Nyy-O 0.6/1kv PVC Power Cable to DIN/VDE Standard
Product Description
1. Operating Characteristics
Rated voltage: 0.6/1(1.2)kV
Max. Permissible continuous operating temperature of conductor: 70° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed:
Nominal cross section of conductor ≤ 300mm2: 160° C;
Nominal cross section of conductor >300mm2: 140° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 20 times of the diameter of cable
For multi-core cable: Not less than 15 times of the diameter of cable
2. Application
Nyy-O 0.6/1kv PVC Power Cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, in tunnel, in cable trench or in conduit, unable to bear external mechanical force.
3. Manufacturing Standards
IEC 60502-1 & Chinese national standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF &AS/NZ also.
NOTE:
If you want to know more details aboutNyy-O 0.6/1kv PVC Power Cable, please visit our website(homepage) because we have no ways to show so much information on this platform. Thank you.
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Cable size | Conductor type | Nominal thickness of PVC insulation(mm) | Nominal thickness of PVC sheath(mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 20 0 C (Ω/km) | |||
Phase core |
Earth core |
Phase core |
Earth core |
Phase core |
Earth core |
|||
3×2.5+1.5mm 2 | RE | RE | 0.8 | 0.8 | 1.8 | 11.7 | 7.41 | 12.1 |
3×4+2.5mm 2 | RE | RE | 1.0 | 0.8 | 1.8 | 13.5 | 4.61 | 7.41 |
3×6+4mm 2 | RE | RE | 1.0 | 1.0 | 1.8 | 15.0 | 3.08 | 4.61 |
3×10+6mm 2 | RM | RE | 1.0 | 1.0 | 1.8 | 17.6 | 1.83 | 3.08 |
3×16+10mm 2 | RM | RM | 1.0 | 1.0 | 1.8 | 20.3 | 1.15 | 1.83 |
3×25+16mm 2 | SM | RM | 1.2 | 1.0 | 1.8 | 21.4 | 0.727 | 1.15 |
3×35+16mm 2 | SM | RM | 1.2 | 1.0 | 1.8 | 23.1 | 0.524 | 1.15 |
3×50+25mm 2 | SM | SM | 1.4 | 1.2 | 1.9 | 26.3 | 0.387 | 0.727 |
3×70+35mm 2 | SM | SM | 1.4 | 1.2 | 2.0 | 30.0 | 0.268 | 0.524 |
3×95+50mm 2 | SM | SM | 1.6 | 1.4 | 2.2 | 34.3 | 0.193 | 0.387 |
3×120+70mm 2 | SM | SM | 1.6 | 1.4 | 2.3 | 37.6 | 0.153 | 0.268 |
3×150+70mm 2 | SM | SM | 1.8 | 1.4 | 2.4 | 40.8 | 0.124 | 0.268 |
3×185+95mm 2 | SM | SM | 2.0 | 1.6 | 2.6 | 45.7 | 0.0991 | 0.193 |
3×240+120mm 2 | SM | SM | 2.2 | 1.6 | 2.8 | 51.3 | 0.0754 | 0.153 |
3×300+150mm 2 | SM | SM | 2.4 | 1.8 | 2.9 | 56.6 | 0.0601 | 0.124 |
0.6/1kv XLPE/PVC POWER CABLE(unarmored) YJV,YJLV | |||||||||||||||||||||
sectional Area of Conductor (mm²) |
Thickness Insulation (mm) |
Non-metallic sheath unarmored cable | |||||||||||||||||||
Thickness of sheath | approx overall diameter | approx cable weight(kg/km) | |||||||||||||||||||
mm | mm | Cu | Al | ||||||||||||||||||
1c | 2c | 3c | 4c | 5c | 1c | 2c | 3c | 4c | 5c | 1c | 2c | 3c | 4c | 5c | 1c | 2c | 3c | 4c | 5c | ||
1.5 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 5.6 | 10 | 10.4 | 11.1 | 11.9 | 45 | 122 | 139 | 167 | 195 | 35 | 103 | 111 | 506 | 148 |
2.5 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 6 | 10.8 | 11.2 | 12.1 | 13 | 57 | 148 | 175 | 215 | 253 | 42 | 117 | 129 | 641 | 175 |
4 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 6.5 | 11.7 | 12.3 | 13.2 | 14.3 | 75 | 185 | 228 | 285 | 337 | 50 | 135 | 153 | 833 | 212 |
6 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 7 | 12.7 | 13.4 | 14.4 | 15.6 | 97 | 239 | 295 | 373 | 445 | 60 | 165 | 183 | 1086 | 258 |
10 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 8.1 | 15 | 15.8 | 17.2 | 18.7 | 143 | 346 | 445 | 568 | 681 | 80 | 220 | 256 | 1629 | 366 |
16 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 9.2 | 17.2 | 18.2 | 19.8 | 21.7 | 206 | 494 | 660 | 835 | 1008 | 106 | 292 | 358 | 2377 | 505 |
25 | 0.9 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 10.6 | 20 | 21.2 | 23.2 | 25.5 | 303 | 711 | 951 | 1217 | 1483 | 146 | 396 | 479 | 3457 | 696 |
35 | 0.9 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 11.8 | 22.4 | 23.8 | 26.1 | 28.7 | 403 | 919 | 1267 | 1598 | 1959 | 185 | 478 | 606 | 4528 | 858 |
50 | 1 | 1.4 | 1.8 | 1.8 | 1.9 | 2 | 13.2 | 25.2 | 26.8 | 29.7 | 32.9 | 554 | 1188 | 1675 | 2209 | 2733 | 241 | 558 | 731 | 6190 | 1160 |
70 | 1.1 | 1.4 | 1.9 | 1.9 | 2 | 2.1 | 15 | 22.2 | 25.7 | 30 | 36.2 | 755 | 1564 | 2260 | 2987 | 3735 | 317 | 683 | 939 | 8348 | 1533 |
95 | 1.1 | 1.5 | 2 | 2 | 2.1 | 2.3 | 16.9 | 25.2 | 29.1 | 34.2 | 40.3 | 1004 | 2069 | 3003 | 3977 | 4975 | 409 | 874 | 1210 | 11091 | 1987 |
120 | 1.2 | 1.5 | 2.1 | 2.1 | 2.3 | 2.4 | 18.5 | 28.2 | 32.4 | 37.2 | 44.7 | 1250 | 2592 | 3763 | 4983 | 6228 | 498 | 1082 | 1498 | 13880 | 2453 |
150 | 1.4 | 1.6 | 2.2 | 2.3 | 2.4 | 2.6 | 20.6 | 31 | 36.2 | 41.2 | 50.3 | 1558 | 3214 | 4700 | 6202 | 7777 | 619 | 1327 | 1869 | 17280 | 3059 |
185 | 1.6 | 1.6 | 2.3 | 2.4 | 2.6 | 2.8 | 22.7 | 36.8 | 40.4 | 46.2 | 58.6 | 1908 | 3978 | 5779 | 7655 | 9623 | 750 | 1650 | 2287 | 21355 | 3803 |
240 | 1.7 | 1.7 | 2.5 | 2.6 | 2.8 | 3 | 25.3 | 41.6 | 47.4 | 53.3 | 63.1 | 2450 | 5104 | 7456 | 9859 | 12326 | 947 | 2084 | 2926 | 27399 | 4776 |
300 | 1.8 | 1.8 | 2.7 | 2.8 | 3 | 3.2 | 27.9 | 46.4 | 50.1 | 59.4 | 68.2 | 3053 | 6328 | 9234 | 12260 | 15291 | 1163 | 2541 | 3554 | 33997 | 5824 |
400 | 2 | 1.9 | 3.1 | 3.3 | 3.6 | 31.6 | 57.2 | 68.4 | 83.1 | 4021 | 12224 | 16240 | 20305 | 1514 | 4651 | 36685 | 7683 | ||||
500 | 2.2 | 2 | 3.3 | 3.3 | 35 | 74.2 | 82.2 | 5002 | 15136 | 20176 | 1869 | 5849 | 7554 | ||||||||
630 | 2.4 | 2.2 | 39.3 | 6290 | 2342 | ||||||||||||||||
800 | 2.6 | 2.3 | 44.8 | 7957 | 2943 | ||||||||||||||||
1000 | 2.8 | 2.4 | 49.9 | 9897 | 3629 |
0.6/1kv XLPE/PVC POWER CABLE(unarmored) YJV,YJLV | |||||||||||||||
sectional Area of Conductor (mm²) | Thickness of insulation (mm) | Non-metallic sheath unarmored cable | |||||||||||||
thickness of sheath | approx overall diameter | cable weight | |||||||||||||
mm | mm | Cu | Al | ||||||||||||
phase line | zero line | phase line | zero line | 3+1c | 3+2c | 4+1c | 3+1c | 3+2c | 4+1c | 3+1c | 3+2c | 4+1c | 3+1c | 3+2c | 4+1c |
2.5 | 1.5 | 0.7 | 0.7 | 1.8 | 1.8 | 1.8 | 11.9 | 12.6 | 12.8 | 206 | 229 | 253 | |||
4 | 2.5 | 0.7 | 0.7 | 1.8 | 1.8 | 1.8 | 12.9 | 13.7 | 14 | 268 | 302 | 323 | 178 | 196 | 197 |
6 | 4 | 0.7 | 0.7 | 1.8 | 1.8 | 1.8 | 14.2 | 15.1 | 15.4 | 352 | 402 | 428 | 215 | 240 | 237 |
10 | 6 | 0.7 | 0.7 | 1.8 | 1.8 | 1.8 | 16.5 | 17.5 | 18.1 | 517 | 584 | 645 | 290 | 321 | 328 |
16 | 10 | 0.7 | 0.7 | 1.8 | 1.8 | 1.8 | 19.2 | 20.5 | 21.1 | 761 | 865 | 955 | 396 | 437 | 444 |
25 | 16 | 0.9 | 0.7 | 1.8 | 1.8 | 1.8 | 22.4 | 23.9 | 24.7 | 1110 | 1278 | 1406 | 538 | 605 | 606 |
35 | 16 | 0.9 | 0.7 | 1.8 | 1.8 | 1.8 | 24.6 | 25.9 | 27.3 | 1402 | 1558 | 1805 | 647 | 709 | 731 |
50 | 25 | 1 | 0.9 | 1.8 | 1.9 | 1.9 | 28 | 29.9 | 31.3 | 1943 | 2243 | 2531 | 842 | 984 | 975 |
70 | 35 | 1.1 | 0.9 | 1.9 | 2 | 2.1 | 29.5 | 33.2 | 34.4 | 2645 | 3038 | 3412 | 1101 | 1273 | 1234 |
95 | 50 | 1.1 | 1 | 2.1 | 2.2 | 2.2 | 33.2 | 37.8 | 38.7 | 3554 | 4105 | 4551 | 1443 | 1679 | 1579 |
120 | 70 | 1.2 | 1.1 | 2.2 | 2.3 | 2.4 | 36.3 | 41.6 | 43.6 | 4504 | 5265 | 5791 | 1793 | 2112 | 1993 |
150 | 70 | 1.4 | 1.1 | 2.3 | 2.4 | 2.5 | 39.7 | 45.9 | 47.9 | 5425 | 6200 | 7018 | 2147 | 2480 | 2380 |
185 | 95 | 1.6 | 1.1 | 2.5 | 2.6 | 2.7 | 45.4 | 51.4 | 53.3 | 6781 | 7792 | 8720 | 2683 | 3095 | 2946 |
240 | 120 | 1.7 | 1.2 | 2.7 | 2.8 | 2.9 | 53 | 58.6 | 60.1 | 8708 | 9960 | 11172 | 3412 | 3907 | 3701 |
300 | 150 | 1.8 | 1.4 | 2.9 | 3 | 3.1 | 58.3 | 65.4 | 62.9 | 10818 | 12394 | 13827 | 4192 | 4823 | 4480 |
400 | 185 | 2 | 1.6 | 3.1 | 3.3 | 3.4 | 67.5 | 74. 2 | 67.8 | 14163 | 16132 | 18093 | 5423 | 6225 | 5725 |
1.8/3(3.6)kv XLPE/PVC single core (unarmored)YJV,YJLV | |||||||||
conductor | thickness of insulation (mm) | copper tape screened (mm) | thickness of sheath(mm) | approx overall diameter (mm) | copper core cable weight (kg/km) | aluminum core cable weight (kg/km) | insulation resistance 20ºC(Min.) (MΩ/km) | ||
sectional area(mm²) | structure | overall diameter (mm) | |||||||
10 | C.C. | 3.9 | 2 | 0.12 | 1.4 | 12.9 | 252 | 189 | 500 |
16 | C.C. | 5 | 2 | 0.12 | 1.4 | 14 | 326 | 226 | 500 |
25 | C.C. | 6 | 2 | 0.12 | 1.4 | 15 | 426 | 269 | 500 |
35 | C.C. | 7.2 | 2 | 0.12 | 1.4 | 16.2 | 538 | 319 | 500 |
50 | C.C. | 8.4 | 2 | 0.12 | 1.5 | 17.6 | 702 | 390 | 500 |
70 | C.C. | 10 | 2 | 0.12 | 1.5 | 19.2 | 914 | 475 | 500 |
95 | C.C. | 11.7 | 2 | 0.12 | 1.6 | 21.1 | 1181 | 586 | 500 |
120 | C.C. | 13.1 | 2 | 0.12 | 1.6 | 22.5 | 1433 | 681 | 500 |
150 | C.C. | 14.6 | 2 | 0.12 | 1.7 | 24.2 | 1743 | 803 | 500 |
185 | C.C. | 16.3 | 2 | 0.12 | 1.7 | 25.9 | 2091 | 933 | 500 |
240 | C.C. | 18.5 | 2 | 0.12 | 1.8 | 28.3 | 2643 | 1140 | 500 |
300 | C.C. | 20.7 | 2 | 0.12 | 1.9 | 30.7 | 3244 | 1364 | 500 |
400 | C.C. | 23.8 | 2 | 0.12 | 2 | 34 | 4225 | 1718 | 500 |
500 | C.C. | 26.6 | 2.2 | 0.12 | 2.1 | 37.4 | 5227 | 2093 | 500 |
630 | C.C. | 30.1 | 2.4 | 0.12 | 2.2 | 41.5 | 6523 | 2574 | 500 |
800 | C.C. | 35 | 2.6 | 0.12 | 2.3 | 47 | 8221 | 3207 | 500 |
1000 | S.S | 39.5 | 2.8 | 0.12 | 2.5 | 52.3 | 10371 | 4104 | 500 |
Note:
C.C.: circular compacted
S.S.: shaped stranded conductor
1.8/3(3.6)KV XLPE/PVC single core (unarmored)YJV,YJLV | |||||||||
conductor | thickness insulation (mm) | copper tape screened (mm) | thickness of sheath(mm) | approx overall diameter (mm) | copper core cable weight (kg/km) | aluminum core cable weight (kg/km) | insulation resistance 20ºC(Min.) (MΩ/km) | ||
sectional area(mm²) | structure | overall diameter (mm) | |||||||
10 | C.C. | 3.9 | 2 | 0.1 | 1.8 | 22.8 | 700 | 511 | 500 |
16 | C.C. | 5 | 2 | 0.1 | 1.8 | 25.2 | 964 | 662 | 500 |
25 | C.C. | 6 | 2 | 0.1 | 1.8 | 27.3 | 1255 | 783 | 500 |
35 | C.C. | 7.2 | 2 | 0.1 | 1.9 | 30.1 | 1623 | 962 | 500 |
50 | C.C. | 8.4 | 2 | 0.1 | 2 | 32.9 | 2016 | 1072 | 500 |
70 | C.C. | 10 | 2 | 0.1 | 2.1 | 36.6 | 2660 | 1336 | 500 |
95 | C.C. | 11.7 | 2 | 0.1 | 2.2 | 40.4 | 3444 | 1647 | 500 |
120 | C.C. | 13.1 | 2 | 0.1 | 2.3 | 43.6 | 4216 | 1946 | 500 |
150 | C.C. | 14.6 | 2 | 0.1 | 2.4 | 47.1 | 5141 | 2304 | 500 |
185 | C.C. | 16.3 | 2 | 0.1 | 2.5 | 50.9 | 6207 | 2707 | 500 |
240 | C.C. | 18.5 | 2 | 0.1 | 2.7 | 56.1 | 7874 | 3335 | 500 |
300 | C.C. | 20.7 | 2 | 0.1 | 2.8 | 61 | 9666 | 3986 | 500 |
400 | C.C. | 23.8 | 2 | 0.1 | 3.1 | 68.3 | 12659 | 5086 | 500 |
500 | C.C. | 26.6 | 2.2 | 0.1 | 3.3 | 75.6 | 15695 | 6228 | 500 |
Note:
- Next: 15kv Copper Cable 3X95mm with Steel Wire Armored
- Previous: 450/750V PVC Insulated Copper Wire with CE, ISO 9001 Certificates
Contact us
Similar Or Related
-
0.6/1kv-2 Core Copper Conductor PVC Insulated PVC Sheathed Power Cable Nyy Power Cable
-
0.6/1kv-4 Core Copper Conductor PVC Insulated PVC Sheathed Power Cable
-
0.6/1kv-3 Core Copper Conductor PVC Insulated PVC Sheathed Power Cable
-
0.6/1kv-3+2 Core Copper Conductor PVC Insulated PVC Sheathed Power Cable
-
0.6/1kv-4+1 Core Copper Conductor PVC Insulated PVC Sheathed Power Cable