1.5mm 2.5mm Fire Resistant Single Core Fire Performance Cwz Cable

1.5mm 2.5mm Fire Resistant Single Core Fire Performance Cwz Cable

1.5mm 2.5mm Fire Resistant Single Core Fire Performance Cwz Cable

Fire Performance CWZ Cable

Insulated

Stranded

Overhead, Underground

Copper

No

PVC

Round Wire

LSOH

ISO9001, CCC

SGS

Hongda

Solid Conductor

Non Compacted Circular Stranded

Hongda Cable

100m Per Roll/Reel, or as Customer Requirement

1.5mm2 to 400mm2

Made in China

8544492900

Product Description

1.5mm 2.5mm Fire Resistant Single Core Fire Performance CWZ Cable

DESCRIPTION

Fire resistant cable to BS6387 CWZ as fire alarm cable (BS5839) and emergency lighting cable (BS5266)

Conductor: Stranded annealed stranded copper

Insulation: MGT (Mica glass tape) fire barrier tape

Sheath/Jacket: LSZH (Low Smoke Zero Halogen)

Colour: Black, blue, brown, green/yellow, grey & red

Voltage: 600/1000v

Operating temperature: Maximum 90°C, minimum bending 0°C

Approvals and Specifications

Manufactured to quality management systems independently
certificated as complying with the requirements of BSEN 9001

Applications: Suited for use on fire alarms and emergency lighting circuits and satisfies the requirements of the code of practice in each case (BS5839 Part 1, BS5266 Part 1)

Standards:
BS EN 50226-1:2001 (IEC60332-1) Common test methods for cables under fire conditions
BS EN 61034-1:2005 – smoke density
BS EN 50267-2-1:1999 (IEC 754-1) – acid gas evolution
IEC60331 – maintenance of circuit integrity when subjected to a 750 0C flame
BS6387:1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions.

Specification:
IEC standard size

Nominal Cross Sectional area
(mm2)
Conductor Thickness of insulation
(mm)
Overall Diameter Maximum continuous cuttent rating in free air
(A)
Minumum insulation resistance at 70ºC
(MΩ-km)
Cable weight (approx.)
Kg/Km
Standard length
(m)
Number of wire
(min)
Diameter Approx.
(mm)
Lower Limit
(mm)
Upper Limit
(mm)
1.5 1 1.38 0.7 2.6 3.2 21 0.011 22 100/C
1.5 7 1.50 0.7 2.7 3.3 21 0.010 24 100/C
2.5 1 1.78 0.8 3.2 3.9 29 0.010 32 100/C
2.5 7 2.01 0.8 3.3 4.0 29 0.009 35 100/C
4 1 2.25 0.8 3.6 4.4 37 0.0085 49 100/C
4 7 2.55 0.8 3.8 4.6 37 0.0077 50 100/C
6 1 2.76 0.8 4.1 5.0 48 0.0070 75 100/C
6 7 3.12 0.8 4.3 5.2 48 0.0065 80 100/C
10 1 3.57 1.0 5.3 6.4 67 0.0070 120 100/C
10 7 4.05 1.0 5.6 6.7 67 0.0065 130 100/C
16 7 5.10 1.0 6.4 7.8 92 0.0050 180 100/C
25 7 6.42 1.2 8.1 9.7 127 0.0050 280 100/C
35 19 4.59 1.2 9.0 10.9 157 0.0043 380 100/C
50 19 8.90 1.4 10.6 12.8 191 0.0043 500 500/D
70 19 10.7 1.4 12.1 14.6 244 0.0035 700 500/D
95 19 12.6 1.6 14.1 17.1 297 0.0035 1000 500/D
120 37 14.21 1.6 15.6 18.8 345 0.0032 1200 500/D
150 37 15.75 1.8 17.3 20.9 397 0.0032 1500 500/D
185 37 17.64 2 19.3 23.3 453 0.0032 1900 500/D
240 61 20.25 2.2 22.0 26.6 535 0.0032 2500 500/D
300 61 22.68 2.4 24.5 29.6 617 0.0030 3100 500/D
400 61 25.65 2.6 27.5 33.2 741 0.0028 3900 500/D
C: packing in coil.
D: packing in drum.

Single Core Copper Conductor Mica Tape Fire Resistant Cable
PACKAGING:
A: Roll of 100 m
B: Reel of 1500 m.
C: Reel of 1000 m.
D: Reel of 500 m.
E: Multiple Reels of 1000 m.
Z – Length to the client’s requirement.

Please contact us for technical support with the right cable selection for your power distribution projects and to discuss your maintenance or project specific requirements. We provide tailored solutions for this cable range which include storage, cutting to length, and 2 days collection as standard.

Any problem and inquiry pls contact with Vivian Yuan.
Phone number: +86-18339931106

Tags: , ,