Middle Voltage 11kv Copper Conductor XLPE Insulated Electric Cable
Product Description
6.35/11kv Middle voltage copper conductor XLPE insulated power cable
1. Description
Construction: Compacted stranded circular copper conductor, extruded semi-conducting compound as conductor shield, cross-linked polyethylene (XLPE) insulation, semi-conducting compound as insulation shield, copper tape or combination of copper wire and tape as metallic screen, three cores assembled together with non-hygroscopic polypropylene filler, wrapped with binder tape, PVC or PE outer sheath.
2. Operating Characteristics
Rated voltage U0/U(Um): 6.35/11(12)kV
U0 is the rated power frequency voltage between conductor and earth or metallic screen for which the cable is designed;
U is the rated power frequency voltage between conductors for which the cable is designed;
Um is the maximum value of the "highest system voltage" for which the equipment may be used.
Max. Permissible continuous operating temperature of conductor: 90 ° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed: 250 ° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 20 times of the diameter of cable
For three core cable: Not less than 15 times of the diameter of cable
3. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, outdoors, in tunnel or in cable trench, unable to bear external mechanical force.
Single core cable in magnetic duct is not permissible.
4. Manufacturing Standards
IEC 60502-2 and Chinese National Standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF
&AS/NZ also.
NOTE:
If you want to know more details about this kind of products, please visit our website(homepage) because we have no ways to show so much information on this platform. Thank you.
Size | Nominal thickness of XLPE insulation(mm) | Approx. thickness of copper tape screen (mm) | Nominal thickness of PVC or PE(mm) | Approx. overall diameter of finished cable(mm) | Max. conductor D.C resistance @ 20 0 C (Ω/km) |
1x25mm 2 | 3.4 | 0.12 | 1.8 | 20.3 | 0.727 |
1x35mm 2 | 3.4 | 0.12 | 1.8 | 21.3 | 0.524 |
1x50mm 2 | 3.4 | 0.12 | 1.8 | 22.4 | 0.387 |
1x70mm 2 | 3.4 | 0.12 | 1.8 | 24.1 | 0.268 |
1x95mm 2 | 3.4 | 0.12 | 1.8 | 25.7 | 0.193 |
1x120mm 2 | 3.4 | 0.12 | 1.8 | 27.1 | 0.153 |
1x150mm 2 | 3.4 | 0.12 | 1.8 | 28.7 | 0.124 |
1x185mm 2 | 3.4 | 0.12 | 1.9 | 30.5 | 0.0991 |
1x240mm 2 | 3.4 | 0.12 | 2.0 | 33.1 | 0.0754 |
1x300mm 2 | 3.4 | 0.12 | 2.0 | 35.1 | 0.0601 |
1x400mm 2 | 3.4 | 0.12 | 2.1 | 38.5 | 0.0470 |
1x500mm 2 | 3.4 | 0.12 | 2.2 | 42.2 | 0.0366 |
1x630mm 2 | 3.4 | 0.12 | 2.3 | 46.3 | 0.0283 |
1x800mm 2 | 3.4 | 0.12 | 2.5 | 50.4 | 0.0221 |
1. Is it a cable factory?
Definitely, we are a wire and cable Manufacturer with 23 years history, our factory located in Zhengzhou, Henan Province,China.
2. Any certificates:
Yes, the CE and ISO 9001:2008 are available.
For bare conductors there are Type Test Report available
3. What Standards you are using?
We can producing the wire and cables according to the popular Standards, such asIEC, ASTM, BS, DIN,SANS,CSA or as the clients requirements
4. OEM services?
Yes, We supply OEM services.
5. Delivery time
It depends on the cable type and quantity you need, you can contact us for the details
6. Payment terms:
Usually we would prefer L/C, T/T, or negotiate with us.
7. Packing
Usually it is packing in coil for PVC builing wire, for the powe cable and bare conductors used to packing by Drums, or as clients requirements.
- Next: 11kv Aluminum Conductor XLPE Insulated PVC Cable 1X150sq. mm
- Previous: Middle Voltage Mv 8.7/15kv Copper Conductor XLPE Insulated Power Cable