33kv Power Cable, Nylon Sheath Anti-Termite, HDPE Sheath, AS/NZS Standard

33kv Power Cable, Nylon Sheath Anti-Termite, HDPE Sheath, AS/NZS Standard

33kv Power Cable, Nylon Sheath Anti-Termite, HDPE Sheath, AS/NZS Standard

BM 3×120

Construction, Underground, Power Station

High Voltage Cable

AC Cable

XLPE

HDPE

Round Wire

Bare Copper Wire

ISO, CCC, CE

Cu/XLPE/Cu Tape/PVC/Sta/PVC

Yifang

Yifang

Wooden Drum or Wooden&Steel Drum

3x120mm2

Henan Province, China

8544601200

Product Description

33KV Compacted Round Copper Conductor Nylon anti-termite HDPE Cable,AS/NZS standard

Description 35KV Compacted Round Copper Conductor Double Steel Tape Armoured Cable
Construction: Compacted stranded circular copper conductor, extruded semi-conducting compound as conductor shield, cross-linked polyethylene (XLPE) insulation, semi-conducting compound as insulation shield, copper tape or combination of copper wire and tape as metallic screen, three cores assembled together with non-hygroscopic polypropylene filler, wrapped with binder tape, PVC inner covering as armoring bedding, galvanized steel tape armored, PVC outer sheath.
2.Operating Characteristics
Rated voltage U0/U(Um): 26/35(40.5)kV
U0 is the rated power frequency voltage between conductor and earth or metallic screen for which the cable is designed;
U is the rated power frequency voltage between conductors for which the cable is designed;
Um is the maximum value of the "highest system voltage" for which the equipment may be used.
Max. permissible continuous operating temperature of conductor: 90 °C
Max. temperature of conductor during short-circuit (5s max. duration) shall not exceed: 250 °C
The ambient temperature under installation should not be lower than: 0 °C
The bending radius of cable is recommended as following:
For single core cable: not less than 20 times of the diameter of cable
For three core cable: not less than 15 times of the diameter of cable

3.Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, outdoors, in tunnel or in cable trench, unable to bear external mechanical force.
Single core cable in magnetic duct is not permissible.

4.Main technical data of 26/35KV, three cores, Copper conductor, XLPE insulated, galvanized steel wire armored and PVC or PE sheath cable

Size Nominal thickness of XLPE insulation(mm) Approx. thickness of copper tape screen (mm) Approx. diameter of steel wire (mm) Nominal thickness of PVC or PE(mm) Approx. overall diameter of finished cable(mm) Max. conductor D.C resistance @ 20 0 C (Ω/km)
3x50mm 2 10.5 0.10 3.15 3.8 92.3 0.387
3x70mm 2 10.5 0.10 3.15 3.9 96.4 0.268
3x95mm 2 10.5 0.10 3.15 4.1 100.4 0.193
3x120mm 2 10.5 0.10 3.15 4.2 103.8 0.153
3x150mm 2 10.5 0.10 3.15 4.3 107.8 0.124
3x185mm 2 10.5 0.10 3.15 4.4 111.5 0.0991
3x240mm 2 10.5 0.10 3.15 4.6 117.3 0.0754
3x300mm 2 10.5 0.10 3.15 4.7 122.1 0.0601
3x400mm 2 10.5 0.10 3.15 5.0 130.0 0.0470