Overahed Power Line ASTM Standard AAC Conductor
Product Description
ASTM B231: Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
ASTM B230: Standard Specification for Aluminum 1350-H19 Wire for Electrical Purposes
Application
This AAC conductor is used in high voltage overhead power transmission lines. Compared with ACSR of the same diameter, it has a smaller breaking load and is used in lines where short span and low resistance are required.
Product Details
1) Conductor: stranded 1350 aluminum
2) Sectional area: 10~1250 mm2
3) No. of strands: 7, 19, 37, 61, 91, 127
4) Aluminum wire performance
Diameter | Min tensile strength (MPa) | Min. elongation (%) | ||
mm | Average | Individual | Average | Individual |
0.227~1.25 | 170 | 160 | … | … |
1.26~1.50 | 200 | 185 | 1.4 | 1.2 |
1.51~1.75 | 195 | 185 | 1.5 | 1.3 |
1.76~2.00 | 195 | 185 | 1.6 | 1.4 |
2.01~2.25 | 190 | 180 | 1.6 | 1.5 |
2.26~2.50 | 185 | 175 | 1.6 | 1.5 |
2.51~2.75 | 180 | 170 | 1.6 | 1.5 |
2.76~3.00 | 175 | 165 | 1.7 | 1.6 |
3.01~3.50 | 170 | 160 | 1.8 | 1.7 |
3.51~3.75 | 170 | 160 | 1.9 | 1.8 |
3.76~4.50 | 165 | 160 | 2.0 | 1.9 |
4.51~5.25 | 165 | 160 | 2.1 | 2.0 |
5.26~6.50 | 160 | 155 | 2.3 | 2.2 |
5) AAC conductor specification
Code | Area (AWG/MCM) |
Stranding (No./mm) |
Overall Dia. (mm) |
Approx. Weight (kg/km) |
Min. Breaking Load (kN) |
Max. DC Resist. @ 20ºC (Ω/km) |
Peachbell | 6 | 7/1.55 | 4.67 | 37 | 2.49 | 2.1692 |
Rose | 4 | 7/1.96 | 5.89 | 58 | 3.96 | 1.3624 |
Iris | 2 | 7/2.47 | 7.42 | 93 | 5.97 | 0.8577 |
Pansy | 1 | 7/2.78 | 8.33 | 117 | 7.32 | 0.6801 |
Poppy | 1/0 | 7/3.12 | 9.36 | 147 | 8.73 | 0.539 |
Aster | 2/0 | 7/3.50 | 10.51 | 186 | 11.0 | 0.4276 |
Phlox | 3/0 | 7/3.93 | 11.80 | 234 | 13.47 | 0.3390 |
Oxlip | 4/0 | 7/4.42 | 13.26 | 296 | 16.98 | 0.2688 |
Valerian | 250 | 19/2.91 | 14.57 | 349 | 20.62 | 0.2275 |
Sneezewort | 250 | 7/4.80 | 14.40 | 349 | 20.07 | 0.2275 |
Laurel | 266.8 | 19/3.01 | 15.05 | 373 | 22.00 | 0.2133 |
Daisy | 266.8 | 7/4.96 | 14.90 | 373 | 21.41 | 0.2133 |
Peony | 300 | 19/3.19 | 15.97 | 419 | 24.03 | 0.1896 |
Tulip | 336.4 | 19/3.38 | 16.91 | 470 | 26.95 | 0.1691 |
Daffodil | 350 | 19/3.45 | 17.24 | 489 | 28.04 | 0.1625 |
Canna | 397.5 | 19/3.67 | 18.36 | 555 | 31.84 | 0.1431 |
Goldentuft | 450 | 19/3.91 | 19.55 | 629 | 34.99 | 0.1264 |
Syringa | 477 | 37/2.88 | 20.19 | 666 | 38.49 | 0.1193 |
Cosmos | 477 | 19/4.02 | 20.12 | 666 | 37.08 | 0.1193 |
Hyacinth | 500 | 37/2.95 | 20.65 | 698 | 40.35 | 0.1138 |
Zinnia | 500 | 19/4.12 | 20.60 | 698 | 38.88 | 0.1138 |
Dahlia | 556.5 | 19/4.35 | 21.73 | 777 | 43.27 | 0.1022 |
Mistiletoe | 556.5 | 37/3.11 | 21.79 | 777 | 43.62 | 0.1022 |
Meadowsweet | 600 | 37/3.23 | 22.63 | 838 | 47.03 | 0.0948 |
Orchid | 636 | 37/3.33 | 23.31 | 888 | 49.85 | 0.0894 |
Heuchera | 650 | 37/3.37 | 23.56 | 908 | 50.95 | 0.0875 |
Flag | 700 | 61/2.72 | 24.48 | 978 | 51.46 | 0.0813 |
Verbena | 700 | 37/3.49 | 24.45 | 978 | 54.87 | 0.0813 |
Nasturtium | 715.5 | 61/2.75 | 24.76 | 1000 | 58.74 | 0.0795 |
Violet | 715.5 | 37/3.53 | 24.74 | 1000 | 56.09 | 0.0795 |
Cattail | 750 | 61/2.82 | 25.35 | 1048 | 59.85 | 0.0795 |
Petunia | 750 | 37/3.62 | 25.32 | 1048 | 5875 | 0.0795 |
Lilac | 795 | 61/2.90 | 26.11 | 1111 | 63.45 | 0.0715 |
Arbutus | 795 | 37/3.72 | 26.06 | 1111 | 6232 | 0.0715 |
Snapdragon | 900 | 61/3.09 | 27.78 | 1257 | 69.78 | 0.0632 |
Cockscomb | 900 | 37/3.96 | 27.73 | 1257 | 68.48 | 0.0632 |
Goldenrod | 954 | 61/3.18 | 28.60 | 1333 | 78.96 | 0.0596 |
Magnolia | 954 | 37/4.08 | 28.55 | 1333 | 72.58 | 0.0596 |
Camellia | 1000 | 61/3.25 | 29.36 | 1397 | 77.53 | 0.0569 |
Hawkweed | 1000 | 37/4.18 | 29.23 | 1397 | 76.08 | 0.0569 |
Larkspur | 1033.5 | 61/3.31 | 29.76 | 1444 | 80.12 | 0.0550 |
Bluebell | 1033.5 | 37/4.24 | 29.72 | 1444 | 78.63 | 0.0550 |
Marigold | 1113 | 61/3.43 | 30.89 | 1555 | 86.28 | 0.0511 |
Hawthorn | 1192.5 | 61/3.55 | 31.05 | 1666 | 92.45 | 0.0477 |
Narcissus | 1272 | 61/3.67 | 33.02 | 1777 | 98.61 | 0.0477 |
Columbine | 1351.5 | 61/3.78 | 34.01 | 1888 | 104.78 | 0.0421 |
Carnation | 1431 | 61/3.89 | 35.03 | 1999 | 107.68 | 0.0398 |
Gladiolus | 1510.5 | 61/4.00 | 35.09 | 2110 | 113.65 | 0.0376 |
Coreopsis | 1590 | 61/4.10 | 36.51 | 2221 | 119.64 | 0.0358 |
Jessamine | 1750 | 61/4.30 | 38.72 | 2445 | 131.68 | 0.0325 |
Cowslip | 2000 | 91/3.76 | 41.40 | 2791 | 153.00 | 0.0285 |
Lupine | 2500 | 91/4.21 | 46.30 | 3524 | 187.00 | 0.0230 |
Trillium | 3000 | 127/3.90 | 50.75 | 4232 | 225.00 | 0.0192 |
Bluebonnet | 3500 | 127/4.21 | 54.80 | 4985 | 262.00 | 0.0166 |
Packaging details
Polyethylene film packaging 1) Usually used for cables with an overall diameter 10mm and below 2) 100 meters per roll or as per customer’s requirements 3) Packaging dimension: 50cm * 50cm * 20cm or below 4) Weight: 30 kg/roll or below |
Steel-wood drum packaging 1) Used for cables with a overall diameter of 10mm and above 2) Drum size: 180cm * 180cm *110cm (different sizes are available according to packaging length) 3) Standard length: as per customer’s requirements. |
Factory
Customer service
1) Select the right cable as per customer’s requirements
2) Design suitable packaging to guarantee safe and the most economic delivery
3) Provide installation and use guidance
4) Product quality guarantee under the normal use
- Next: Single Core Flexible Electric Wire Low Voltage
- Previous: Low Voltage Copper/PVC/PVC Electrical Cable Flexible
Contact us
Similar Or Related
-
Aster Cable 366mm2 37 Strands AAAC Bare Conductor for 90kV HV Substation
-
AAAC Bare Conductor 100mm2 7/4.26mm for Uganda 33kV Distribution Line
-
AAAC Bare Conductor 50mm2 7/3.02mm for Uganda 11kV Distribution Line
-
Aerial Bundled Conductor 70mm2 Hard drawn Aluminum ABC Cable for 400V Distribution Line
-
50mm2;AAAC PVC Covered Hazel Conductor BS 3242 for 11kV Distribution Line