11kv XLPE/Swa Armoured/PVC Power Cable 3core 70mm2

11kv XLPE/Swa Armoured/PVC Power Cable 3core 70mm2

11kv XLPE/Swa Armoured/PVC Power Cable 3core 70mm2

YJV32

Construction, Underground, Industrial, Power Station

Low and Medium Voltage Cable

DC & AC

XLPE

PVC or PE or HDPE or LSZH

Round Wire

Copper or Aluminum

ISO, CCC, CE

Yjv32

Yifang

1 or 3

35mm2~

Red,Black or as Your Requirement

Aluminum or Copper

Yifang Cable

Drum or According to U Request

IEC, BS, DIN, NFC, ASTM, etc

Zhengzhou, Henan, China

8544492100

Product Description

11KV XLPE/STA armoured/PVC Power cable 3C35MM2

armoured XLPE insulated medium voltage cable

Medium Voltage Power Cable is used in fixed laying to distribute the electricity in the AC rated voltage 35kV and under 35kV transmission line.
The Max operation temperature of cable conductor is 90 deg., the operation temperature for conductor in the condition of short circuit(not more 5 seconds) should not be above 250 deg.
The laying temperature should not be below 0 deg.
Features:
1) copper or aluminium conductor, XLPE insulated, PVC or PE sheathed cable;
2) copper or aluminium conductor, XLPE insulated, steel wire or steel tape armour, PVC or PE sheathed cable.
Note:
We can also produce anti-termite, water-proof, low smoke and low halogen or non-halogen cables respectively according to the requirements of customers.
3) Rated voltage: 3.6/6kv, 6/6kv, 6/10kv, 6.35/11kv, 8.7/10kv, 8.7/15kv, 12/20kv, 18/30kv, 21/35kv, 18/36kv.
Specifications:
1) Conductor cores: 1 or 3
2) Cross sectional area: 25-800sqmm
3) Standard: IEC or other requirements
Packing:
In wooden drums, steel-wooden drums, steel drum or as per the requirements of customers.

STANDARDS
IEC BS DIN ASTM CSA NFC AS

Class 2 stranded conductors for single-core and multi-core cables
1 2 3 4 5 6 7 8 9 10
Nominal crosssectional area Minimum number of wires in the conductor Maximum resistance of conductor at 20ºC
Circular Circular compacted Shaped Annealed copper conductor Aluminium or aluminium alloy conductor
Cu Al Cu Al Cu Al Plain wires Metal-coated wires
mm2 Ω/KM Ω/KM Ω/KM
0.5 7 36 36.7
0.75 7 24.5 24.8
1 7 18.1 18.2
1.5 7 6 12.1 12.2
2.5 7 6 7.41 7.58
4 7 6 4.61 4.7
6 7 6 3.08 3.11
10 7 7 6 6 1.83 1.84 3.08
16 7 7 6 6 1.15 1.16 1.91
25 7 7 6 6 6 6 0.727 0.734 1.2
35 7 7 6 6 6 6 0.524 0.529 0.868
50 19 19 6 6 6 6 0.387 0.391 0.641
70 19 19 12 12 12 12 0.268 0.27 0.443
95 19 19 15 15 15 15 0.193 0.195 0.32
120 37 37 18 15 18 15 0.153 0.154 0.253
150 37 37 18 15 18 15 0.124 0.126 0.206
185 37 37 30 30 30 30 0.0991 0.1 0.164
240 37 37 34 30 34 30 0.0754 0.0762 0.125
300 61 61 34 30 34 30 0.0601 0.0607 0.1
400 61 61 53 53 53 53 0.047 0.0475 0.0778
500 61 61 53 53 53 53 0.0368 0.0369 0.0605
630 91 91 53 53 53 53 0.0283 0.0286 0.0469
800 91 91 53 53 0.0221 0.0224 0.0367
1000 91 91 53 53 0.0176 0.0177 0.0291

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.