Primary Ud Cable, 15 Kv, Cu/Tr-XLPE/Neutral/PVC (AEIC CS 8/ICEA S-94-649)

Primary Ud Cable, 15 Kv, Cu/Tr-XLPE/Neutral/PVC (AEIC CS 8/ICEA S-94-649)
Primary UD Cable
Underground
Low and Medium Voltage Cable
DC Cable
XLPE
PVC
Round Wire
Bare Copper Wire
ISO, CCC
Primary Ud Cable
Boan
15 Kv
B
2-1000 AWG or Kcmil
100% or 133%
1/3 or Full
Copper Wire
14/12/10/9 AWG
DingAn or OEM
Heated Steel-Wooden Drum/Steel Drum
SGS
Jiangsu Yixing, China
8544601200

Product Description

Primary UD Cable, 15 KV, CU/TR-XLPE/Neutral/PVC (AEIC CS 8/ICEA S-94-649)
Applications:
Predominantly used for primary underground distribution; Suitable for use in wet or dry locations, direct burial, underground duct, and where exposed to sunlight. To be used at 15, 000 volts or less and at conductor temperatures not to exceed 90° C for normal operation.
Specifications:
Primary UD Cable meets or exceeds the following ASTM specifications:
B-3 Soft Annealed Copper Wire.
B-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft.
B-230 Aluminum, 1350-H19 Wire for Electrical Purposes.
B-231 Aluminum 1350 Conductors, Concentric-Lay-Stranded.
B-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes.
Primary UD Cable is manufactured to the latest edition of the following specifications, and in case of specification conflicts, in the order listed:
ANSI/ICEA S-94-649
AEIC CS-8
RUS U-1
Construction:
The phase conductor is concentrically stranded, compressed soft copper or 1350-H16/26 aluminum alloy. The cable is composed of the conductor with moisture block in the strands, covered by a semi-conducting cross-linked polyethylene strand shield, a tree-retardant cross-linked polyethylene primary insulation, and a semi-conducting cross-linked polyethylene insulation shield. Conductors are available with either 100% or 133% insulation levels. A concentric neutral of bare copper wires and an insulating polyethylene jacket is applied over the insulation shield. The cable is identified by surface print on the jacket and with the lightning bolt symbol for supply cables indented in the jacket. A semi-conducting polyethylene jacket is available upon request.
Maximum Conductor Normal Operation: – 90O C;
Emergency Overload: – 130O C
Temperatures: Short Circuit – 250 C
Application: Medium voltage power cable for single phase underground distribution (UD), including getaway systems in low profile substations.
Size AWG or kcmil Number of Strands Nominal OD Over Insulation in 1/3 Neutral Full Neutral
Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft
Copper 100% Insulation Level (175 mil)
2 1 0.68 6 14 80 1.05 610
2 7 0.68 6 14 80 1.05 610 16 14 80 1.05 743
1 19 0.71 7 14 80 1.09 694 13 12 80 1.12 883
1/0 19 0.75 9 14 80 1.13 808 16 12 80 1.16 1034
2/0 19 0.80 11 14 80 1.17 942 13 10 80 1.25 1247
3/0 19 0.85 14 14 80 1.22 1115 16 10 80 1.30 1481
4/0 19 0.90 18 14 80 1.28 1332 16 9 80 1.38 1790
250 37 0.96 13 12 80 1.37 1519 25 10 80 1.41 2095
350 37 1.06 18 12 80 1.49 2011 22 8 80 1.59 2826
500 37 1.19 17 10 80 1.66 2741 31 8 110 1.78 3947
750 61 1.38 20 9 110 1.94 4008
1000 61 1.53 26 9 110 2.12 5170
Copper 133% Insulation Level (220 mil)
2 7 0.77 6 14 80 1.14 672 16 14 80 1.14 805
1 19 0.81 7 14 80 1.18 759 13 12 80 1.21 947
1/0 19 0.85 9 14 80 1.22 875 16 12 80 1.25 1100
2/0 19 0.89 11 14 80 1.26 1012 13 10 80 1.34 1316
3/0 19 0.94 14 14 80 1.31 1187 16 10 80 1.39 1553
4/0 19 1.00 18 14 80 1.37 1407 16 9 80 1.47 1865
250 37 1.05 13 12 80 1.48 1622 25 10 80 1.52 2198
350 37 1.16 18 12 80 1.58 2097 22 8 80 1.68 2912
500 37 1.28 17 10 110 1.82 2943 31 8 110 1.87 4046
750 61 1.47 20 9 110 2.03 4118
1000 61 1.62 26 9 110 2.21 5291