 70mm2 95mm2 ABC Service Drop Aerial Bundled Cable

abc cable 50mm

Hongda

ABC Cable

ISO, CCC, SGS

Aluminum / AAC

Round Wire

Crosslinking

XLPE

DC Cable

Low and Medium Voltage Cable

Overhead, Street Lighting

IEC60502, NFC33 209, BS 7870-5

Available on 500 Metre Wooden Drums

4kv

0.6/1kv

Hongda Cable

Wooden Drum or as Customer Requirement

6mm2 to 120mm2

China

8544492100

Product Description

4 Core 50 mm 70mm2 95mm2 ABC Service Drop Aerial Bundled Cable
Aerial Bundle Conductor (ABC)

Description

Cable Description

Self-supporting system consists of four cores of hard-drawn stranded and compacted aluminium conductors of equal cross-section and insulated with carbon-loaded XLPE to ensure UV protection. All cores strained equally. Supporting-core system consists of three phase cores of hard-drawn stranded compacted aluminium conductors insulated with carbon-loaded XLPE laid up around an aluminium-alloy supporting core insulated with carbon loaded XLPE to ensure UV protection. Additional sub-conductors optional in both self-supporting-core systems.

Installation Information
· Economical
· Flexible
· Safe
· Vandal proof
· Durable
· Aesthetically pleasing
· Adaptable

Technical Data

Rated voltage kV 0.6/1
Test voltage Veff kV 4
Laying temperature °C min. -20
Operating temperature °C -30 ~ +80
Conductor temperature °C max. +80
Short-circuit temperature °C/s max. +130 /5
Bending radius (min.)   18 × o of cable

Aerial Bundle Conductor (ABC) Application
Bundle conductor for overhead distribution network without and with public lighting. (between pole to pole)

Construction:

Conductor Phase Stranded All Aluminium conductor (AAC)
Neutral/Messenger Stranded All Alloy Aluminium Conductor (AAAC)
Insulation Extrude of XLPE, capable for continous operation at maximum cable’s temperature.

Properties:
Aluminum XLPE cable Insulated Overhead ABC Cable
 

number of cores x nominal cross section max. conductor- resistance min. breaking load of conductor strand Current rating in the air Outer diameter Total weight
mm^2 Ohm/km kN A mm kg/km
1x 16 RM 1,910 2,5 72 80 74
1x 25 RM 1,200 4,0 107 90 106
1x 35 RM 0,868 5,5 132 105 138
1x 50 RM 0,641 8,0 165 118 182
1x 70 RM 0,443 10,7 205 130 252
1x 95 RM 0,320 13,7 240 154 333
1x 120 RM 0,253 18,6 290 170 408
1x 150 RM 0,206 23,2 334 190 502
1x 185 RM 0,164 28,7 389 210 611
1x 240 RM 0,125 37,2 467 240 801
2x 16 RM 1,910 2,5 72 156 147
2x 25 RM 1,200 4,0 107 180 208
2x 35 RM 0,868 5,5 132 200 277
2x 50 RM 0,641 8,0 165 235 361
2x 70 RM 0,443 10,7 205 254 505
2x 95 RM 0,320 13,7 240 303 666
2x 150 RM 0,206 23,2 334 380 1004
4x 16 RM 1,910 2,5 72 188 286
4x 25 RM 1,200 4,0 107 212 430
4x 35 RM 0,868 5,5 132 241 553
4x 50 RM 0,641 8,0 165 278 746
4x 70 RM 0,443 10,7 205 318 1009
4x 95 RM 0,320 13,7 240 378 1332
4x 120 RM 0,253 18,6 290 544 1632
4x 50 + 1x 25 RM 0,641/1,200 8,0/4,0 165/107 319 814
4x 50 + 1x 35 RM 0,641/0,868 8,5/5,5 165/132 319 845
4x 70 + 1x 25 RM 0,443/1,200 10,7/4,0 205/107 360 1105
4x 70 + 2x 25 RM 0,443/1,200 10,7/4,0 205/107 400 1217
4x 95 + 1x 25 RM 0,320/1,200 13,7/4,0 240/107 418 1438
4x 95 + 2x 25 RM 0,320/1,200 13,7/4,0 240/107 420 1544
4×120 + 1x 25 RM 0,253/1,200 18,6/4,0 290/107 590 2050

other cross-sections on request of Aerial Bundle Conductor (ABC)

Physical Properties
Cable size Insulation Thickness Approx Maximum Diameter Approx. Net. Weight Standard Length
Phase Neutral / Messenger Public Lighting Phase Neutral/Messenger Public Lighting
mm2 mm mm mm mm mm mm kg/km m
2×25+25 1.4 1.4 10.0 10.0 10.0 338 500
2×35+25 1.6 1.4 11.2 10.0 10.0 394 500
2×50+35 1.6 1.6 12.6 11.2 11.2 526 500
2×70+50 1.8 1.6 15.4 12.6 12.6 760 500
2×95+70 2.0 1.8 17.0 15.4 15.4 975 500
3×25+25 1.4 1.4 10.0 10.0 10.0 452 500
3×35+25 1.6 1.4 11.2 10.0 10.0 537 500
3×50+35 1.6 1.6 12.6 11.2 11.2 717 500
3×70+50 1.8 1.6 15.4 12.6 12.6 1057 500
3×95+70 2.0 1.8 17.0 15.4 15.4 1360 500
3×25+25+2×16 1.4 1.4 1.2 10.0 10.0 8.1 602 500
3×35+25+2×16 1.6 1.4 1.2 11.2 10.0 8.1 687 500
3×50+35+2×16 1.6 1.6 1.2 12.6 11.2 8.1 867 500
3×70+50+2×16 1.8 1.6 1.2 15.4 12.6 8.1 1207 500
3×95+70+2×16 2.0 1.8 1.2 17.0 15.4 8.1 1510 500
3×25+25+16 1.4 1.4 1.2 10.0 10.0 8.1 527 500
3×35+25+16 1.6 1.4 1.2 11.2 10.0 8.1 612 500
3×50+35+16 1.6 1.6 1.2 12.6 11.2 8.1 792 500
3×70+50+16 1.8 1.6 1.2 15.4 12.6 8.1 1132 500
3×95+70+16 2.0 1.8 1.2 17.0 15.4 8.1 1435 500

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information

For more information, don’t hesitate to contact Vivian Yuan on +86-18339931106