10mm2 Copper Electrical Wire PVC Insulated Copper Wire
10mm2 Copper Electrical Wire PVC Insulated Copper Wire
BV
Insulated
Stranded
Housing
Copper
No Jacket
PVC
Round Wire
Housing
ISO9001, CCC
OEM
NO
in Roll or in Pallent
10mm2
Henan
8544492100
Product Description
Description
PVC insulated wire belong to the series of laying electric wires, which is mainly suitable for laying at the fixed places. It is widely used as connectors of drive, lighting, electric equipments, instrument and telecommunication equipments with rated voltage 450/750V or below. Part of the plastic wires are used at the equipment with AC rated voltage 300/300V or below.
Features
1. The rated voltage U0 / U 450/750V
2. Cable conductor long-term work for 90 ° C temperature of cable
3. The smallest bending radius is six times the diameter of cable
4. Cable shall not be in the sunlight long exposure to
5. The bottom line of cable core must good grounding
Application
Used in electronics, instruments and electronic equipment and automatic generation device with the power cord, line and signal transmission lines, concrete can be used for anti-theft alarm system, building talkback system, instrument and meter, and monitoring control such as the installation of surveillance.
Manufacturing Standards GB/T 12706-2008, IEC 60502-2
Nominal sectional area mm2 |
Conductor No/Dia. mm |
Nominal Insulated thick mm |
Max overall Dia. mm |
Condcutor Resistance at 20 |
Min insulated resistance at 70MΩ/km |
Weight Kg/km |
||
Cu | Al | Cu | Al | |||||
1.5 | 1/1.38 | 0.7 | 3.3 | 12.1 | – | 0.011 | 19.2 | – |
1.5 | 7/0.52 | 0.7 | 3.5 | 12.1 | – | 0.010 | 20.6 | – |
2.5 | 1/1.78 | 0.8 | 3.9 | 7.41 | 11.8 | 0.010 | 30.8 | 15.0 |
4 | 1/2.25 | 0.8 | 4.4 | 4.61 | 7.39 | 0.0085 | 45.5 | 21.0 |
6 | 1/2.76 | 0.8 | 4.9 | 3.08 | 4.91 | 0.0070 | 65.0 | 29.0 |
10 | 7/1.35 | 1.0 | 7.0 | 1.83 | 3.08 | 0.0065 | 110.0 | 52.0 |
16 | 7/1.70 | 1.0 | 8.0 | 1.15 | 1.91 | 0.0050 | 170.0 | 70.0 |
25 | 7/2.14 | 1.2 | 10.0 | 0.727 | 1.20 | 0.0050 | 270.0 | 110.0 |
35 | 7/2.52 | 1.2 | 11.5 | 0.524 | 0.868 | 0.0040 | 364.0 | 150.0 |
50 | 19/1.78 | 1.4 | 13.0 | 0.387 | 0.641 | 0.0045 | 500.0 | 200.0 |
70 | 19/2.14 | 1.4 | 15.0 | 0.268 | 0.443 | 0.0035 | 688.0 | 269.0 |
95 | 19/2.52 | 1.6 | 17.5 | 0.193 | 0.320 | 0.0035 | 953.0 | 360.0 |
120 | 37/2.03 | 1.6 | 19.0 | 0.153 | 0.253 | 0.0032 | 1168.0 | 449.0 |
150 | 37/2.25 | 1.8 | 21.0 | 0.124 | 0.206 | 0.0032 | 1466.0 | 551.0 |
185 | 37/2.52 | 2.0 | 32.5 | 0.099 | 0.164 | 0.0032 | 1808.0 | 668.0 |
Flexible wire
Nominal sectional area mm2 |
Conductor No/Dia. mm |
Nominal Insulated thick mm |
Max overall Dia. mm |
Condcutor Resistance at 20 |
Min insulated resistance at 70MΩ/km |
Weight Kg/km |
2.5 | 9/0.41 | 0.8 | 4.2 | 7.41 | 0.011 | 33.0 |
4 | 19/0.52 | 0.8 | 4.8 | 4.61 | 0.009 | 48.0 |
6 | 19/0.64 | 0.8 | 5.6 | 3.08 | 0.0084 | 68.0 |
10 | 49/0.52 | 1.0 | 7.6 | 1.83 | 0.0072 | 115.0 |
16 | 49/0.64 | 1.0 | 8.8 | 1.15 | 0.0062 | 176.0 |
25 | 98/0.58 | 1.2 | 11.0 | 0.727 | 0.0058 | 272.0 |
35 | 133/0.58 | 1.2 | 12.5 | 0.524 | 0.0052 | 384.0 |
50 | 133/0.68 | 1.4 | 16.5 | 0.387 | 0.0051 | 510.0 |
70 | 189/0.68 | 1.4 | 16.5 | 0.268 | 0.0045 | 714.0 |
95 | 259/0.68 | 1. | 19.5 | 0.139 | 0.0035 | 965.0 |
120 | 259/0.76 | 1.8 | 22.0 | 0.153 | 0.0032 | 1210.0 |
150 | 259/0.85 | 1.8 | 25.0 | 0.124 | 0.0032 | 1510.0 |
- Next: Electric Projects Used 11kv Aluminum Conductor Mv Armored Cable
- Previous: 2.5mm2 Housing Building Electrical Wire PVC Insulated Copper Wire
Contact us