Product Description

Thhn-Thwn TW /THW Nylon Outer Jacket Wire Building Electric Wire

Applications:
1Type THHN/THWN2 building wire is intended for general purpose applications as defined by the National Electrical Code (NEC)Type THHN-THWN-2 is permitted for new construction or rewiring for 60 volt applications. Applications requiring Type THHN or THWN-
2, the conductor is appropriate for use in wet or dry locations at temperatures not to exceed 90°C or not to exceed 75°C in oil or coolants. Applications requiring Type MTW conductor is appropriate for use in dry locations at 90°C, or not to exceed 60°C in wet locations or where exposed to oils or coolants. Applications requiring Type AWM conductor is appropriate for use at temperatures to not exceed 105°C in dry locations.

Features:
Nylon outer jacket for easy pulling. VW-1 rated 14 AWG – 8 AWG. All sizes are rated gasoline and oil-resistant II.
Jacket: A tough, polyamide, Nylon outer covering per UL-1063 and UL-83.

Construction:

BUILDING WIRE
UL Listed Types TFFN, THHN/THWN
Insulation: PVC (Poly Vinyl Chloride) with Secondary Nylon Jacket
Conductor: Bare Copper Voltage Rating: 600 Volts

STANDARDS & REFERENCE:
THHN or THWN-2* or MTW (also AWM) meets or exceeds all applicable ASTM specifications, UL Standard 83, UL Standard 1063 (MTW), Federal Specification A-A-59544, and requirements of the National Electrical Code.
AWM Conductors shall be UL-listed Type THHN or THWN-2* or MTW or AWM, suitable for
Operation at 600 volts at conductor temperatures not to exceed 105° C.
Underwriters Laboratories Standards UL-83, UL-1063, UL-758
AWM Spec 1316, 1317, 1318, 1319, 1320, 1321
ASTM Stranding Class B3, B8, B787
Federal Specification A-A-59544
Canadian Standards Association C22.2 No. 75
NEMA WC70/ICEA S-95-658
Institute of Electrical and Electronics Engineers

parameter of Thhn-Thwn TW /THW Nylon Outer Jacket Wire Building Electric Wire

Conductor Insulation
Thickness
(mils)
Jacket thickness
(mils)
Nominal O.D Approx. net weight/1000ft Allowable ampacities
Size
(AWG or kcmil)
Strands Solid Stranded Solid Stranded 60 0 C 75 0 C 90 0 C
14 19 15 4 102 109 15 16 15 15 15
12 19 15 4 119 128 23 24 20 20 20
10 19 20 4 150 161 37 38 30 30 30
8 19 30 5 / 213 / 62 40 50 55
6 19 30 5 / 249 / 95 55 65 75
4 19 40 6 / 318 / 152 70 85 95
3 19 40 6 / 346 / 188 85 100 110
2 19 40 6 / 378 / 234 95 115 130
1 19 50 7 / 435 / 299 110 130 150
1/0 19 50 7 / 474 / 371 125 150 170
2/0 19 50 7 / 518 / 461 145 175 195
3/0 19 50 7 / 568 / 574 165 200 225
4/0 19 50 7 / 624 / 717 195 230 260
250 37 60 8 / 694 / 850 215 255 290
300 37 60 8 / 747 / 1011 240 285 320
350 37 60 8 / 797 / 1173 260 310 350
400 37 60 8 / 842 / 1333 280 335 380
500 37 60 8 / 926 / 1653 320 380 430
600 61 70 9 / 1024 / 1985 355 420 475
750 61 70 9 / 1126 / 2462 400 475 535
1000 61 70 9 / 1275 / 3254 455 545 615