Nyy, Nyy-J, Nyy-O Copper PVC Insulation Flame Retardant PVC Sheath Power Cable
Product Description
Fixed installation, direct burial; PVC cable with different application areas
NYY-J, NYY-O, VDE, PVC-Starkstromkabel acc. HD 603 / VDE 0276-603, direct burial and building installation, fixed installation with various applications
- CPR: Article number choice under lappkabel/cpr
- Standard cable for direct burial with different application areas
- 0,6/1,0 kV alternative to the PVC installation cable NYM
APPLICATIONS:
Low voltage power distribution cable for fixed installations. In swtich stations, power plants and industrial plants. Used in dry indoor places, underground in cable ducts.Mechanical damage unexpected.
The NYY cable range includes NYY-J and NYY-O cables. These are widely used European power and control cables designed for fixed wiring installation with a voltage rating of 600/1000V. They can be safely deployed in most applications where mechanical stresses are not anticipated – indoors, outdoors, direct burial underground, in concrete, or submerged in water. When NYY cables are required to comply with the UK wiring regulations BS7671 for burial in the ground, they require installation in a conduit or duct to provide protection against mechanical damage. They are not suitable for installation in concrete which is shaken, vibrated or compressed.
NYY-J & NYY-O CABLE CONSTRUCTION
Conductor | Up to 25mm2: solid copper (Class 1) 25mm2 and above: stranded copper (Class 2) |
Insulation | Polyvinyl Chloride (PVC) Type DIV4 |
Filler | PVC |
Sheath | Flame retardant PVC Type DMV5 (FR-PVC) |
The construction of the NYY-O differs from the NYY-J in that it doesn’t have a green/yellow earth wire.
These black NYY cables have a UV-stabilised outersheath making them suitable for direct exposure to sunlight. They have an operating temperature range of -15oC to +70oC when fixed and -5oC to +50oC when flexed.
Parameter of NYY cable
Rated Cross Section & number of cores | Insulation Thickness (mm) | Overall Diameter (mm) | Approx. Weight (kg/km) |
CU factor (per km) |
Conductor DC resistance at 200C (ohm/km) |
Current Capacity (A) |
|
Ground | Air | ||||||
1×4 | 1,0 | 8,8 | 130 | 38 | 4,61 | – | 37 |
1×6 | 1,0 | 9,3 | 155 | 58 | 3,08 | – | 48 |
1×10 | 1,0 | 10,1 | 204 | 96 | 1,83 | – | 66 |
1×16 | 1,0 | 11 | 268 | 154 | 1,15 | 107 | 89 |
1×25 | 1,2 | 12,5 | 370 | 215 | 0,727 | 137 | 118 |
1×35 | 1,2 | 13,6 | 475 | 300 | 0,524 | 165 | 145 |
1×50 | 1,4 | 14,6 | 595 | 404 | 0,387 | 195 | 176 |
1×70 | 1,4 | 16,3 | 810 | 591 | 0,268 | 239 | 224 |
1×95 | 1,6 | 18,2 | 1075 | 818 | 0,193 | 287 | 271 |
1×120 | 1,6 | 19,6 | 1320 | 1038 | 0,153 | 326 | 314 |
1×150 | 1,8 | 21,4 | 1600 | 1278 | 0,124 | 366 | 361 |
1×185 | 2,0 | 23,5 | 1980 | 1597 | 0,0991 | 414 | 412 |
1×240 | 2,2 | 26,9 | 2600 | 2113 | 0,0754 | 481 | 484 |
2×1,5 | 0,8 | 11,6 | 211 | 29 | 12,1 | 32 | 20 |
2x,5 | 0,8 | 12,7 | 262 | 48 | 7,41 | 42 | 27 |
2×4 | 1 | 14,1 | 335 | 77 | 4,61 | 54 | 37 |
2,6 | 1 | 15,0 | 401 | 115 | 3,08 | 68 | 48 |
3×1,5 | 0,8 | 12,0 | 233 | 43 | 12,1 | 26 | 18,5 |
3×2,5 | 0,8 | 13,3 | 297 | 72 | 7,41 | 34 | 25 |
3×4 | 1 | 14,7 | 383 | 115 | 4,61 | 44 | 34 |
3×6 | 1 | 15,8 | 469 | 173 | 3,08 | 56 | 43 |
3×10 | 1 | 17,5 | 634 | 288 | 1,83 | 75 | 60 |
3×16/10 | 1,0 / 1,0 | 21,0 | 955 | 557 | 1,15 / 1,83 | 98 / 75 | 80 / 60 |
3×25/16 | 1,2 / 1,0 | 23,5 | 1370 | 874 | 0,727 / 1,15 | 128 / 98 | 106 / 80 |
3×35/16 | 1,2 / 1,0 | 25,9 | 1740 | 1162 | 0,524 / 1,15 | 157 / 98 | 131 / 80 |
3×50/25 | 1,4 / 1,2 | 29,6 | 2330 | 1680 | 0,387 / 0,727 | 185 / 128 | 159 / 106 |
3×70/35 | 1,4 / 1,2 | 33,6 | 3200 | 2352 | 0,268 / 0,524 | 228 / 157 | 202 / 131 |
3×95/50 | 1,6 / 1,4 | 38,7 | 4330 | 3216 | 0,193 / 0,387 | 275 / 185 | 244 / 159 |
3×120/70 | 1,6 / 1,4 | 42,9 | 5470 | 4128 | 0,153 / 0,268 | 313 / 228 | 282 / 202 |
3×150/70 | 1,8 / 1,4 | 46,1 | 6450 | 4992 | 0,124 / 0,268 | 353 / 228 | 324 / 202 |
3×185/95 | 2,0 / 1,6 | 52,0 | 8180 | 6240 | 0,0991 / 0,193 | 399 / 275 | 371 / 244 |
3×240/120 | 2,2 / 1,6 | 59,0 | 10620 | 8064 | 0,0754 / 0,153 | 464 / 313 | 436 / 282 |
4×1,5 | 0,8 | 12,8 | 266 | 58 | 12,1 | 26 | 18,5 |
4×2,5 | 0,8 | 14,2 | 343 | 96 | 7,41 | 34 | 25 |
4×4 | 1 | 15,8 | 448 | 154 | 4,61 | 44 | 34 |
4×6 | 1 | 17,0 | 554 | 230 | 3,08 | 56 | 43 |
4×10 | 1 | 18,9 | 760 | 384 | 1,83 | 75 | 60 |
4×16 | 1 | 21,1 | 1030 | 614 | 1,15 | 98 | 80 |
4×25 | 1,2 | 25,0 | 1515 | 960 | 0,727 | 128 | 106 |
4×35 | 1,2 | 27,7 | 1970 | 1344 | 0,524 | 157 | 131 |
4×50 | 1,4 | 31,5 | 2610 | 1920 | 0,387 | 185 | 159 |
5×1,5 | 0,8 | 13,6 | 307 | 72 | 12,1 | 25 | 18,5 |
7×1,5 | 0,8 | 14,5 | 360 | 101 | 12,1 | 15 | 12 |
10×1,5 | 0,8 | 17,5 | 490 | 144 | 12,1 | 12,5 | 10,2 |
12×1,5 | 0,8 | 17,9 | 535 | 173 | 12,1 | 11,9 | 9,7 |
14×1,5 | 0,8 | 18,7 | 590 | 202 | 12,1 | 11,3 | 9,3 |
NYY-J & NYY-O CABLE SELECTION
As a leading NYY supplier and supplier of fixed installation power supply cables manufactured to various European and national standards, our technical engineers have vast experience of advising on cable selection for NYY-J and NYY-O as well as their aluminium conductor counterparts NAYY-J and NAYY-O. For technical support, please see the NYY specification datasheet or call us to discuss your specific project requirements.
- Next: N2X Ry-O/N2X Ry-J Cu/PVC Power Cable to DIN/VDE0276
- Previous: Nyy Cable Low Voltage PVC Insulation Copper Cable