3X70+2X35mm2 Copper XLPE Insulated PVC Sheathed Power Cable

3X70+2X35mm2 Copper XLPE Insulated PVC Sheathed Power Cable

3X70+2X35mm2 Copper XLPE Insulated PVC Sheathed Power Cable

3×70+2×35

Construction, Underground, Industrial, Power Station

1kv

DC Cable

XLPE

PVC

Round Wire

Bare Copper Wire

ISO, CCC, VDE

YJV

Jytop

Phase 0.268 Ohm/Km & Earth 0.524 Ohm/Km

Phase 0.193 Ohm/Km & Earth 0.387 Ohm/Km

Phase 0.153 Ohm/Km & Earth 0.268 Ohm/Km

Phase 1.83 Ohm/Km & Earth 3.08 Ohm/Km

ASTM, AS/NZS, BS, CSA, DIN, IEC…

JYTOP

Packed in Reels

as per popular standards or clients's requirement

Zhengzhou, China

8544492100

Product Description

3X70+2X35mm2 copper XLPE Insulated PVC Sheathed Power Cable

1. Applications
This product is applied to the fixed installation, power transmission and power distribution circuit of rated voltage 35KV and below.
XLPE insulated power cable has a number of advantages compared with paper insulated and PVC insulated cables. XLPE cable has high electric property, mechanical property, heat aging performance, environmental stress crack resistance, chemical corrosion resistance, and it also has simple structure, convenient operation and it is not restricted by laying in large difference of level. It can be applied in high temperature of 90 degree for a long time.

2. Standard
IEC 60502, IEC60332, IEC 60754

3. Specification
Rated Voltage, No. of Core and Range of Sectional Area

Rated voltage (kv)
Sectional area (mm2)
No. of core
1st class 0.6/1 3.6/6 6/6 8.7/10 12/20 18/20 21/35 26/35
2nd class 6/10 8.7/15 18/30
1 Core 2.5-400 25-500 25-500 25-500 35-500 50-500 50-500 50-500
2 Core 2.5-300
3 Core 2.5-300 25-400 25-400 25-400 35-400 50-400 50-400 50-400
4 Core 2.5-300
5 Core 2.5-300

4. The main Technical Index of the cable
1). DC resistance: conductor resistance of finished cable at 20ºC per kilometer is not more than the following values.

Nominal section area (mm2) 1.5 2.5 4 6 10 16 25 35 50 70
Copper core 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268

2). Voltage Test and Partial Discharge Test

Rate voltage Uo (kv)
Item
0.6/1 1.8/3 3.6/6 6/6 6/10 8.7/10 8.7/15 12/20 18/20 18/30 21/35 26/35
Voltage Test voltage 3.5 6.5 12.5 21 30.5 42 63 73.5 91
Test time 5 5 5 5 5 5 5 5 5
Partial discharge test Test voltage 6.2 10.4 15.1 20.8 31.1 36.3 45
Discharge capacity 10 10 10 10 10 10 10

Main technical data of 0.6/1KV 5 core CU/XLPE/PVC or PE Power cable

Cable size

Conductor type Nominal thickness of XLPE insulation(mm) Nominal thickness of PVC or PE sheath(mm) Approx. cable overall diameter (mm) Max. D.C resistance @ 20 0 C (Ω/km)
Phase
core
Earth
core
Phase
core
Earth
core
Phase
core
Earth
core
3×2.5+2×1.5mm 2 RE RE 0.7 0.7 1.8 11.9 7.41 12.1
3×4+2×2.5mm 2 RE RE 0.7 0.7 1.8 13.1 4.61 7.41
3×6+2x4mm 2 RE RE 0.7 0.7 1.8 14.5 3.08 4.61
3×10+2x6mm 2 RM RE 0.7 0.7 1.8 17.1 1.83 3.08
3×16+2x10mm 2 RM RM 0.7 0.7 1.8 20.2 1.15 1.83
3×25+2x16mm 2 SM RM 0.9 0.7 1.8 22.7 0.727 1.15
3×35+2x16mm 2 SM RM 0.9 0.7 1.8 24.2 0.524 1.15
3×50+2x25mm 2 SM SM 1.0 0.9 1.9 27.5 0.387 0.727
3×70+2x35mm 2 SM SM 1.1 0.9 2.0 31.2 0.268 0.524
3×95+2x50mm 2 SM SM 1.1 1.0 2.2 35.8 0.193 0.387
3×120+2x70mm 2 SM SM 1.2 1.1 2.3 39.7 0.153 0.268
3×150+2x70mm 2 SM SM 1.4 1.1 2.4 42.7 0.124 0.268
3×185+2x95mm 2 SM SM 1.6 1.1 2.6 48.2 0.0991 0.193
3×240+2x120mm 2 SM SM 1.7 1.2 2.8 53.8 0.0754 0.153
3×300+2x150mm 2 SM SM 1.8 1.4 3.0 59.4 0.0601 0.124

Note: RE= round conductor RM = stranded conductor SM=sectional conductor