Cu/XLPE/Cts/PVC/Swa/PVC, Power Cable, 6.35/11 Kv, 3/C (BS 6622)

Cu/XLPE/Cts/PVC/Swa/PVC, Power Cable, 6.35/11 Kv, 3/C (BS 6622)

Cu/XLPE/Cts/PVC/Swa/PVC, Power Cable, 6.35/11 Kv, 3/C (BS 6622)

Cu/XLPE/CTS/PVC/SWA/PVC

Construction, Underground, Industrial, Power Station

Low and Medium Voltage Cable

DC Cable

XLPE

PVC

Round Wire

Bare Copper Wire

ISO, CCC, CE

Cu/XLPE/Cts/PVC/Swa/PVC

Boan

BS 6622

6.35/11 Kv

3

2

70-630 mm2

Copper Tape

Steel Wire Armour

DingAn

Fumigated Steel-Wooden Drum/Steel Drum

SGS, CE

Jiangsu Yixing, China

8544601200

Product Description

Cu/XLPE/CTS/PVC/AWA/PVC, Power Cable, 6.35/11 KV, 3/C (BS 6622)

Application
Power cables for power networks, underground and in cable ducting.

Standards
BS6622

Technical Data

Conductor
Class 2 stranded plain copper conductor to BS EN 60228:2005 (previously BS6360)

Conductor Screen
Semi-conducting material

Insulation
XLPE (Cross-Linked Polyethylene) Type GP8 to BS7655
Insulation Screen
Semi-conducting material

Metallic Screen
Individual and overall copper tape screen to BS6622

Filler
PETP (Polyethylene Terephthalate) fibres

Separator
Binding tape

Bedding
PVC (Polyvinyl Chloride) Type TM1 to BS7655

Armouring
Single Core: SWA (Galvanized Steel Wire Armoured)
Sheath
PVC (Polyvinyl Chloride) Type TM1 to BS7655

Sheath Colour
Red or Black

Voltage Rating
6500/11000V

Temperature Rating
0°C to +90°C

Minimum Bending Radius
Single Cores: 12 x overall diameter
No. of Cores x Nominal Cross Sectional Area Nominal Diameter Nominal Weight
Under Armour Over Armour Overall
# x mm² mm kg/Km
3 x 25 39.0 44.0 48.8 4300
3 x 35 41.6 46.6 51.6 4700
3 x 50 44.4 49.4 54.6 5300
3 x 70 48.1 53.1 58.5 6300
3 x 95 52.0 57.0 62.6 7300
3 x 120 55.6 60.6 66.6 8400
3 x 150 58.6 63.6 69.8 9600
3 x 185 62.7 67.7 74.1 11000
3 x 240 68.1 74.4 81.2 14000
3 x 300 73.5 79.8 87.0 16600

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.