Copper Outdoor Electrical Building Wire 600V 2AWG Xhhw-2 Cable
Product Description
Application
Type XHHW-2 is intended for use as general purpose wiring in air conduit or other recognized reaceways for service, feeder and branch circuit wiring as specified in the National Electric Code at a max. Conductor temperature of 90 Degree C. In wet or dry locations.
Construction
Compressed stranded 8000 Series aluminum alloy conductor, black abrasion, heat and moisture resistant crosslinked polyethylene insulation.
Standards
UL Standards 44 and Federal specification JC-30B NEC ASTM B 800, B 801
Specifcation of XHHW-2 cable
Cond. AWG or MCM |
Stranding | Insulation thickness (mls) |
Outside diameter (in) |
Lbs/1000ft | Ampacity (amps) 90ºC |
8 | 7/w | 45 | .230 | 29 | 45 |
6 | 7/w | 45 | .260 | 40 | 60 |
4 | 7/w | 45 | .305 | 58 | 75 |
2 | 7/w | 45 | .360 | 86 | 100 |
1 | 19/w | 55 | .415 | 109 | 115 |
1/0 | 19/w | 55 | .450 | 132 | 135 |
2/0 | 19/w | 55 | .490 | 162 | 150 |
3/0 | 19/w | 55 | .540 | 199 | 175 |
4/0 | 19/w | 55 | .590 | 245 | 205 |
250 | 37/w | 65 | .655 | 294 | 230 |
300 | 37/w | 65 | .705 | 347 | 255 |
350 | 37/w | 65 | .750 | 398 | 280 |
400 | 37/w | 65 | .795 | 450 | 305 |
500 | 37/w | 65 | .870 | 552 | 350 |
600 | 61/w | 80 | .980 | 672 | 385 |
700 | 61/w | 80 | 1.040 | 774 | 420 |
750 | 61/w | 80 | 1.075 | 825 | 435 |
1000 | 61/w | 80 | 1.230 | 1077 | 500 |