Bare Conductor Acar
Product Description
Bare Conductor ACAR
ACAR
Aluminum Conductor. Aluminum Alloy Conductor Reinforced.
STANDARDS
ACAR bare conductor meets or exceeds the following ASTM standards:
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
B-398 Aluminum-Alloy 6201-T81 for Electrical Purposes.
B-524 Concentric-Lay-Stranded Aluminum Conductors, Aluminum Alloy Reinforced ACAR, 1350/6201.
CONSTRUCTION
Aluminum alloy 1350-H19 wires, concentrically stranded about an aluminum alloy 6201 core. Although the alloy strands generally comprise the core of the cable, in some constructions they are distributed in layers throughout the aluminum alloy 1350-H19 strands.
NOTE:
If you want to know more details about this kind of products, please visit our website(homepage) because we have no ways to show so much information on this platform. Thank you.
Size (kcmil) |
Stranding (EC/6201) |
Diameter(ins) | Weight per 1000 ft. (Lbs.) |
Rated strength (Lbs.) |
Resistance Ω/1000 ft. |
Allowable ampacity+ (Amps) |
|||
Individual wire | Complete cable |
DC at 20ºC |
AC at 75ºC |
||||||
6201 | 1350 | ||||||||
355.0 | 12/7 | 0.1367 | 0.1367 | 0.683 | 332.1 | 8500 | .0514 | .0624 | 519 |
465.9 | 12/7 | 0.1566 | 0.1566 | 0.783 | 435.8 | 11000 | .0392 | .0477 | 616 |
503.6 | 12/7 | 0.1628 | 0.1628 | 0.814 | 471.1 | 11900 | .0362 | .0441 | 646 |
653.1 | 12/7 | 0.1854 | 0.1854 | 0.927 | 611.0 | 15400 | .0279 | .0342 | 760 |
739.8 | 30/7 | 0.1414 | 0.1414 | 0.990 | 692.7 | 15300 | .0240 | .0296 | 831 |
739.8 | 18/19 | 0.1414 | 0.1414 | 0.990 | 691.6 | 18800 | .0252 | .0308 | 814 |
853.7 | 30/7 | 0.1519 | 0.1519 | 1.063 | 799.3 | 17500 | .0208 | .0257 | 907 |
853.7 | 18/19 | 0.1519 | 0.1519 | 1.063 | 798.0 | 21500 | .0218 | .0268 | 890 |
927.2 | 30/7 | 0.1583 | 0.1583 | 1.108 | 868.2 | 19000 | .0192 | .0238 | 955 |
927.2 | 18/19 | 0.1583 | 0.1583 | 1.108 | 866.7 | 23400 | .0201 | .0247 | 936 |
1024.5 | 30/7 | 0.1664 | 0.1664 | 1.165 | 959.3 | 20900 | .0173 | .0216 | 1015 |
1024.5 | 18/19 | 0.1664 | 0.1664 | 1.165 | 957.7 | 25800 | .0182 | .0225 | 995 |
1081.0 | 30/7 | 0.1709 | 0.1709 | 1.196 | 1012.1 | 22100 | .0164 | .0205 | 1048 |
1081.0 | 18/19 | 0.1709 | 0.1709 | 1.196 | 1010.5 | 27200 | .0172 | .0213 | 1028 |
1109.0 | 30/7 | 0.1731 | 0.1731 | 1.212 | 1038.4 | 22700 | .0160 | .0200 | 1065 |
1109.0 | 18/19 | 0.1731 | 0.1731 | 1.212 | 1036.6 | 27900 | .0168 | .0208 | 1044 |
1172.0 | 30/7 | 0.1780 | 0.1780 | 1.246 | 1097.3 | 24000 | .0152 | .0190 | 1101 |
1172.0 | 18/19 | 0.1780 | 0.1780 | 1.246 | 1095.5 | 29500 | .0159 | .0198 | 1080 |
1197.0 | 30/7 | 0.1799 | 0.1799 | 1.259 | 1120.8 | 24500 | .0148 | .0187 | 1115 |
1197.0 | 18/19 | 0.1799 | 0.1799 | 1.259 | 1118.9 | 30200 | .0156 | .0194 | 1094 |
1280.0 | 30/7 | 0.1860 | 0.1860 | 1.302 | 1198.5 | 26200 | .0139 | .0175 | 1160 |
1280.0 | 18/19 | 0.1860 | 0.1860 | 1.302 | 1196.5 | 32200 | .0146 | .0182 | 1139 |
1361.0 | 42/19 | 0.1494 | 0.1494 | 1.344 | 1273.6 | 30300 | .0133 | .0168 | 1196 |
1527.0 | 42/19 | 0.1582 | 0.1582 | 1.424 | 1428.8 | 33600 | .0118 | .0151 | 1314 |
1703.0 | 42/19 | 0.1671 | 0.1671 | 1.504 | 1593.5 | 37500 | .0106 | .0137 | 1363 |
1933.0 | 42/19 | 0.1780 | 0.1780 | 1.602 | 1808.8 | 42500 | .00936 | .0123 | 1465 |
2267.0 | 42/19 | 0.1928 | 0.1928 | 1.735 | 2142.0 | 49900 | .00806 | .0108 | 1594 |
2493.0 | 72/19 | 0.1655 | 0.1655 | 1.821 | 2356.9 | 50400 | .00722 | .0099 | 1687 |
2493.0 | 54/37 | 0.1655 | 0.1655 | 1.821 | 2354.5 | 57600 | .00743 | .0101 | 1670 |
+Ampacity based on 75ºC conductor temperature, 25ºC ambient temperature, with 2 ft./sec. wind in the sun. |