Middle Voltage Copper / Aluminum Conductor XLPE Insulated Power Cable

CABLE CONSTRUCTION: 8.7/15KV AL/XLPE/CWS/AWA//PVC or PE

1. Description
Construction: Compacted stranded circular aluminum conductor, extruded semi-conducting compound as conductor shield, cross-linked polyethylene (XLPE) insulation, semi-conducting compound as insulation shield, copper tape or combination of copper wire and tape as metallic screen, three cores assembled together with non-hygroscopic polypropylene filler, wrapped with binder tape, PVC inner covering as armoring bedding, galvanized steel wire armored, PVC or PE outer sheath.

2. Operating Characteristics
Rated voltage U0/U(Um): 8.7/15(17.5)kV
U0 is the rated power frequency voltage between conductor and earth or metallic screen for which the cable is designed;
U is the rated power frequency voltage between conductors for which the cable is designed;
Um is the maximum value of the "highest system voltage" for which the equipment may be used.
Max. Permissible continuous operating temperature of conductor: 90 ° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed: 250 ° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 15 times of the diameter of cable
For three core cable: Not less than 12 times of the diameter of cable
When the armored single core cable used for Alternative Current(AC) system, the armoring material should be non-magnetic.

3. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, outdoors, in tunnel, in cable trench, or direct in ground, able to bear external mechanical force and certain pulling force.

4. Manufacturing Standards
IEC 60502-2 and Chinese National Standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF &AS/NZ also.

Operating Temperature: up to 70°C (PVC insulation); up to 90°C (XLPE or EPR insulation)
Temperature Range: -5°C ( PVC sheath ); -20°C ( PE sheath )
Short Circuit Temperature( 5 seconds maximum duration ): 140-160°C (PVC insulation);
250°C (XLPE)
Bending Radius: 12 x OD
Current Rating Conditions:
Ground Temperature:
20°C
Ambient Temperature (air): 30°C
Depth of Soil: 0.8m
Thermal Resistance of Soil: 1.5K•m/W
Insulation Thickness:

Nom. Cross Section Area Insulation Thickness at Nominal Voltage
1.8/3KV 3.6/6KV 6/10KV 8.7/15KV 12/20KV 18/30KV 21/35KV 26/35KV
(Um=3.6KV) (Um=7.2KV) (Um=12KV) (Um=17.5KV) (Um=24KV) (Um=36KV) (Um=42KV) (Um=42KV)
mm2 mm mm mm mm mm mm mm mm
XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE
10 2 2.5
16 2 2.5 3.4
25 2 2.5 3.4 4.5
35 2 2.5 3.4 4.5 5.5
50 – 185 2 2.5 3.4 4.5 5.5 8 9.3 10.5
240 2 2.6 3.4 4.5 5.5 8 9.3 10.5
300 2 2.8 3.4 4.5 5.5 8 9.3 10.5
400 2 3 3.4 4.5 5.5 8 9.3 10.5
500 – 1600 2.2-2.8 3.2 3.4 4.5 5.5 8 9.3 10.5