Copper XLPE Insulated PVC Sheath Aluminum Steel Wire Armoured Cable

Copper XLPE Insulated PVC Sheath Aluminum Steel Wire Armoured Cable

Copper XLPE Insulated PVC Sheath Aluminum Steel Wire Armoured Cable

YJV22

Insulated

Stranded

Underground

Copper

PVC

PVC

Round Wire

Flame Retardant

ISO9001, CE, CCC, RoHS

Jytop

Ce, ISO 9001

ASTM, AS/NZS, BS, CSA, DIN, IEC…

0.6/1kv 6/10kv 12/20kv 18/30kv 25/35kv

Black,Red,Yellow,Blue,Brown,Green

20 Days

JYTOP

Drum or Reel

based on DIN VDE 0276-603

Zhengzhou, China

8544492100

Product Description

Copper XLPE Insulated PVC Sheath Aluminum Steel Wire Armoured Underground Power Cable

1. Operating Characteristics
Rated voltage: 0.6/1(1.2)kV
Max. Permissible continuous operating temperature of conductor: 70° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed:
Nominal cross section of conductor ≤ 300mm2: 160° C;
Nominal cross section of conductor >300mm2: 140° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 20 times of the diameter of cable
For multi-core cable: Not less than 15 times of the diameter of cable

2. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, in tunnel, in cable trench or in conduit, unable to bear external mechanical force.

3. Manufacturing Standards
IEC 60502-1 & Chinese national standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF &AS/NZ also.

pvc insulated steel wire armoured construction power cable size

1) Standard :IEC60502,GB/T 12706

2).Voltage :0.6/1KV

3).Specification:

Type Designation Application
VV Copper conductor ,PVC insulated ,PVC sheathed power cable For laying indoors, in tunnel or cable trench,unable to bear extermal mechanical forces. Single core cable is not permissible to lay in magnetic duct
VLV Aluminium conductor ,PVC insulated ,PVC sheathed power cable
VY Copper conductor, PVC insulated, PE sheathed power cable
VLY Aluminium conductor ,PVC insulated ,PE sheathed power cable
VV22 Copper conductor ,PVC insulated ,steel tape armoured ,PVC sheathed power cable For laying indoors, in cable trench or direct in ground ,able to bear external mechanical forces, but unable to bear pulling force
VLV22 Aluminium conductor ,PVC insulated ,steel tape armoured ,PVC sheathed power cable
VV23 Copper conductor ,PVC insualted ,steel tape armoured ,PE sheathed power cable
VLV23 Alunminium conductor ,PVC insulated ,steel tape armoured ,PE sheathed power cable
VV32 Copper conductor, PVC insulated, steel wire armoured,PVC insulated power cable For laying indoors, in cable or direct in ground ,able to bear external mechanical forces, but unable to bear large pulling forces
VLV32 Aluminium conductor, PVC insulated ,steel tape armoured ,PVC sheathed power cable
VV33 Copper conductor, PVC insulated steel wire armoured , PE sheathed power cable
VLV33 Aluminium conductor , PVC insulated , streel wire armoured ,PE sheathed power cable
Note: The armoured single core cables is only used for D.C.system. As for A.C.system,non-magnetic armored material should be applied

4).nominal cross-sectional areas:1.5 mm2 , 2.5 mm2 ,4 mm2 , 6 mm2 , 10 mm2 , 16 mm2 ,25 mm2 , 35 mm2 , 50 mm2 ,70 mm2 , 95 mm2 ,120 mm2 ,150 mm2 ,185 mm2 ,240 mm2 ,300 mm2 400 mm2 500 mm2 630 mm2 800 mm2

5)production range: single core cable from 1.5 mm2 to 800 mm2,muli-core cable from 1.5 mm2 to 400 mm2

6).operating characteristics:
Rated power-frequency voltage u0/u:0.6/1 KV
Max permissible continuous operating temperature of conductor 70
Max short-circuit temperature of the conductor shall not exceed (Max 5 seconds duration): cross-section of conductor 300 mm2

The bending radius of single core cable should not be less than 20 times of the cable diameter ,the bending radius of multi-core cable should not be less than 15 times of the cable diameter