Overhead Duplex Aluminum Service Drop & Ud ASTM Standard ABC Cable
Product Description
Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy neutral messsenger.
ASTM B-230, B-231, B-232 and B-399 & ICEA S-76-474.
Specifications
Code Word | Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | ||||||
Size (AWG or kcmil) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
AAC NEURAL-MESSENGER | ||||||||||
Pekingese | 6 | 1 | 45 | 6 | 7 | 563 | 61 | 61 | 85 | 70 |
Collie | 6 | 7 | 45 | 6 | 7 | 563 | 64 | 64 | 85 | 70 |
DachShund | 4 | 1 | 45 | 4 | 7 | 881 | 92 | 92 | 115 | 90 |
Spaniel | 4 | 7 | 45 | 4 | 7 | 881 | 96 | 96 | 115 | 90 |
Doberman | 2 | 7 | 45 | 2 | 7 | 1350 | 147 | 147 | 150 | 120 |
Bull | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 234 | 234 | 205 | 160 |
* Code Words For XLP Insulated Products Are Formed By Adding "/XLP" to the Conventional Code Words Above (e.g.-Chihuahua/XLP).+ Conductor Temperature of 90°C For XLP, 75°C For Poly; Ambient Temperature of 40°C; Emissivity 0.9; 2 ft./sec. Wind In Sun. |
Code Word | Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | ||||||
Size (AWG or kcmil) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
ACSR NEUTRAL-MESSENGER | ||||||||||
Setter | 6 | 1 | 45 | 6 | 6/1 | 1190 | 72 | 72 | 85 | 70 |
Shepherd | 6 | 7 | 45 | 6 | 6/1 | 1190 | 75 | 75 | 85 | 70 |
Eskimo | 4 | 1 | 45 | 4 | 6/1 | 1860 | 110 | 110 | 115 | 90 |
Terrier | 4 | 7 | 45 | 4 | 6/1 | 1860 | 115 | 115 | 150 | 120 |
Chow | 2 | 7 | 45 | 2 | 6/1 | 2850 | 176 | 176 | 150 | 120 |
Bull | 1/0 | 9 | 60 | 1/0 | 6/1 | 4380 | 280 | 280 | 205 | 160 |
* Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP).+ Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. |
Code Word | Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | |||||||
Size (AWG or kcmil) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Insul. Thick. (mils) | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
6201 ALLOY NEUTRAL-MESSENGER | |||||||||||
Chihuahua | 6 | 1 | 45 | 6 | 30.58 | 7 | 1110 | 65 | 65 | 85 | 70 |
Vizsla | 6 | 7 | 45 | 6 | 30.58 | 7 | 1110 | 68 | 68 | 85 | 70 |
Harrier | 4 | 1 | 45 | 4 | 48.69 | 7 | 1760 | 99 | 99 | 115 | 90 |
Whippet | 4 | 7 | 45 | 4 | 48.69 | 7 | 1760 | 103 | 103 | 115 | 90 |
Schnauzer | 2 | 7 | 45 | 2 | 77.47 | 7 | 2800 | 157 | 157 | 150 | 120 |
Heeler | 1/0 | 9 | 60 | 1/0 | 123.3 | 7 | 4460 | 250 | 250 | 205 | 160 |
* Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP).+ Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.++ Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201. |
(1)Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent
resistivity per ASTM B-399 for 6201.
(2)Conductor temperature of 90 Centgrade for XLPE, 75 Centgrade for PE; ambient temperatures of
40 Centgrade; emissivity 0.9; 2ft./sec/wind in sun.
Delivery and Service
OEM is accepted, delivery on time with good quality is assured, whenever you have enquiry or questions, please feel free to contact us anytime. Here is our website for your reference:jytopcable
- Next: Overhead Power Transmission Lines Conductors ABC Triplex Bundled Cables
- Previous: Aluminium Wire 3X95mm2 Aerial Bundle Cable ABC Cable
Contact us
Similar Or Related
-
Duplex Triplex Quadruplex Service Drop Cable Aluminum ABC Cable 2X16mm2
-
16mm Aluminium XLPE Cable Duplex Aluminium ABC Cable Aerial Bunched Cable
-
Duplex Cable Shepherd AWG #6/7 AAC for Philippines Duplex Cables
-
Overhead 0.6/1kv 11kv 33kv Aluminum Conductor XLPE Insulated Aerial Bundled Cable ABC Cable
-
Overhead Duplex Aluminum Service Drop & Ud ASTM Standard ABC Cable