Aerial Bundle Cable ABC to Sans 1418 Size 3X70+54.6

Aerial Bundle Cable ABC to Sans 1418 Size 3X70+54.6

Aerial Bundle Cable ABC to Sans 1418 Size 3X70+54.6

abc to Sans

Phase Insulated with Bare Neutral

Solid or Stranded

Overhead

Aluminum or Aluminum Alloy or Aluminum & Steel

No

PE or XLPE

Round Wire

Overhead

ISO9001, CE, CCC

Jytop

Black,Red,Yellow,Blue,Brown,Green

16mm 25mm 35mm

0.6/1kv

2,3,4,5

Aluminum or Aluminum Alloy or ACSR

Henan

3X70+54.6

JYTOP

Packed in Reels

as per Sans 1418 Standards

Zhengzhou, China

8544492100

Product Description

Aerial Bundle Conductor-ABC(South Africa Standard Sizes)-SANS 1418-1

Table 01

Type of conductor or core Norminal cross-sectional area mm2 Nubmer of wires
Min.
Diameter of conductormm Resistanceat 20ºC Ω/km Max. Breaking force(N) Thickness of insulation (mm) Outer diameter of core(mm)
Min. Max. Min. Average Min. Min. Max.
Phase or auxiliary or non-strain-bearing netural(aluminium) +16 6 4.6 5.1 1.91 2070 1.2 0.98 7.0 7.8
25 6 5.8 6.3 1.2 3300 1.4 1.16 8.6 9.4
35 6 6.8 7.3 0.868 4500 1.6 1.34 10.0 10.9
50 6 7.9 8.4 0.641 6200 1.6 1.34 11.1 12.0
70 12 9.7 10.2 0.443 8900 1.8 1.52 13.3 14.2
95 15 11.0 12.0 0.320 12300 1.8 1.52 14.6 16.0
120 15 12.5 13.5 0.253 15600 1.8 1.52 16.3 17.5
150 15 13.9 15.0 0.206 19200 1.8 1.52 17.1 18.6
Service connection(aluminium) 16 6 4.6 5.2 1.91 2070 1.2 0.98 7.0 8.0
25 6 5.6 6.5 1.2 3300 1.4 1.16 8.6 9.6
Service connection(copper) 10 6 4.2 1.83 3600 1.2 0.98 6.2 7.0
16 6 5.3 1.15 5760 1.2 0.98 7.2 8.0
25 6 6.6 0.727 8750 1.4 1.16 8.6 9.6
Number and nominal diameter of wires
mm
Supporting
core(aluminium alloy)
54.6 7×3.15 9.2 9.6 0.630 16600 1.6 1.34 12.3 13.0
70 7×3.50 10.0 10.4 0.500 20100 1.6 1.34 12.9 13.6
+Auxiliary conductors or cores only

When a supporting core is specified in a tender invitation,the combinations listed in Table 02 below:

Table 02

1 2
Nominal cross sectional area of supporting conductor mm2 Nominal cross-sectional areas of phase conductors mm2
54.6 25,35,50,70,95
70 70,95,120
95 95,120,150

—————————————————————————————————————————–

Aerial Bundle Conductor-ABC(South Africa Custimized Size Specification)

Table 03

Type of conductor or core Norminal cross-sectional area mm2 Nubmer of wires Diameter of conductormm Resistanceat 20ºC Ω/km Max. Breaking force(N) Thickness of insulation (mm) Outer diameter of core(mm)
Min. Max. Min. Average Min. Min. Max.
Phase or auxiliary or non-strain-bearing netural(aluminium) 16 7/1.65 4.6 5.1 1.91 2070 1.2 0.98 7.0 7.8
25 7/2.15 5.8 6.3 1.2 3300 1.4 1.16 8.6 9.4
35 7/2.55 6.8 7.3 0.868 4500 1.6 1.34 10.0 10.9
50 7/2.99 7.9 8.4 0.641 6200 1.6 1.34 11.1 12.0
70 14/2.59 9.7 10.2 0.443 8900 1.8 1.52 13.3 14.2
95 19/2.59 11.0 12.0 0.320 12300 1.8 1.52 14.6 16.0
120 19/2.99 12.5 13.5 0.253 15600 1.8 1.52 16.3 17.5
150 30/2.59 13.9 15.0 0.206 19200 1.8 1.52 17.1 18.6
Service connection(aluminium) 16 7/1.65 4.6 5.2 1.91 2070 1.2 0.98 7.0 8.0
25 7/2.15 5.6 6.5 1.2 3300 1.4 1.16 8.6 9.6
Service connection(copper) 10 7/1.35 4.2 1.83 3600 1.2 0.98 6.2 7.0
16 7/1.69 5.3 1.15 5760 1.2 0.98 7.2 8.0
25 7/2.19 6.6 0.727 8750 1.4 1.16 8.6 9.6
Supporting core(aluminium alloy) 16 7/1.71 5.1 5.2 2.053 5070 1.4 1.16 7.9 8.0
25 7/2.15 6.4 6.5 1.314 8000 1.4 1.16 9.2 9.3
35 7/2.48 6.6 7.5 0.986 10300 1.6 1.34 10.7 10.8
50 7/2.89 7.7 8.4 0.720 14200 1.6 1.34 11.9 12.0
54.6 7/3.15 9.2 9.6 0.630 16600 1.6 1.34 12.3 13.0
70 7/3.50 10.0 10.4 0.500 20100 1.6 1.34 12.9 13.6

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.