High Voltage Aluminum Conductor Alloy Reinforced Acar
Product Description
ASTM B524: Standard Specification for Concentric-lay-stranded Aluminum Conductors, Aluminum Alloy Reinforced (ACAR, 1350/6201)
ASTM B230: Standard Specification for Aluminum 1350-H19 Wire for Electrical Purposes
ASTM B398: Standard Specification for Aluminum-Alloy 6201-T81 and 6201-T83 Wire for Electrical Purposes
Application
This aluminum conductor alloy reinforced ACAR is used in high voltage overhead power transmission lines. Compared with ACSR conductor of the same diameter, AAAC has smaller linear mass and lower resistivity.
Product Details
1) Conductor: stranded 1350 aluminum
2) Conductivity: 61.2% IACS
3) Mechanical performance of aluminum wire
Diameter | Min. Tensile Strength (MPa) | Min. Elongation in 250mm (%) | ||
mm | Average for a lot | Individual test value | Average for a lot | Individual test value |
0.227 to 1.25 | 170.0 | 160.0 | … | … |
1.26 to 1.50 | 200.0 | 185.0 | 1.4 | 1.2 |
1.51 to 1.75 | 195.0 | 185.0 | 1.5 | 1.3 |
1.76 to 2.00 | 195.0 | 185.0 | 1.6 | 1.4 |
2.01 to 2.25 | 190.0 | 180.0 | 1.6 | 1.5 |
2.26 to 2.50 | 185.0 | 175.0 | 1.6 | 1.5 |
2.51 to 2.75 | 180.0 | 170.0 | 1.6 | 1.5 |
2.76 to 3.00 | 175.0 | 165.0 | 1.7 | 1.6 |
3.01 to 3.50 | 170.0 | 160.0 | 1.8 | 1.7 |
3.51 to 3.75 | 170.0 | 160.0 | 1.9 | 1.8 |
3.76 to 4.50 | 165.0 | 160.0 | 2.0 | 1.9 |
4.51 to 5.25 | 165.0 | 160.0 | 2.1 | 2.0 |
5.26 to 6.50 | 160.0 | 155.0 | 2.3 | 2.2 |
4) Reinforced core: stranded 6201 aluminum alloy
5) Alloy conductivity: 52.5% IACS
6) Alloy mechanical performance
Diameter (mm) | Min Tensile Strength (MPa) | Elongation in 250mm | ||
Over | Through | Average for a lot | Individual test | % |
3.25 | 4.75 | 315 | 305 | 3.0 |
1.50 | 3.25 | 330 | 315 | 3.0 |
7) Sectional area: 10~1250 mm2
8) No. of strands: 7, 19, 37, 61, 91, 127
9) Cable specification (ASTM standard)
Packaging details
Polyethylene film packaging 1) Usually used for cables with an overall diameter 10mm and below 2) 100 meters per roll or as per customer’s requirements 3) Packaging dimension: 50cm * 50cm * 20cm or below 4) Weight: 30 kg/roll or below |
Steel-wood drum packaging 1) Used for cables with a overall diameter of 10mm and above 2) Drum size: 180cm * 180cm *110cm (different sizes are available according to packaging length) 3) Standard length: as per customer’s requirements. |
Factory
Customer service
1) Select the right cable as per customer’s requirements
2) Design suitable packaging to guarantee safe and the most economic delivery
3) Provide installation and use guidance
4) Product quality guarantee under the normal use
- Next: 0.6/1kv Overhead Xable Aluminum Conductor XLPE Insulation with Three Core Cable
- Previous: Copper Clad Aluminum Copper Clad Steel Copper Clad Aluminum Aloy
Contact us
Similar Or Related