Low Voltage Power Cable with Copper or Aluminium
Product Description
1.XLPE/PVC Insulation LV (Low Voltage) Power Cable cable belongs to cables rated voltage up to 1KV. They are used for laying indoor, tunnel, underground, canal, water and seabed, etc .
Standard available such as ASTM , BS , DIN ,NFC , AS/NZS , CSA , IS , etc.
2.Brief Construction:
2.1 Number of Core : 1Core , 2Core,3Core , 4Core , 5Core , 3+1Core(3.5Core) , 3+2 Core , 4+1Core , etc.
2.2 Conductor material: Copper or Aluminum (Stranded Round /Stranded compacted round/stranded compacted sector)
2.3 Insulation Material: XLPE/PVC/PE/LSHF
2.4 Inner sheath (applicable if there is armour layer): PVC/PE
2.5 Armour layer (if required) :Galvanized steel wire / Steel Tape
2.6 Outer sheath : PVC/PE
3.The max. conductor long time permissible operating temperature is 70 degree for PVC Insulation and 90degreefor XLPE Insulation ; In short circuit, max. Temperature is 160 degree for PVC Sheath and 250degreefor PVC Sheath.
4.Packing : In roll / In wooden drum / In Iron-wooden drum / In steel drum.
5.Certificate: ISO , CE , SGS, SONCAP , BV , COC,ETC.
6.For other detailed information, pls contact us directly .
Nominal Cross Section mm 2 | 1.5 | 2.5 | 4 | 6 | 10 | 16 | 25 |
Cu core Ohm/km | 12.1 | 7.41 | 4.61 | 3.08 | 1.83 | 1.15 | 0.727 |
Al core Ohm/km | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | 1.91 | 1.2 |
Nominal Cross Section mm 2 | 35 | 50 | 70 | 95 | 120 | 150 | 185 |
Cu core Ohm/km | 0.524 | 0.387 | 0.268 | 0.193 | 0.153 | 0.124 | 0.0991 |
Al core Ohm/km | 0.868 | 0.641 | 0.443 | 0.32 | 0.253 | 0.206 | 0.164 |
Nominal Cross Section mm 2 | 240 | 300 | 400 | 500 | 630 | 800 | 1000 |
Cu core Ohm/km | 0.0754 | 0.06 | 0.047 | 0.0366 | 0.0283 | 0.0221 | 0.0176 |
Al core Ohm/km | 0.125 | 0.1 | 0.0778 | 0.0605 | 0.0469 | 0.0367 | 0.0291 |
- Next: 600V 600V Cu / PVDF / Hmwpe Cathodic Protection Cable