CAAI CABLE

Phase Insulated with Bare Neutral

Solid or Stranded

Overhead

Aluminum or Aluminum Alloy or Aluminum & Steel

No

PE or XLPE

Round Wire

Overhead

ISO9001, CE, CCC

Jytop

Black,Red,Yellow,Blue,Brown,Green

16mm 25mm 35mm

0.6/1kv

2,3,4,5

Aluminum or Aluminum Alloy or ACSR

Henan

4X16

4X25

Caai Cable

Caai

JYTOP

Packed in Reels

as per IEC, ASTM, BS, Sans

Zhengzhou, China

8544492100

Product Description

0.6/1kv CAAI Cable, CAAI-S Cable

ASTM BS Standard 0.6/1kv pvc/xlpe/pe insulatedDuplex aerial bundle cable, abc cable

We can supply this conductor according to different recognized standards, such as IEC Standard, ANSI/ICEA , NFC, NBR, ITP ,customer special specification also can be satisfied.

Application: ABC cable Conllie, duplex cable, service drop, overhead cable.
The basic construction is as following:
A, 2, 3, 4 power cores consisting of strandard aluminium conductor, insulated with XLPE or PVC, PE.
B, One sheath lighting aluminium conductor with XLPE insulation(optional)
C, One messenger Al-alloy (bare or covered)

It meets or exceeds the following specification:
A, Aluminium wire, 1350-H19 for electrical purposes.
B, Aluminium conductor, concentric-lay-stranded.
C, Aluminium conductor, concentric-lay-stranded, coated steel reinforgorced(ACSR, AAC, AAAC)
D, Concentric-lay stranded 6201-T81 conductors.
E, Compressed Round Stranded Aluminium consuctors using single input wire.

Specifications:
Conductor: Aluminum
Insulation: PVC, XLPE, PE
Application: Overhead line
Core: 2.3, 4 core( Duplex, triplex, quoduplex)

Code word

AWG or kcmil Bare Neutral Messenger Phase Conductor

Weight
Kg/km

Allowable
Ampacities(A)
ACSR Rated strength Ibs. AAC Insul
Thick.
mm
XLPE PE
Number Dia mm Number Dia mm Number Dia mm
Setter 1*6AWG+1*6AWG 1 1.68 6 1.68 1190 1 4.11 1.14 111 85 70
Bull 1*1/0AWG+1*1/0AWG 1 3.37 6 3.37 4380 19 1.89 1.52 427 205 160
Shepherd 1*6AWG+1*6AWG 1 1.68 6 1.68 1190 7 1.56 1.14 113 85 70
Eskimo 1*4AWG+1*4AWG 1 2.12 6 2.12 1860 1 5.19 1.14 171 115 90
Terrier 1*4AWG+1*4AWG 1 2.12 6 2.12 1860 7 1.96 1.14 173 115 90
Chow 1*2AWG+1*2AWG 1 2.67 6 2.67 2850 7 2.47 1.14 266 150 120

Aerial Bundle Conductor-ABC(South Africa Standard Sizes)-SANS 1418-1

Table 01

Type of conductor or core Norminal cross-sectional area mm2 Nubmer of wires
Min.
Diameter of conductormm Resistanceat 20ºC Ω/km Max. Breaking force(N) Thickness of insulation (mm) Outer diameter of core(mm)
Min. Max. Min. Average Min. Min. Max.
Phase or auxiliary or non-strain-bearing netural(aluminium) +16 6 4.6 5.1 1.91 2070 1.2 0.98 7.0 7.8
25 6 5.8 6.3 1.2 3300 1.4 1.16 8.6 9.4
35 6 6.8 7.3 0.868 4500 1.6 1.34 10.0 10.9
50 6 7.9 8.4 0.641 6200 1.6 1.34 11.1 12.0
70 12 9.7 10.2 0.443 8900 1.8 1.52 13.3 14.2
95 15 11.0 12.0 0.320 12300 1.8 1.52 14.6 16.0
120 15 12.5 13.5 0.253 15600 1.8 1.52 16.3 17.5
150 15 13.9 15.0 0.206 19200 1.8 1.52 17.1 18.6
Service connection(aluminium) 16 6 4.6 5.2 1.91 2070 1.2 0.98 7.0 8.0
25 6 5.6 6.5 1.2 3300 1.4 1.16 8.6 9.6
Service connection(copper) 10 6 4.2 1.83 3600 1.2 0.98 6.2 7.0
16 6 5.3 1.15 5760 1.2 0.98 7.2 8.0
25 6 6.6 0.727 8750 1.4 1.16 8.6 9.6
Number and nominal diameter of wires
mm
Supporting
core(aluminium alloy)
54.6 7×3.15 9.2 9.6 0.630 16600 1.6 1.34 12.3 13.0
70 7×3.50 10.0 10.4 0.500 20100 1.6 1.34 12.9 13.6
+Auxiliary conductors or cores only

When a supporting core is specified in a tender invitation,the combinations listed in Table 02 below:

Table 02

1 2
Nominal cross sectional area of supporting conductor mm2 Nominal cross-sectional areas of phase conductors mm2
54.6 25,35,50,70,95
70 70,95,120
95 95,120,150

—————————————————————————————————————————–

Aerial Bundle Conductor-ABC(South Africa Custimized Size Specification)

Table 03

Type of conductor or core Norminal cross-sectional area mm2 Nubmer of wires Diameter of conductormm Resistanceat 20ºC Ω/km Max. Breaking force(N) Thickness of insulation (mm) Outer diameter of core(mm)
Min. Max. Min. Average Min. Min. Max.
Phase or auxiliary or non-strain-bearing netural(aluminium) 16 7/1.65 4.6 5.1 1.91 2070 1.2 0.98 7.0 7.8
25 7/2.15 5.8 6.3 1.2 3300 1.4 1.16 8.6 9.4
35 7/2.55 6.8 7.3 0.868 4500 1.6 1.34 10.0 10.9
50 7/2.99 7.9 8.4 0.641 6200 1.6 1.34 11.1 12.0
70 14/2.59 9.7 10.2 0.443 8900 1.8 1.52 13.3 14.2
95 19/2.59 11.0 12.0 0.320 12300 1.8 1.52 14.6 16.0
120 19/2.99 12.5 13.5 0.253 15600 1.8 1.52 16.3 17.5
150 30/2.59 13.9 15.0 0.206 19200 1.8 1.52 17.1 18.6
Service connection(aluminium) 16 7/1.65 4.6 5.2 1.91 2070 1.2 0.98 7.0 8.0
25 7/2.15 5.6 6.5 1.2 3300 1.4 1.16 8.6 9.6
Service connection(copper) 10 7/1.35 4.2 1.83 3600 1.2 0.98 6.2 7.0
16 7/1.69 5.3 1.15 5760 1.2 0.98 7.2 8.0
25 7/2.19 6.6 0.727 8750 1.4 1.16 8.6 9.6
Supporting core(aluminium alloy) 16 7/1.71 5.1 5.2 2.053 5070 1.4 1.16 7.9 8.0
25 7/2.15 6.4 6.5 1.314 8000 1.4 1.16 9.2 9.3
35 7/2.48 6.6 7.5 0.986 10300 1.6 1.34 10.7 10.8
50 7/2.89 7.7 8.4 0.720 14200 1.6 1.34 11.9 12.0
54.6 7/3.15 9.2 9.6 0.630 16600 1.6 1.34 12.3 13.0
70 7/3.50 10.0 10.4 0.500 20100 1.6 1.34 12.9 13.6