Standard Building Wires & Cables Cable Thw-90 6mm2 10 mm2
More product about Building CablesProduct Description
Standard wires & cables <1kV
THW-90 450/750 V less than or equal to 10 mm2
Description
General application in fixed installations, resistant to humidity and heat.
STANDARD
International: IEC 60228
National: NTP 370,252; NTP-IEC 60228; UL 2556
DESCRIPTION
Application:
In fixed installations, in buildings, inside premises with a dry or humid environment, control panel connections and, in general, in all installations that require greater current capacity to the TW-80 cable.
Construction:
1. Conductor: Compressed soft copper, class 2.
2. Insulation: Double layer PVC compound.
Main features:
Good dielectric strength, resistance to moisture, grease, oil and heat up to service temperature. Does not spread VW-1 flame.
Section:
From 2.5 mm2 to 10 mm2.
Packaging:
From 2.5 mm2 to 6 mm2 in 100 meter rolls.
10 mm2 cables on reels.
cable thw Colour:
At the request of the client.
ELECTRICAL CHARACTERISTICS
Nominal operating voltage Uo / U (Um) | 450/750 V |
Dielectric strength | 2.5kV |
Dielectric Rigidity Time Vac to insulation | 5min |
CHARACTERISTICS OF USE
Maximum operating temperature | 90 ° C |
Emergency overload temperature | 130 ° C |
Maximum short-circuit conductor temperature | 250 ° C |
cable thw DIMENSION
Name | Section | Diam. Conductor (mm) | Insulation Thickness (mm) | Cable Diameter (mm) | Approx. Weight (kg/km) |
THW-90 2,5 mm2 | 2.5 | 1.9 | 0.8 | 3.6 | 32 |
THW-90 4 mm2 | 4 | 2.4 | 0.8 | 4.1 | 47 |
THW-90 6 mm2 | 6 | 3.0 | 0.8 | 4.7 | 67 |
THW-90 10 mm2 | 10 | 3.7 | 1.1 | 6.0 | 111 |