4 Core Copper XLPE Insulated Armoured Underground Cable

4 Core Copper XLPE Insulated Armoured Underground Cable

4 Core Copper XLPE Insulated Armoured Underground Cable

4X185sq. mm

Construction, Underground, Industrial, Power Station

Low and Medium Voltage Cable

DC Cable

XLPE

PVC

Round Wire

Bare Copper Wire

ISO

YJV

Jytop

ASTM, AS/NZS, BS, CSA, DIN, IEC…

Ce, ISO 9001

JYTOP

Packed in Reels

as per popular standards or clients's requirement

Zhengzhou, China

8544492100

Product Description

4 Core Copper XLPE Insulated Armoured Underground Cable

Product Description:
The PVC insulated power cable and fire resistant cable are suitable for fixed laying in power transmission and distribution lines with A. C. 50Hz and voltage rating of up to or including 6KV.

1. Conductors: Copper or aluminum.
2. Both armored and non-armored type power cables are available.
3. Voltage rating: 0.6/1kV 3.6/6kV.
4. PVC or PE sheathed.
5. Number of cable cores: One core (Single core), two cores(Double cores), three cores,
Four cores (Four Equal-section-area cores or three equal-section-area cores and one smaller section area neutral core),
Five cores (Five equal-area cores or three equal-section-area cores and two smaller section area neutral cores).
6. Standards: Chinese national standard GB 12706 and GB 12666.6(equivalent to IEC 60502 and IEC 60331)IEC, BS, DIN, ASTM, CSA, NFC, AS, GOST etc. Or other special characteristics as customers request.

Application conditions
1. The long-time permissible operation temperature of conductor shall not be higher than 70oC.
2. Conductor maximum short circuit (not more than 5 seconds) temperature shall not be higher than 160 ºC.
3. The power cable is not limited by drop in level when being laid, and the ambient temperature shall not be lower than 0ºC.
If so, the cable should to be preheated.
4. Perfect chemical stability, resistant against acids, alkalis, grease and organic solvents, and flame.
5. Light weight, perfect bending properties, installed and maintained easily and conveniently.

Note: RE= round conductor RM = stranded conductor SM=sectional conductor

Cable size Conductor type Nominal thickness of XLPE insulation(mm) Nominal thickness of PVC or PE sheath(mm) Approx. cable overall diameter (mm) Max. D.C resistance @ 20ºC(Ω/km)
4×1.5mm 2 RE or RM 0.7 1.8 10.5 12.1
4×2.5mm 2 RE or RM 0.7 1.8 11.5 7.41
4x4mm 2 RE or RM 0.7 1.8 12.6 4.61
4x6mm 2 RE or RM 0.7 1.8 13.8 3.08
4x10mm 2 RM 0.7 1.8 16.9 1.83
4x16mm 2 RM 0.7 1.8 19.5 1.15
4x25mm 2 SM 0.9 1.8 21.3 0.727
4x35mm 2 SM 0.9 1.8 23.4 0.524
4x50mm 2 SM 1.0 1.9 26.8 0.387
4x70mm 2 SM 1.1 2.0 30.6 0.268
4x95mm 2 SM 1.1 2.1 34.9 0.193
4x120mm 2 SM 1.2 2.3 38.4 0.153
4x150mm 2 SM 1.4 2.4 42.5 0.124
4x185mm 2 SM 1.6 2.6 47.4 0.0991
4x240mm 2 SM 1.7 2.8 53.4 0.0754
4x300mm 2 SM 1.8 3.0 59.0 0.0601