4X95+50mm2 Copper XLPE Insulated PVC Sheath Electrical Power Cable
Product Description
CONSTRUCTION: CU/XLPE/PVC or PE
Operation characteristic
The maximum operating temperature of cores shall not exceed 90ºC ween the cable used for a long period. The temperature of cores shall not exceed 250ºC at short circuit for 5 seconds. The ambient temperature should not be below 0ºC during installation.
The permissible bending radius for cable should be the permissible bending radius for cable shall be complied with the regulation as below:
For single-core No armoured cable: R>20(D+d)±5% For multi-core:R>15(D+d)±5%
Armoured cable:R>15(D+d)±5% For multi-core:R>12(D+d)±5%
Where:R-being radius(mm) D–overall diameter of the cable(mm)
d-diameter of conductor(mm)
The single core cable of using in AC circuit shall be without armour or with steel wire armour and shall not be laid in magnetic ducts.
Main Technical Properties
Rated voltage of cable | 0.6/1(1.2)KV |
D.C. Resistance of conductor | According to GB/T3956-2008 or IEC 60228-2004 |
Power frequency withstand voltage test for 5 minutes | No breakdown at 3.5 KV |
Hot set test for insulation,200ºC 15 min with pressure 20N/cm2 Load elongation |
≤175% |
Max permanent elongation after cooled | ≤15% |
Installation and operation condition of cable
In air:
1. The single-core cables are parallel laid,the distance between the cable center is 2 times of the cable diameter for cross-section area of conductor≤185mm² and 90mm for cross sectional area of conductor ≥240mm²
2. Ambient air temperature:40ºC
3. Max.Continuous operating temperature of conductor:70ºC
Current rating factors for variation in ambient air temperature
Ambient air temperature | 20ºC | 25ºC | 30ºC | 35ºC | 40ºC | 45ºC |
Rating factor | 1.29 | 1.22 | 1.15 | 1.08 | 1.0 | 0.91 |
Direct in the ground:
1. The single-core cables are installed separately,the distance between the cable center is 2 times of cable diameter.
2. Soil temperature:25ºC
3. Max. Continuous operating temperature of conductor:70ºC
4. Thermal resist of soil:1.0ºC.m/W
5. Depth of laying:0.7m
Current rating for variation in soil temperature
Soil temperature | 20ºC | 25ºC | 30ºC | 35ºC | 40ºC |
Rating factor | 1.04 | 1.0 | 0.96 | 0.92 | 0.87 |
Main technical data :
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Cable size |
Conductor type | Nominal thickness of XLPE insulation(mm) | Nominal thickness of PVC or PE sheath(mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 20 0 C (Ω/km) | |||
Phase core |
Earth core |
Phase core |
Earth core |
Phase core |
Earth core |
|||
4×2.5+1.5mm 2 | RE | RE | 0.7 | 0.7 | 1.8 | 12.2 | 7.41 | 12.1 |
4×4+2.5mm 2 | RE | RE | 0.7 | 0.7 | 1.8 | 13.4 | 4.61 | 7.41 |
4×6+4mm 2 | RE | RE | 0.7 | 0.7 | 1.8 | 14.7 | 3.08 | 4.61 |
4×10+6mm 2 | RM | RE | 0.7 | 0.7 | 1.8 | 17.8 | 1.83 | 3.08 |
4×16+10mm 2 | RM | RM | 0.7 | 0.7 | 1.8 | 30.8 | 1.15 | 1.83 |
4×25+16mm 2 | SM | RM | 0.9 | 0.7 | 1.8 | 23.2 | 0.727 | 1.15 |
4×35+16mm 2 | SM | RM | 0.9 | 0.7 | 1.8 | 25.1 | 0.524 | 1.15 |
4×50+25mm 2 | SM | SM | 1.0 | 0.9 | 1.9 | 28.6 | 0.387 | 0.727 |
4×70+35mm 2 | SM | SM | 1.1 | 0.9 | 2.1 | 32.8 | 0.268 | 0.524 |
4×95+50mm 2 | SM | SM | 1.1 | 1.0 | 2.2 | 37.4 | 0.193 | 0.387 |
4×120+70mm 2 | SM | SM | 1.2 | 1.1 | 2.4 | 41.4 | 0.153 | 0.268 |
4×150+70mm 2 | SM | SM | 1.4 | 1.1 | 2.5 | 45.2 | 0.124 | 0.268 |
4×185+95mm 2 | SM | SM | 1.6 | 1.1 | 2.7 | 50.7 | 0.0991 | 0.193 |
4×240+120mm 2 | SM | SM | 1.7 | 1.2 | 2.9 | 56.8 | 0.0754 | 0.153 |
4×300+150mm 2 | SM | SM | 1.8 | 1.4 | 3.1 | 62.8 | 0.0601 | 0.124 |