0.6/1kv Copper or Aluminum PVC Insualted Armored Electrical Power Cable

0.6/1kv Copper or Aluminum PVC Insualted Armored Electrical Power Cable

0.6/1kv Copper or Aluminum PVC Insualted Armored Electrical Power Cable

4x35mm2

Construction, Underground, Industrial, Power Station

Low and Medium Voltage Cable

DC Cable

PVC

PVC

Round Wire

Aluminum

ISO, CCC, CE

YJLV22

Jytop

Factory

Henan China

Black,Red,Yellow,Blue,Brown,Green

95mm 120mm 150mm

Ce,ISO9001

Armor Cable

JYTOP

Reel or Drum

as per popular standards or clients's requirement

Zhengzhou, China

8544492100

Product Description

0.6/1kv copper or aluminum PVC insualted Armored Electrical Power Cable

Operating Characteristics of armed cable :
Rated voltage: 0.6/1(1.2)kV
Max. permissible continuous operating temperature of conductor: 70 °C
Max. temperature of conductor during short-circuit (5s max. duration) shall not exceed:
Nominal cross section of conductor ≤300mm2: 160 °C
Nominal cross section of conductor >300mm2: 140 °C

The ambient temperature under installation should not be lower than: 0 °C The bending radius of cable is recommended as following:

For single core cable: not less than 15 times of the diameter of cable
For multi-core cable: not less than 12 times of the diameter of cable

When the armored single core cable used for Alternative Current(AC) system, the armoring material should be non- magnetic.

3. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid in high fall area, able to bear external mechanical force, and certain pulling force.

4. Manufacturing Standards
IEC 60502-1 & Chinese national standard GB/T 12706-2008

We can produce above cables according to popular international standards such as ASTM,BS,DIN,NF &AS/NZ also.

5. Technical data of armor cable
Main technical data of 0.6/1KV, four cores, Aluminum conductor, PVC insulated, galvanized steel wire armored and PVC or PE sheath cables
CABLE CONSTRUCTION 0.6/1KV AL/PVC/SWA/PVC or PE

Cable size Conductor type Nominal thickness of PVC insulation (mm) Approx. diameter of steel wire(mm) Nominal thickness of PVC sheath(mm) Approx. cable overall diameter (mm) Max. D.C
resistance @
200C (Ω/km)
4×1.5mm2 RE or RM 0.8 0.8 1.8 14.9 18.1
4×2.5mm2 RE or RM 0.8 1.25 1.8 16.7 12.1
4x4mm2 RE or RM 1.0 1.25 1.8 18.8 7.41
4x6mm2 RE or RM 1.0 1.25 1.8 20.1 4.61
4x10mm2 RM 1.0 1.6 1.8 23.9 3.08
4x16mm2 RM 1.0 1.6 1.8 26.4 1.91
4x25mm2 SM 1.2 1.6 1.9 27.8 1.20
4x35mm2 SM 1.2 1.6 2.0 30.2 0.868
4x50mm2 SM 1.4 1.6 2.1 33.7 0.641
4x70mm2 SM 1.4 2.0 2.3 38.3 0.443
4x95mm2 SM 1.6 2.0 2.4 43.2 0.320
4x120mm2 SM 1.6 2.5 2.6 47.8 0.253
4x150mm2 SM 1.8 2.5 2.7 51.8 0.206
4x185mm2 SM 2.0 2.5 2.9 56.9 0.164
4x240mm2 SM 2.2 2.5 3.1 63.5 0.125
4x300mm2 SM 2.4 3.15 3.4 71.1 0.100
4x400mm2 SM 2.6 3.15 3.7 78.5 0.0778

Note: RE= round conductor RM = stranded conductor SM=sectional conductor

Main technical data of 0.6/1KV, 3+1 cores, Aluminum conductor, PVC insulated, galvanized steel wire armored and PVC or PE sheath cables
CABLE CONSTRUCTION 0.6/1KV AL/PVC/SWA/PVC or PE

Cable size

Conductor type Nominal thickness of
PVC
insulation(mm)
Approx. diameter
of steel wire(mm)
Nominal thickness
of PVC
sheath
(mm)
Approx. cable overall
diameter (mm)
Max. D.C
resistance @
200C (Ω/km)
Phase core Earth core Phase core Earth core Phase core Earth core
3×2.5+1.5mm2 RE RE 0.8 0.8 1.25 1.8 16.1 12.1 18.1
3×4+2.5mm2 RE RE 1.0 0.8 1.25 1.8 18.3 7.41 12.1
3×6+4mm2 RE RE 1.0 1.0 1.25 1.8 19.8 4.61 7.41
3×10+6mm2 RM RE 1.0 1.0 1.6 1.8 23.5 3.08 4.61
3×16+10mm2 RM RM 1.0 1.0 1.6 1.8 26.2 1.91 3.08
3×25+16mm2 SM RM 1.2 1.0 1.6 1.8 28.0 1.20 1.91
3×35+16mm2 SM RM 1.2 1.0 1.6 1.8 29.6 0.868 1.91
3×50+25mm2 SM SM 1.4 1.2 1.6 2.0 32.8 0.641 1.20
3×70+35mm2 SM SM 1.4 1.2 2.0 2.1 37.4 0.443 0.868
3×95+50mm2 SM SM 1.6 1.4 2.0 2.3 41.7 0.320 0.641
3×120+70mm2 SM SM 1.6 1.4 2.5 2.4 46.2 0.253 0.443
3×150+70mm2 SM SM 1.8 1.4 2.5 2.5 49.6 0.206 0.443
3×185+95mm2 SM SM 2.0 1.6 2.5 2.7 54.5 0.164 0.320
3×240+120mm2 SM SM 2.2 1.6 2.5 2.9 60.3 0.125 0.253
3×300+150mm2 SM SM 2.4 1.8 2.5 3.1 65.9 0.100 0.206
3×400+185mm2 SM SM 2.6 2.0 3.15 3.5 74.1 0.0778 0.164

Note: RE= round conductor RM = stranded conductor SM=sectional conductor

Main technical data of 0.6/1KV, five cores, Aluminum conductor, PVC insulated, galvanized steel wire armored and PVC or PE sheath cables
CABLE CONSTRUCTION 0.6/1KV AL/PVC/SWA/PVC or PE

Cable size Conductor type Nominal
thickness of PVC
insulation (mm)
Approx. diameter
of steel wire(mm)
Nominal
thickness of PVC sheath(mm)
Approx. cable
overall diameter (mm)
Max. D.C
resistance @
200C (Ω/km)
5×1.5mm2 RE or RM 0.8 1.25 1.8 16.7 18.1
5×2.5mm2 RE or RM 0.8 1.25 1.8 17.8 12.1
5x4mm2 RE or RM 1.0 1.25 1.8 20.2 7.41
5x6mm2 RE or RM 1.0 1.6 1.8 22.2 4.61
5x10mm2 RM 1.0 1.6 1.8 25.7 3.08
5x16mm2 RM 1.0 1.6 1.9 28.8 1.91
5x25mm2 SM 1.2 1.6 1.9 29.6 1.20
5x35mm2 SM 1.2 2.0 2.0 33.6 0.868
5x50mm2 SM 1.4 2.0 2.2 38.6 0.641
5x70mm2 SM 1.4 2.0 2.3 43.1 0.443
5x95mm2 SM 1.6 2.5 2.6 50.1 0.320
5x120mm2 SM 1.6 2.5 2.7 54.1 0.253
5x150mm2 SM 1.8 2.5 2.9 59.4 0.206
5x185mm2 SM 2.0 2.5 3.1 64.9 0.164
5x240mm2 SM 2.2 3.15 3.3 73.6 0.125
5x300mm2 SM 2.4 3.15 3.6 80.7 0.100

Note: RE= round conductor RM = stranded conductor SM=sectional conductor

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.