Product Description

Basic Information
1. Standard: IEC60227, HD22.4, NFC-32-12-4.
2. Voltage: 450/750V, 300/500V,300/300V
3. Conductor: Copper
4. Construction: Solid, Stranded wires, flexible
5. Numer of Cores: single core, two cores, 3 cores, multi-cores,
6. Material of insulation: PVC,EPR.
7. Insulation: PVC
8. Cross Section area of conductor: 0.5mm2, 1mm2, 2mm2, 1.5mm2, 6mm2, 10mm2……….300mm2

Type Name
BV Copper conductor PVC insulated cable
BVR Copper conductor PVC insulated flexible cable
BVV Copper conductor PVC insulated PVC sheathed round cable
BVVB Copper conductor PVC insulated PVC sheathed flat cable
RVS Copper conductor PVC insulated stranded cable for flexible connecting

Structure of Product

1.Conductor
2.Insulation
3.Sheath

Application
It applies to electrical appliance, instrument and telecom device with rated voltage up to and including 450/750V.

The main features of the flame retardant PVC cable or wire is hard to get fair or that the continuous burning of cables is very limited when it is on fire. It applies to the places with special demands for flame retardant property. Flame retardant cable is classified as class A, B or C. Among the 3 classes, class A is the best in aspect of flame retardance.

Fire-resistance cable can operate normally for some time when it is burning except that it can transmit electrical power under normal condition. It is used in the places with special demands for fire resistance property.

The Main Features
1. Rated voltage U0/U is 450/750V, 300/500V, or 300/300V.

2. Permissible continuous working temperature of cable conductor
–for type of cable RV-90 and BV-90, the temperature should be not more than 90ºC
–for others, the temperature should be not more than 70ºC.

3. Ambient temperature should be not less than 0ºC, and permissible bending radius of cable for fixed connecting should be as follows during installation.

4. Flame retardant cable should pass the test of bunched cables or wires under fire conditions which is described in the standards of GB/T18380.3-2001.

5. Fire resistant cable should pass the test of fire resistant stipulated in the standards of GB/T19216.21-2003.

Key Technical Parameter
60227 IEC 01(BV) GB/T5023-2008

Nominal
cross- section
mm2
Conductor
Type
Upper limit Of O.D.
mm
Max.D.C.
resistance at 20ºC
Ω/km
Min.insulation
resistance
at 70ºC
MΩ·km
Approx.
ampacity A
Reference
weight
of cable
kg/km
1.50 1 3.2 12.1 0.011 25 20.0
1.50 2 3.3 12.1 0.010 25 21.5
2.50 1 3.9 7.41 0.010 34 31.8
2.50 2 4.0 7.41 0.009 34 34.8
4.00 1 4.4 4.61 0.0085 44 46.8
4.00 2 4.6 4.61 0.0077 44 50.3
6.00 1 5.0 3.08 0.0070 58 66.50
6.00 2 5.2 3.08 0.0065 58 71.00
10 2 6.7 1.83 0.0065 79 116.0
16 2 7.8 1.15 0.0050 111 180
25 2 9.7 0.727 0.0050 146 277
35 2 10.9 0.524 0.0040 180 375
50 2 12.8 0.387 0.0045 282 536
70 2 14.6 0.268 0.0035 281 706
95 2 17.1 0.193 0.0035 344 977
120 2 18.8 0.153 0.0032 397 1231
150 2 20.9 0.124 0.0032 456 1503
185 2 23.3 0.0991 0.0032 519 1870
240 2 26.6 0.0754 0.0032 592 2457
300 2 29.6 0.0601 0.0030 685 3053
400 2 33.2 0.0470 0.0028 799 3948