600/1000V XLPE Insulated, PVC Sheathed, Double Steel Tape Armoured 3 Cores Power Cable

600/1000V XLPE Insulated, PVC Sheathed, Double Steel Tape Armoured 3 Cores Power Cable

600/1000V XLPE Insulated, PVC Sheathed, Double Steel Tape Armoured 3 Cores Power Cable

CU/XLPE/PVC/DSTA/PVC 600/1000V Class 2

Insulated

Stranded

Underground

Copper

PVC

XLPE

Round Wire

Flame Retardant

ISO9001, CCC

Hongda

Double Steel Tape Armour

Hongda

Steel & Wooden Drum

3 cores

China

8544601200

Product Description

APPLICATION
The cables are mainly used in power stations, mass transit underground passenger systems,
airports, petrochemical plants, hotels, hospitals, and high-rise buildings.

STANDARDS
Basic design adapted to IEC 60502-1

FIRE PERFORMANCE

Flame Retardance (Single Vertical
Wire Test)**

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE
0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation
(Vertically-mounted bundled wires
& cable test)**

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.

VOLTAGE RATING
600/1000V

CABLE CONSTRUCTION

Conductor: Plain annealed copper wire, normal stranded or compact stranded according to IEC(EN)
60228 class 2.
Insulation: Extruded cross-linked XLPE compound.
Filler, binder and inner covering: PP, PET, PVC
Armouring: Double steel tape
Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance,
anti rodent and anti termite properties can be offered as option. Compliance to fire performance
standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the
PVC compound and the overall cable design. LSPVC can also be provided upon request.

COLOUR CODE
Insulation Colour as per BS7671

With Earth Conductor

Without Earth Conductor

2Cores

Brown, Blue

3Cores

Yellow/Green, Brown, Blue

Brown, Gray, Black

4Cores

Yellow/Green, Brown, Gray, Black

Brown, Gray, Black, Blue

5Cores

Yellow/Green, Brown, Gray, Black, Blue

Brown, Gray, Black, Blue, Black

Above 5 Cores

Yellow/Green, Black Numbered

Black Numbered

Sheath Colour: Black (other colors upon request)

Physical AND THERMAL PROPERTIES
Temperature range during operation: Max.90°C for XLPE
250°C in short-circuit for 5secs max.
Minimum bending radius: 10x Overall Diameter

CONSTRUCTION PARAMETERS

Conductor FGD400 1RVMV-R

No. of Core X
Cross Section

Phases Neutral Nominal
Diameter
Overall
Conducrtor
Nominal
Insulation
Thickness

Nominal
Steel
Tape
Thickness

Nominal
Sheath
Thickness

Nominal
Overall
Diatemer

Approx.
No./ Weight

No./ Weight
Nominal
Diameter
of
Strands

No./
Nominal
Diameter
of
Strands

Pha.

Neu.

Pha.

Neu.

mm2

No/mm

No/mm

mm

mm

mm

mm

mm

mm

mm

Kg/km

3×10+1×6

7/1.35

7/1.04

3.75

2.90

0.7

0.7

0.2

1.8

20.1

740

3×16+1×10

7/1.70

7/1.35

4.75

3.75

0.7

0.7

0.2

1.8

22.5

1,004

3×25+2×16

7/2.14

7/1.70

5.85

4.75

0.9

0.7

0.2

1.8

25.8

1,421

3×35+1×16

7/2.52

7/1.70

6.90

4.75

0.9

0.7

0.2

1.8

27.7

1,745

3×35+1×25

7/2.52

7/2.14

6.90

5.85

0.9

0.9

0.2

1.8

28.6

1,864

3×50+1×25

19/1.78

7/2.14

8.15

5.85

1.0

0.9

0.2

1.8

31.3

2,358

3×50+1×35

19/1.78

7/2.52

8.15

6.90

1.0

0.9

0.2

1.9

32.0

2.72

3×70+1×35

19/2.14

7/2.52

9.75

6.90

I.1

0.9

0.2

2.0

35.9

3166

3×70+1×50

19/2.14

19/1.78

9.75

8.15

I.1

1.0

0.2

2.0

36.8

3.341

3×95+1×50

19/2.52

19/1.78

11.4

8.15

I.1

1.0

0.5

2.1

41.4

4,611

3×120+1×70

37/2.03

19/2.14

12.8

9.75

1.2

I.1

0.5

2.3

45.6

5682

3×150+1×95

37/2.25

19/2.52

14.3

11.4

1.4

I.1

0.5

2.4

50.8

7,072

3×150+1×120

37/2.25

37/2.03

14.3

12.8

1.4

1.2

0.5

2.5

51.8

7,357

3×185+1×95

37/2.52

19/2.52

15.9

11.4

1.6

I.1

0.5

2.6

54.7

8,348

3×185+1×120

37/2.52

37/2.03

15.9

12.8

1.6

1.2

0.5

2.6

55.8

8638

3×240+1×120

61/2.25

37/2.03

18.2

12.8

1.7

1.2

0.5

2.7

61.0

10,660

3×240+1×150

61/2.25

37/2.25

18.2

14.3

1.7

1.4

0.5

2.8

62.2

11024

3×300+1×150

61/2.52

37/2.25

20.4

14.3

1.8

1.4

0.5

2.9

66.8

12,809

3×300+1×185

61/2.52

37/2.52

20.4

15.9

1.8

1.6

0.5

3.0

68.1

13,256

Notes:
1) *All conductors in accordance with lEC 60228. Compact shape (Com.) or non-compact depending on order.
2) Beside above list we can also provide others size depend on customer’s requirement.

Electrical Properties

No. of Core X
Cross Section

Conductor Max.DC resistance of conductor @20°C
Phases Neutral Dia.Overall
Conducrtor

No./Nominal
Diameter of
Strands

No./Nominal
Diameter of
Strands

Pha.

Neu.

Pha.

Neu.

mm2

No/mm

No/mm

mm

mm

Ω/km

Ω/km

3×10+1×6

7/1.35

7/1.04

3.75

2.90

1.83

3.08

3×16+1×10

7/1.70

7/1.35

4.75

3.75

1.15

1.83

3×25+2×16

7/2.14

7/1.70

5.85

4.75

0.727

1.15

3×35+1×16

7/2.52

7/1.70

6.90

4.75

0.524

1.15

3×35+1×25

7/2.52

7/2.14

6.90

5.85

0.524

0.727

3×50+1×25

19/1.78

7/2.14

8.15

5.85

0.387

0.727

3×50+1×35

19/1.78

7/2.52

8.15

6.90

0.387

0.524

3×70+1×35

19/2.14

7/2.52

9.75

6.90

0268

0.524

3×70+1×50

19/2.14

19/1.78

9.75

8.15

0268

0.387

3×95+1×50

19/2.52

19/1.78

11.4

8.15

0.193

0.387

3×120+1×70

37/2.03

19/2.14

12.8

9.75

0.153

0.268

3×150+1×95

37/2.25

19/2.52

14.3

11.4

0.124

0.193

3×150+1×120

37/2.25

37/2.03

14.3

12.8

0.124

0.153

3×185+1×95

37/2.52

19/2.52

15.9

11.4

0.0991

0.193

3×185+1×120

37/2.52

37/2.03

15.9

12.8

0.0991

0.153

3×240+1×120

61/2.25

37/2.03

18.2

12.8

0.0754

0.153

3×240+1×150

61/2.25

37/2.25

18.2

14.3

0.0754

0.124

3×300+1×150

61/2.52

37/2.25

20.4

14.3

0.0601

0.124

3×300+1×185

61/2.52

37/2.52

20.4

15.9

0.0601

0.0991

Electrical PROPERTIES
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C

Current-Carrying Capacities (Amp)

Conductor
crosssectional
area
Reference
Method 1 (clipped
direct)
Reference Method 11 (on
a perforated horizontal
cable trayor Reference
Method 13 [free air] )
In single-way
ducts
Laid direct in ground
one
2-core
cable
single
phase
a.c. or
d.c.
one
3-core
or
4-core
cable
3-phase
a.c.
one 2-core
cable single
phase a.c.
or d.c.
one 3-core
or 4-core
cable
3-phase
a.c.
one
2-core
cable
single
phase
a.c. or
d.c.
one
3-core or
4-core
cable
3-phase
a.c.
one
2-core
cable
single
phase
a.c. or
d.c.
one
3-core or
4-core
cable
3-phase
a.c.

1

2

3

4

5

6

7

8

9

mm2

A

A

A

A

A

A

A

A

10

85

73

90

78

65

80

16

110

94

115

99

115

94

140

115

25

146

124

152

131

145

125

180

150

35

180

154

188

162

175

150

215

180

50

219

187

228

197

210

175

255

215

70

279

238

291

251

260

215

315

265

95

338

289

354

304

310

260

380

315

120

392

335

410

353

355

300

430

360

150

451

386

472

406

400

335

480

405

185

515

441

539

463

455

380

540

460

240

607

520

636

546

520

440

630

530

300

698

599

732

628

590

495

700

590

Voltage Drop (Per Amp Per Meter)

Conductor cross-sectional area

2-core cable d.c.

2 cables, single-phase a.c.

3 or 4 cables, 3-phase a.c.

2 cables, single- phase a.c.

3 or 4 cables,
3-phase a.c.

In ducts or in ground

In ducts or
in ground

1

2

3

4

5

6

mm2

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

6

7.9

7.9

6.8

7.9

6.5

10

4.7

4.7

4.0

4.7

3.9

16

2.9

2.9

2.5

2.9

2.6

r

x

z

r

x

z

25

1.850

1.350

0.160

1.900

1.600

0.140

1.650

1.900

1.600

35

1.350

1.350

0.155

1.350

1.150

0.135

1.150

1.350

1.200

50

0.980

0.990

0.155

1.000

0.860

0.135

0.870

1.000

0.870

70

0.670

0.670

0.150

0.690

0.590

0.130

0.600

0.690

0.610

95

0.490

0.500

0.150

0.520

0.430

0.130

0.450

0.520

0.450

120

0.390

0.400

0.145

0.420

0.340

0.130

0.370

0.420

0.360

150

0.310

0.320

0.145

0.350

0.280

0.125

0.300

0.350

0.300

185

0.250

0.260

0.145

0.290

0.220

0.125

0.260

0.290

0.250

240

0.195

0.200

0.140

0.240

0.175

0.125

0.210

0.240

0.210

300

0.155

0.160

0.140

0.210

0.140

0.120

0.185

0.210

0.190

400

0.120

0.130

0.140

0.190

0.115

0.120

0.165

0.190

0.180

Packing & Shipping
We provide you with the best product packaging design services, thereby allowing you to save more shipping charges

FAQ

1. Q: Are you the factory or the trading company?
A: We are the factory.
2. Q: How long is your guarantee Period?
A: We usually offer 1 year guarantee for our general products.
3. Q: How can I get the samples?
A: We can make the sample order. And usually you will charge for it.
But the samples fee will be return to you when you make the bulk order.
4. Q: Where is your factory? How can we visit your factory?
A: Our factory located in Jiaozuo city, Henan Province and our office is in Zhengzhou city. You could reach here by train and by air. We can pick you up in the airport and the railway station.
5. Q: What is your MOQ?
A: It`s base on the cable type or size. Please contact Ms. Melon. She will offer you the details.

Factory

Established in 2004, Henan Hongda Cable Co., Ltd, is dedicated into manufacturing various types of electric power wire and cable. Today, Henan Hongda has grown into an integrated system solution provider in electric power distribution industry, extending the business from power cable and electric wire manufacture to electric power distribution system design, and electric distribution system construction and installation.
Today, Henan Hongda has grown into an integrated system solution provider in electric power distribution industry, extending the business from power cable and electric wire manufacture to electric power distribution system design, and electric distribution system construction and installation.

Our Service

1. Design wire and cable according to your real application
2. Optimized reel size for freight cost saving
3. Customized package to feature your brand
4. Short lead time to meet your urgent demand
5. Diversified delivery terms for your options
6. Quick response (24 hours on line)
7. Professional knowledge for clear answer to your any question
8. Comprehensive technical documents to support your tender bidding
9. One-year limited warranty for our wire and cable
10. Cable sample available
11. Specify the cable only according to the location
12. OEM is available
13. Abundant cables and wires for your option

Contact Us

Ms. Melon Liu
************************************************************************************************

Tel: +86 371 55367868 / 55367868 Fax: +86371 55367870
Mob.: +86 18339931106
Henan Hongda Cable Co., Ltd http://hongdacable
Changping Road 3,Zhandian NewDistrict,Wuzhi County,Jiaozuo,Henan Province, China
Office Add: Room2108,Yaxing Times Square,Zhengzhou,Henan,China. P.C. 450000
************************************************************************************************

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.