Mv Distribution Line Aerial Bundled Conductor ABC Overhead Cables

MV Aerial Bundled Conductor ABC Cables Standards:
IEC 60502 / AS/NZS 3599-1 standards
MV Aerial Bundled Conductor ABC Cables Constructions:

Conductor: Round, Aluminium Conductor
Conductor Screen: Extruded semi-conductive layer.
Insulation: XLPE
insulation Screen: Extruded semi-conductive layer.
metallic Screen(optional): Copper wire screen or copper tape screen.
Separator: Semi-conductive swellable tape.
outer Sheath: HDPE.
Messager wire: Galvanized steel wires.
Assembly: Three XLPE insulated screened cores are bundled around the galvanized steel
wires in a right hand lay.
MV Aerial Bundled Conductor ABC Cables Application:
Aerial bundled cables are mainly used for secondary overhead lines on poles or as feeders
to residential premises.
The Function of messenger wire:
A) It acts as load bearing wire. B) It acts as earth or neutral conductor
MV Aerial Bundled Conductor ABC Cables Specifications:
AS/NZS 3599 Part 1 6.35/11 kV AL/XLPE /CWS/HDPE Screened Cables

Application
The cables are designed for aerial power lines with rated voltage Uo(Um) 10(12) kV ~35(40.5)kV.

Product properties and range
* Rated voltage is 10kV and 35KV
* No. of cores : 1 , Nominal cross-section(mm2): 16~300
* Max.Continuous permissive working temperature of conductor:
XLPE insulation should be not more than 90ºC.
*Max. Temperature at short circuit (the longest continuous time is not more than 5S) XLPE insulation is 250ºC.
* Installation temperature of cable should be not less than -20ºC.
* Permissive bending radius of cable should be not less than 20(D+d) mm.
D -the actual overall diameter of cable ,mm;
d-the actual overall diameter of conductor ,mm.
* Insulation resistance of common insulation construction of aerial cable should be not less than 1500MΩ km, and insulation
resistance of thin XLPE insulated construction of light aerial cable should be not less than 1000mΩ km.

parameter of abc cable

Number of CoresxNominal Cross Section Phase Conductor Messenger Suspension Unit Continuous current rating at 30ºCambient temp
Stranding Nominal Sectional Area Maximum Conductor Resistance Stranding Nominal Sectional Area Breaking Load
No.×mm2 mm mm mm mm No.×mm mm2 KN
3×35 6.9 3.4 0.8 1.2 7/4.75 52.4 1370
3×50 8.1 3.4 0.8 1.2 7/4.75 54.6 1530
3×70 9.7 3.4 0.8 1.2 7/4.75 57.8 1790
3×95 11.4 3.4 0.8 1.2 7/4.75 61.3 2100
3×120 12.8 3.4 0.8 1.2 19/3.50 67.3 2540
3×150 14.2 3.4 0.8 1.2 19/3.50 70.1 2840
3×185 15.7 3.4 0.8 1.2 19/3.50 73.1 3190

AS/NZS 3599 Part 1 12.7/22 kV AL/XLPE /HDPE Non-screened Cables

Number of CoresxNominal Cross Section Diameter of Conductor Thickness of Insulation Thickness of Insulation Screen Thickness of Sheath Messenger Suspension Unit Stranding Nominal Sectional Area Breaking Load
No.×mm2 mm mm mm mm No.×mm mm2 KN
3×35 6.9 5.5 0.8 1.2 7/4.75 61 1780
3×50 8.1 5.5 0.8 1.2 7/4.75 63.3 1970
3×70 9.7 5.5 0.8 1.2 7/4.75 66.5 2260
3×95 11.4 5.5 0.8 1.2 7/4.75 69.9 2600
3×120 12.8 5.5 0.8 1.2 19/3.50 75.9 3070
3×150 14.2 5.5 0.8 1.2 19/3.50 78.7 3390
3×185 15.7 5.5 0.8 1.2 19/3.50 81.7 3760

AS/NZS 3599 Part 1 12.7/22 kV AL/XLPE /CWS/HDPE Screened Cables

Number of CoresxNominal Cross Section Diameter of Conductor Thickness of Insulation Thickness of Insulation Screen Copper Wire Screen Stranding Thickness of Sheath Galvanized Steel Wire Stranding Nominal Sectional Area Breaking Load
No.×mm2 mm mm mm No.×mm mm No.×mm mm2 KN
No.×mm2 mm mm mm No.×mm mm No.×mm mm2 KN
Light Duty Screen
3×35 6.9 5.5 0.8 25/0.85 1.8 7/2.00 62.7 2280
3×35 6.9 5.5 0.8 25/0.85 1.8 19/2.00 66.7 2580
3×50 8.1 5.5 0.8 25/0.85 1.8 19/2.00 69 2780
3×70 9.7 5.5 0.8 25/0.85 1.9 19/2.00 72.6 3110
3×95 11.4 5.5 0.8 25/0.85 1.9 19/2.00 76 3460
3×120 12.8 5.5 0.8 25/0.85 2 19/2.00 79.2 3810
3×150 14.2 5.5 1 25/0.85 2 19/2.00 82.8 4230
3×185 15.7 5.5 1 25/0.85 2.1 19/2.00 86.2 4650
Heavy Duty Screen
3×35 6.9 5.5 0.8 40/0.85 1.8 7/2.00 62.7 2510
3×35 6.9 5.5 0.8 40/0.85 1.8 19/2.00 66.7 2810
3×50 8.1 5.5 0.8 23/1.35 1.8 19/2.00 71 3300
3×70 9.7 5.5 0.8 32/1.35 1.9 19/2.00 74.6 3970
3×95 11.4 5.5 0.8 39/1.35 1.9 19/2.00 78 4600
3×120 12.8 5.5 0.8 39/1.35 2 19/2.00 81.2 4950
3×150 14.2 5.5 1 39/1.35 2 19/2.00 84.8 5360
3×185 15.7 5.5 1 39/1.35 2.1 19/2.00 88.2 5790

Other cross-sections can be offered upon request.

IEC 60502 6.35/11 kV ABC for Overhead Distribution Lines

Number of CoresxNominal Cross Section Phase Conductor Messenger Suspension Unit Continuous current rating at 30 ambient temp
Stranding Nominal Sectional Area Maximum Conductor Resistance Stranding Nominal Sectional Area Breaking Load
No.×mm2 No.×mm mm2 Ω/Km No.×mm mm2 KN A
3X50 + 1X25 19/1.78 50 0.641 7/3.0 50 60 116
3X70 + 1X50 19/.14 70 0.443 7/3.15 50 62 210
3X95+ 1X50 19/2.52 95 0.32 7/3.0 50 60 173
3X185+1X120 37/2.52 185 0.164 7/4.67 120 150 259
3X150 +1X50 37/2.25 150 0.206 7/3.15 50 62 365
3X240 +1X50 61/2.25 240 0.125 7/3.15 50 62 500

IEC 60502 19/33 kV ABC for Overhead Distribution Lines

Number of CoresxNominal Cross Section Phase Conductor Messenger Suspension Unit Continuous current rating at 30 ambient temp
Stranding Nominal Sectional Area Maximum Conductor Resistance Stranding Nominal Sectional Area Breaking Load
No.×mm2 No.×mm mm2 Ω/Km No.×mm mm2 KN A
3X50 + 1X50 19/1.78 50 0.641 7/3.0 50 60 165
3X150+ 1X50 37/2.25 150 0.206 7/3.0 50 60 315
3X185+1X70 37/2.52 185 0.164 7/3.57 70 91 355
3X70 +1X50 19/2.14 7 0.443 7/3.15 50 62 250
3X150 +1X50 37/2.25 150 0.206 7/3.15 50 62 370