Nyy Cable Copper PVC Insulated PVC Sheathed Electrical Power Cable

Nyy Cable Copper PVC Insulated PVC Sheathed Electrical Power Cable

Nyy Cable Copper PVC Insulated PVC Sheathed Electrical Power Cable

nyy

Insulated

Stranded

Heating, Underground

Aluminum

PVC

PVC

Round Wire

Refractory

ISO9001, CE, CCC, RoHS

Jytop

Ce, ISO 9001

IEC60502 ,VDE0276

Black,Red,Yellow,Blue,Brown,Green

0.6/1kv

JYTOP

Drum or Reel

4x150mm2

Zhengzhou, China

8544492100

Product Description

NYY Cable IEC60502 VDE0276 Copper PVC insulated PVC sheathed Electrical Power Cable

Operating Characteristics of nyy cable

Conductor: Cu, class 1 or 2 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295
class 1: solid, round(RE) or sector (SE)
class 2: multi wire stranded, round (RM) or sector (SM), multi wire exceeding 50 mm² are compacted
Insulation: PVC compound DIV-4 acc. to HRN HD 603.1
Filler: extruded elastomer or plastomer compound or wrapped thermoplastic tapes
Sheath: PVC compound DMV-5 acc. to HRN HD 603.1
sheath colour: black
Temperature range:
during installation: -5 °C up to +50 °C
fixed installed: -30 °C up to +70 °C
at short circuit of max. 5 s: up to 160 °C
Nominal voltage: Uο/U = 0,6/1 kV
Test voltage: 4 kV
Max. operating voltage in three-phase systems: 1,2 kV
Maximal tensile strength: 50 N/mm²
Behaviour in fire: IEC 60332-1
Minimal inner bending radius:
single core: 15D
multi core: 12D

Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, in tunnel, in cable trench or in conduit, unable to bear external mechanical force.

NYY power cable to IEC60502

Conductors: Plain annealed copper conductors

Insulation: PVC (Polyvinyl-Chloride)

Core identification: 2 Core (blue & brown), 3 Core (blue, brown & Green/Yellow), 4 Core (black, brown, grey & green/yellow), 5 Core (black, blue, brown, grey & green/yellow), 7 Core and above (white numbered cores & 1 green/yellow)

Sheath/Jacket: PVC (Polyvinyl-Chloride)

Colour: Black

Voltage: 600/1000v

Operating temperature: Maximum 70°C, minimum bending 0°C

Types: O – Excluding protective earth conductor. J – Including protective earth conductor

Standard: VDE0271 Power cables. Specifications for power cables 0.6/1kv and above for special applications

DIN VDE 0276-603 Power cables Part 603 distribution cables of rated voltage 0.6/1kv

DIN VDE 0276-627 Power cables Part 627 multicore & multipair cables for installation above and below ground

IEC60502 Power cables with extruded insulation and their accessories for rated voltages from 1kV to 30kV

Applications: Energy cables for use in open air, underground, indoors and in cable ducts

Minimum Bending Radius: 15 x Overall Diameter for Solid Conductors. 12 x Overall Diameter for Stranded Conductors

Paramter of NYY cable

Cable size Conductor type Nominal thickness of PVC insulation(mm) Nominal thickness of PVC sheath(mm) Approx. cable overall diameter (mm) Max. D.C resistance @ 20 0 C (Ω/km)
Phase
core
Earth
core
Phase
core
Earth
core
Phase
core
Earth
core
4×2.5+1.5mm 2 RE RE 0.8 0.8 1.8 12.7 7.41 12.1
4×4+2.5mm 2 RE RE 1.0 0.8 1.8 14.8 4.61 7.41
4×6+4mm 2 RE RE 1.0 1.0 1.8 16.4 3.08 4.61
4×10+6mm 2 RM RE 1.0 1.0 1.8 19.4 1.83 3.08
4×16+10mm 2 RM RM 1.0 1.0 1.8 22.4 1.15 1.83
4×25+16mm 2 SM RM 1.2 1.0 1.8 23.8 0.727 1.15
4×35+16mm 2 SM RM 1.2 1.0 1.8 25.7 0.524 1.15
4×50+25mm 2 SM SM 1.4 1.2 2.0 29.6 0.387 0.727
4×70+35mm 2 SM SM 1.4 1.2 2.1 33.4 0.268 0.524
4×95+50mm 2 SM SM 1.6 1.4 2.3 38.6 0.193 0.387
4×120+70mm 2 SM SM 1.6 1.4 2.4 42.2 0.153 0.268
4×150+70mm 2 SM SM 1.8 1.4 2.6 46.2 0.124 0.268
4×185+95mm 2 SM SM 2.0 1.6 2.8 51.7 0.0991 0.193
4×240+120mm 2 SM SM 2.2 1.6 3.0 58.0 0.0754 0.153
4×300+150mm 2 SM SM 2.4 1.8 3.2 64.2 0.0601 0.124

Note: RE= round conductor RM = stranded conductor SM=sectional conductor